Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop G
Sequence Number 5
Notes
Date Text
2008-03-13 12:43:22DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 **********FROM PREVIOUS REVIEWS: 5TH REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. OK
 2. OK
 3. OK - NATURAL
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED. GAS REVIEW WILL STAY IN FAILED
 STATUS UNTIL MANUF. SPECIFICATION SHEETS WITH LISTING
 AND BTU'S THAT REFLECT THE RISER DIAGRAM ARE
 SUBMITTED.
 ********RESPONSE NOTED, BUT THE ONLY GAS MANUF.
 SPECIFICATION SHEET SUBMITTED ARE FOR THE WATER
 HEATERS. THE MANUF. SPECIFICATION SHEETS FOR THE DRYERS
 AND THE POOL HEATER ARE REQUIRED.
 **********RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DRYERS AND THE POOL HEATER DO NOT SHOW A LISTING, NOR
 DO THE BUT LOADS REFLECT THE RISER DIAGRAM. PLEASE
 INDICATE MODEL NUMBER.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]