Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop M
Sequence Number 5
Notes
Date Text
2008-01-16 11:59:02*** PROVISO ***
 1) PER 2004 FBC/M 607.5.3 DUCT PENETRATIONS IN FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE
 DAMPERS INSTALLED IN ACCORDANCE WITH THEIR LISTING OR
 MEET THE EXCEPTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  
  