Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop P
Sequence Number 4
Notes
Date Text
2008-01-31 16:55:25 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEW: 3RD REVIEW: ********FROM
 PREVIOUS REVIEWS: 4TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
 ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND.
 PLEASE SUBMIT THE CALCULATIONS REQUESTED.
 ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT
 SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE
 SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR
 EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA
 SHOWING THE INFORMATION REQUESTED. ********RESPONSE
 NOTED, BUT CALCULATIONS WERE NOT SUBMITTED. HAVING DONE
 THE CALCULATIONS FOR ONE AREA, IT APPEARS THAT THE AREA
 DRAINS APPROXIMATELY 2784SF. THIS IS THE NORTHWEST
 CORNER. OTHER AREAS HAVE A MUCH SMALLER AREA, (TWO
 AREAS BETWEEN COL. LINES 4 & 8 ON THE EAST SIDE OF THE
 ROOF). SUBMIT THE CALCULATIONS FOR EACH AREA SHOWING
 THE SQUARE FOOTAGE OF EACH AREA, WITH 1/2 THE AREA OF
 ALL VERTICAL WALLS, AS WELL AS ALL ROOF AREAS THAT
 DRAIN ONTO THE ROOF FROM ABOVE. ALSO THE ROOF FOR THE
 STAIRWELL IS NOT INDICATED ON THE PLUMBING SHEET AND NO
 INDICATION OF HOW THE ROOF WILL BE DRAINED. PRIMARY AND
 SECONDARY ROOF DRAINS ARE REQUIRED FOR THE ROOF OVER
 THE STAIRWELL. (INFORMATIONAL, THE STAIRWELL IS NOT
 INDICATED ON SHT A-201 DETAIL 1, SHT A-301 DETAIL 2,
 NOR IS IT SHOWN ON THE ROOF PLAN SHT P105).
  
 9. OK
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE SHOWER, THE TUB, NOR THE SINK.
 ********RESPONSE NOTED, BUT NOT ADDRESSED FOR THE
 SHOWER, TUB, SINK.
  
 11. OK
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING
 IS NOT SHOWN:
 A. OK
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE
 ********RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS
 NOT SHOWN ON SHT A-401.
 D. OK
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 B. 11-4.18.4 FLUSH CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED (HEIGHT)
 ____FOR LAVS:
 A. OK
 B. OK
 C. OK
 SHT A-803
 ___FOR W/C'S:
 A. OK
 ___FOR LAVS:
 A. OK
 B. OK
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. OK
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 OK
 B. 11-4.24.5 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 ********NOT ADDRESSED
 C. 11-4.24.7 FAUCETS (TYPE)
 ******NOT ADDRESSED
 ****NO RESPONSE, NOT ADDRESSED
 ******RESPONSE NOTED, NOT COMPLETLY ADDRESSED
 ********RESPONSE NOTED, BUT NOT FAUCET NOT APPROVED.
 (SEE ATTACHED SHEET)
  
  
 15. N/A
  
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN KEYNOTES #47 &
 #48 ON SHT P101 AND RELATED WATER PIPING THAT INDICATES
 WATER TO THE WATER WALL FEATURE? BACKFLOW PREVENTION IS
 REQUIRED FOR THE WATER SUPPLY. PLEASE INDICATE METHOD.
 SECTION 608.--PLEASE INDICATE THE DRAINAGE PIPING
 ON THE FLOOR PLAN AND MAKE SURE IT IS REFLECTED IN AN
 ISOMETRIC RISER DIAGRAM.
 ********RESPONSE NOTED, BUT THE WATTS 709 IS A DOUBLE
 CHECK VALVE ASSEMBLIES AND IS NOT APPROVED FOR THIS
 APPLICATION. (THE MINIMUM SIZE IS 2-1/2"). A WATTS N36
 VACUUM BREAKER, (OR EQUIVALENT), INSTALLED AT THE TOP
 OF THE DROP WILL BE SUFFICIENT. PLEASE CORRECT KEYNOTE
 21 ON SHT P101B
  
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL SANITARY
 PIPING NOT SHOWN. THE PIPING FOR ALL SYSTEMS IS NOT
 VERY LEGIBLE. THE PIPING IS NOT SHOWN TO MANY RISERS,
 AND IN MANY CASES THE PIPING IS HARD TO FOLLOW BECAUSE
 IS IS COVERED BY DARKER/BOLDER LINES OR OTHER SYSTEMS.
 IN SOME CASES IT IS NOT CLEAR WHAT SYSTEM CONNECTS TO
 WHAT RISER. SOME FIXTURES HAVE NO WATER PIPING SHOWN.
 SEE NEW COMMENTS FOR SHT P101 AT THE END OF THESE
 COMMENTS.
 ********RESPONSE NOTED, BUT THE BRANCH PIPING TO SANT.
 RISERS 13, 14, 16, 17 & 18 IS STILL NOT SHOWN ON THE
 FLOOR PLAN.
  
