Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop P
Sequence Number 5
Notes
Date Text
2008-03-13 12:12:09 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEW: 3RD REVIEW:
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
 **********FROM PREVIOUS REVIEWS: 5TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********RESPONSE NOTED, BUT NOT ADDRESSED
 B. OK
 ____FOR LAVS:
 A. OK
 B. OK
 C. OK
 SHT A-803
 ___FOR W/C'S:
 A. OK
 ___FOR LAVS:
 A. OK
 B. OK
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********NO RESPONSE, NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 **********NO RESPONSE, NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. OK
  
 14. OK
 15. N/A
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
 ********RESPONSE NOTED, BUT THE PIPE SIZES ARE NOT
 SHOWN FOR MUCH OF THE PIPING, DFU'S ARE NOT INDICATED
 AS THEY ACCUMULATE IN THE SYSTEM, NOT ALL PIPING FOR
 THE FOOD PREP AREA PER SHT P-401 DETAIL 5,THE
 DOWNSTREAM VENT FOR THE DOMESTIC PUMP ROOM OFFSETS
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL.
 (SECTION 905.4). THE PIPING FOR THE GREASE INTERCEPTOR
 IS NOT SHOWN ON THE RISER DIAGRAM. THE BRANCH LINE FOR
 KEY NOTE 48, (WATER WALL), SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. VENTING DOES NOT
 REFLECT THE FLOOR PLAN IN SOME AREAS AND NOT SHOWN IN
 OTHERS. PIPING DOES NOT REFLECT THE FLOOR PLAN AT THE
 FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 & 60.
 THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. THE
 BRANCH LINE FOR THE ICE MACHINE, (9), IS SHOWN UPSTREAM
 OF THE DOUBLE WYE FITTING ON THE FLOOR PLAN, BUT
 DOWNSTREAM OF THE DOUBLE WYE ON THE RISER DIAGRAM. THE
 RISER DIAGRAM FOR THE PUBLIC TOILET ROOMS DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR DRAIN LINES ARE SHOWN
 ON THE BRANCH LINE TO THE LAVS ON THE RISER DIAGRAM,
 BUT OFF THE BRANCH LINE TO THE WATER CLOSETS, URINAL ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER DIAGRAMS AND
 THE FLOOR PLAN.
 **********RESPONSE NOTED, BUT THE PIPING FOR THE FOOD
 PREP AREA, (3 COMP. SINK, HAND SINK, AND FLOOR DRAIN),
 IS NOT SHOWN ON THE RISER DIAGRAM AS WELL AS THE
 ISOMETRIC PIPING FOR THE GREASE INTERCEPTOR AS
 INDICATED. PIPING DOES NOT REFLECT THE FLOOR PLAN AT
 THE FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 &
 60. THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON
 THE FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. AFTER
 CHECKING THE DRAINAGE FIXTURE UNITS FOR ALL RISERS AND
 BRANCH LINES IT APPEARS THAT THE DFU'S INDICATED ARE
 NOT CORRECT IN MANY AREAS. ALSO THE PIPE SIZE FOR THE
 BUILDING DRAIN SHALL BE INCREASED TO 8" DOWNSTREAM OF
 RISERS 24 THRU 27 AND 44 THRU 47 AS THE DFU'S ADD UP TO
 742. 6" IS SHOWN.
  
 32A. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN MANY AREAS WHERE THE BRANCH
 LINES CONNECT TO THE MAIN WATER LINES, (SEE RISER
 BRANCH TO RISERS 53, 54, 55,45, 46, 47 & THEDISH
 SANITIZER,AT THE PUBLIC TOILET ROOMS, RISER NUMBERS
 DO NOT REFLECT THE FLOOR PLAN FOR RISERS 28, 29 & 30,
 (TWO SETS). THE REQUIRED WATER HAMMER ARRESTORS SHALL
 BE INDICATED PER SECTION 604.9, (ICE MAKERS, DISH
 WASHER, WASH MACHINES OR ANY OTHER QUICK CLOSING
 VALVE). SOME LINES HAVE THE HOT WATER LINES LABELED AS
 COLD WATER AND SOME LINES HAVE THE COLD WATER LINES
 LABELED AS HOT WATER LINES. IN THE PUBLIC TOILETS
 FIXTURES 3B HAVE THE COLD ON THE LEFT AND THE HOT ON
 THE RIGHT. (SECTION 607.4). SHOW ALL VALVES REQUIRED
 PER SECTIONS 606.1 & 606.2 ON THE RISER DIAGRAM. SHOW
 ALL PIPE SIZES PER SECTION 604. SHT P507 DETAIL 2 THE
 STANDARD TOILET AND THE URINAL ARE MISLABELED AND THE
 FIXTURE INDICATED AS P5A, (SHOWER?), IS NOT INDICATED
 ON THE WATER RISER DIAGRAM. PLEASE CLARIFY.
 **********RESPONSE NOTED, BUT THE PIPING TO THE DISH
 SANITIZER AND THE PUBLIC TOILETS STILL DOES NOT REFLECT
 THE FLOOR PLAN.--THE REQUIRED WATER HAMMER
 ARRESTORS SHALL BE INDICATED PER SECTION 604.9, (ICE
 MAKERS, DISH WASHER, WASH MACHINES OR ANY OTHER QUICK
 CLOSING VALVE). THIS IS A REQUIREMENT FOR THE WATER
 SYSTEM AND SHALL BE SHOWN ON THE WATER SYSTEM.
  
