Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 5
Notes
Date Text
2008-05-14 11:20:57** DENIED/TEMPORARY**
  
 1) NOTE: PLEASE SEE THE THIRD SET OF REVISED ENERGY
 CALCULATIONS COULD NOT BE LOCATED ATTACHED TO PLANS.
 ONLY TWO COMPLETE SETS OF DOCUMENTS WERE ATTACHED TO
 TWO OF THE SETS.
 PLANS ARE IN A FAILED STATUS UNTIL THIRD SET IS
 SUBMITTED. THE THIRD COPY MAY BE BROUGHT IN AT ANY TIME
 BEFORE ALL REVIEWS ARE DONE. IF THESE ARE OK REVIEW
 STOP WILL BE UPDATED TO A *P* STATUS.
 ** ONCE FIRE REVIEW IS DONE AND IF OK, WILL NEED TO
 RETAIN ONE COPY OF REVISED ELECTRICAL PLANS FOR FILE.
  
 2) NOTE: REDLINED PLANS FOR MAIN ELECTRICAL ROOM DOOR
 AS THE SWING DIRECTION NEEDS TO SWING OUT. ONE DOOR OK,
 THE OTHER SHOWS IN-SWING.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  