Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop G
Sequence Number 6
Notes
Date Text
2008-03-19 08:31:06 
  
  
  
 PASSED/PROVISO
  
 THE PIPE SIZING FOR THE SUPPLY LINES AND SHUT OFF
 VALVES TO EACH 200 CFH UNIT SHALL BE 1-1/4" AND THE
 INLET PRESSURE SHALL BE INDICATED AS 1/2 PSI. REVISION
 REQUIRED AT THE TIME OF APPLICATION FOR THE GAS
 PERMIT.
  
 MANUF. SPECIFICATION SHEETS REQUIRED SHOWING LISTING
 AND BTU LOAD FOR FIXTURES REQUIRED AT THE TIME OF
 APPLICATION FOR THE GAS PERMIT.
  
 WELDING CERTIFICATIONS REQUIRED FOR WELDER AS WELL AS
 THE WELDING PROCEDURE AT THE TIME OF APPLICATION FOR
 THE GAS PERMIT.
  
  
  
  
  
 .