 33 OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM AND THE
 FLOOR PLAN STATE "FOR CONT. SEE P101C". THE SHT P101C
 SUBMITTED IS FOR HOMEWOOD SUITES, NOT SPRINGHILL
 SUITES. RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO PIPING TO THE RISERS FOR THE STORM DRAINAGE AT THE
 "PORTE COCHERE" AS WELL AS THE PIPING FOR THE DRAINAGE
 TO THE EAST SIDE OF THE BUILDING. (NO SHT A101C
 SUBMITTED FOR THE SPRINGHILL SUITES). SOME PIPE SIZING
 IS INCORRECT. (SEE 4" HORIZONTAL INDICATED FOR 2068SF).
 SHOW ALL PIPE SIZES, AND INDICATED THE SQUARE FOOTAGE
 AS IT ACCUMULATES IN THE SYSTEM.
 **********RESPONSE NOTED BUT THE PIPE SIZING IS STILL
 INCORRECT FOR THE PIPING FOR THE 4" 2371SF 1/8"-FT,
 ZONES 1 & 2. ALSO THE PIPING SHALL BE UNIFORM IN SLOPE.
 THE PIPING SHOWS 1/4"-FT TO 1/2"-FT IN ONE AREA AND
 1/8"-FT TO 1/2"-FT IN TWO OTHER AREAS. (SEE ZONES 7 &
 1). SECTION 704.1. ONE LINE DOES NOT INDICATE THE SLOPE
 OR PIPE SIZE ON THE HORIZONTAL 2344SF. (ZONE 6 OFD).
 SECTION 106.1.2.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. OK
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3. ********RESPONSE
 NOTED, BUT THE RISER DIAGRAMS FOR DETAILS 5 & 6 ARE NOT
 SHOWN ON SHTS P507 OR P508. NO WATER TO THE HAND SINK
 NOR TO THE 3 COMPARTMENT SINK. NO SANITARY SHOWN TO THE
 HAND SINK, THE 3 COMPARTMENT SINK OR THE FLOOR DRAIN
 SHOWN IN DETAIL 5 SHT P401. THE FLOOR DRAIN SHALL
 CONNECT TO THE GREASE LINE, NOT THE SANITARY LINE.
 **********RESPONSE NOTED, BUT ISOMETRICS FOR DETAILS 5
 & 6 NOT ADDRESSED AS THEY ARE NOT ON SHTS P507 OR
 P508.
  
 3C. OK
 4C. OK
 5C. OK
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
 ********RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE NOT SHOWN ON THE WATER RISER DIAGRAMS. RISER 5/502
 NOW SHOWS P-7, (BREAK SINK), AND P-8, (LAUNDRY ROOM
 SINK), WHERE AS THE FLOOR PLAN SHOWS SHOWER/TUB.ALSO
 ON SANITARY RISER 48 FIRST FLOOR SHOWS TWO FIXTURES, P4
 & P-13, BUT ON THE FLOOR PLAN NO FIXTURES ARE SHOWN.
 PLEASE CORRELATE. SANITARY RISER 48 APPEARS TO RUN
 THROUGH THE BASE CABINET ON THE FIRST FLOOR. PLEASE
 CLARIFY.
 **********RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTORS ARE A WATER SUPPLY PIPING REQUIREMENT AND
 SHALL BE SHOWN ON THE PIPING FOR THE FIXTURES
 INDICATED. THE WATER RISER DIAGRAMS INDICATED IN
 COMMENT RESPONSE ARE NOT SHOWN ON SHEETS P507 OR P508.
  
 7C. OK
 8C. OK
 9C. OK
 10C. OK
  
 **********NEW COMMENT**********
  
 1D. SHTS P504 & P505 THE WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS THE WATER
 PIPING FOR THE MAINS IN THE CEILING OF THE FIRST FLOOR,
 BUT THE RISER DIAGRAMS SHOW THE WATER RISERS CONNECTING
 TO THE MAIN UNDERGROUND. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604.
 **********RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 2D. N/A PER R. BROWN.
  
 **********NEW COMMENT**********
  
 1E. MANY OF THE MARKS FOR FIXTURES ON THE FLOOR PLANS &
 WATER RISER DIAGRAMS DO NOT REFLECT THE FIXTURE MARKS
 CALLED OUT ON THE FIXTURE SCHEDULE ON SHT P601. PLEASE
 CORRELATE. (EXAMPLE ON ONE IS THE DRINKING FOUNTAIN AT
 THE PUBLIC TOILETS SHTS P101B & P508 INDICATED AS
 FIXTURE P5A, (ROLL IN SHOWER), AND IS NOT SHOWN ON SHT
 P507.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  