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
 ********RESPONSE NOTED, BUT THE PIPE SIZES ARE NOT
 SHOWN FOR MUCH OF THE PIPING, DFU'S ARE NOT INDICATED
 AS THEY ACCUMULATE IN THE SYSTEM, NOT ALL PIPING FOR
 THE FOOD PREP AREA PER SHT P-401 DETAIL 5,THE
 DOWNSTREAM VENT FOR THE DOMESTIC PUMP ROOM OFFSETS
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL.
 (SECTION 905.4). THE PIPING FOR THE GREASE INTERCEPTOR
 IS NOT SHOWN ON THE RISER DIAGRAM. THE BRANCH LINE FOR
 KEY NOTE 48, (WATER WALL), SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. VENTING DOES NOT
 REFLECT THE FLOOR PLAN IN SOME AREAS AND NOT SHOWN IN
 OTHERS. PIPING DOES NOT REFLECT THE FLOOR PLAN AT THE
 FOLLOWING RISERS: 5, 6, 7, 8, 9, 10, 18, 19, 22 & 60.
 THE CLEANOUT DOWNSTREAM OF SANT. RISER 63 SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE RISER DIAGRAM. THE
 BRANCH LINE FOR THE ICE MACHINE, (9), IS SHOWN UPSTREAM
 OF THE DOUBLE WYE FITTING ON THE FLOOR PLAN, BUT
 DOWNSTREAM OF THE DOUBLE WYE ON THE RISER DIAGRAM. THE
 RISER DIAGRAM FOR THE PUBLIC TOILET ROOMS DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR DRAIN LINES ARE SHOWN
 ON THE BRANCH LINE TO THE LAVS ON THE RISER DIAGRAM,
 BUT OFF THE BRANCH LINE TO THE WATER CLOSETS, URINAL ON
 THE FLOOR PLAN. PLEASE CORRELATE THE RISER DIAGRAMS AND
 THE FLOOR PLAN.
  
 32A. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN MANY AREAS WHERE THE BRANCH
 LINES CONNECT TO THE MAIN WATER LINES, (SEE RISER
 BRANCH TO RISERS 53, 54, 55,45, 46, 47 & THEDISH
 SANITIZER,AT THE PUBLIC TOILET ROOMS, RISER NUMBERS
 DO NOT REFLECT THE FLOOR PLAN FOR RISERS 28, 29 & 30,
 (TWO SETS). THE REQUIRED WATER HAMMER ARRESTORS SHALL
 BE INDICATED PER SECTION 604.9, (ICE MAKERS, DISH
 WASHER, WASH MACHINES OR ANY OTHE QUICK CLOSING VALVE).
 SOME LINES HAVE THE HOT WATER LINES LABELED AS COLD
 WATER AND SOME LINES HAVE THE COLD WATER LINES LABELED
 AS HOT WATER LINES. IN THE PUBLIC TOILETS FIXTURES 3B
 HAVE THE COLD ON THE LEFT AND THE HOT ON THE RIGHT.
 (SECTION 607.4). SHOW ALL VALVES REQUIRED PER SECTIONS
 606.1 & 606.2 ON THE RISER DIAGRAM. SHOW ALL PIPE SIZES
 PER SECTION 604. SHT P507 DETAIL 2 THE STANDARD TOILET
 AND THE URINAL ARE MISLABELED AND THE FIXTURE INDICATED
 AS P5A, (SHOWER?), IS NOT INDICATED ON THE WATER RISER
 DIAGRAM. PLEASE CLARIFY.
  
 33 OK
 34. OK
 35. OK
 36. OK
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
 ********RESPONSE NOTED, BUT THE RISER DIAGRAM AND THE
 FLOOR PLAN STATE "FOR CONT. SEE P101C". THE SHT P101C
 SUBMITTED IS FOR HOMEWOOD SUITES, NOT SPRINGHILL
 SUITES. RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 NO PIPING TO THE RISERS FOR THE STORM DRAINAGE AT THE
 "PORTE COCHERE" AS WELL AS THE PIPING FOR THE DRAINAGE
 TO THE EAST SIDE OF THE BUILDING. (NO SHT A101C
 SUBMITTED FOR THE SPRINGHILL SUITES). SOME PIPE SIZING
 IS INCORRECT. (SEE 4" HORIZONTAL INDICATED FOR 2068SF).
 SHOW ALL PIPE SIZES, AND INDICATED THE SQUARE FOOTAGE
 AS IT ACCUMULATES IN THE SYSTEM.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P101 PLUMBING KEYNOTES, 18, 30 & 31 WERE NOT
 FOUND. PLEASE CLARIFY.--KEYNOTES 41 & 43 STATE "NOT
 USED" BUT WERE FOUND ON THE FLOOR PLAN. PLEASE CLARIFY.
 --KEYNOTE 14 IS SHOWN CONNECTING TO THE BUILDING
 SANT. DRAIN. PLEASE CLARIFY.--KEYNOTE 20, ONE
 APPEARS TO BE CONNECTING TO STORM DRAIN LINE AND ONE
 APPEARS TO BE SHOWN TO A HOT WATER LINE. PLEASE
 CLARIFY.--KEYNOTE 25 STILL SHOWS 7" W.C. FOR THE
 GAS PRESSURE. RISER CHANGED TO 12" - 14" W.C. PLEASE
 CORRELATE.--KEYNOTE 47 INDICATES WATER SUPPLY TO
 WATER WALL. BACKFLOW PREVENTION IS REQUIRED. PLEASE
 INDICATE METHOD. (A VACUUM BREAKER AT THE HIGHES POINT
 WILL SUFFICE).SECTION 608.--KEYNOTE 1 INDICATES
 SANT./HOT/COLD BUT MOST KEYNOTES ON THE FLOOR PLAN ONLY
 SHOW THE HOT & COLD WATER BUT NO SANITARY. CLARIFY. --
 KEYNOTE 9 IS SHOWING THE WATER SUPPLY TO AN ICE MACHINE
 CONNECTING TO A 2-1/2" FIRE LINE IN THE STAILWELL. THE
 FIRE LINE IS NOT CONSIDERED A POTABLE WATER LINE, AND
 ONLY THE PIPING REQUIRED FOR THE FIGHTING OF FIRES
 SHALL BE LOCATED IN THE STAIRWELLS. NFPA-101 SECTION
 7.1.3.2.1(6). PLEASE DELETE THE CONNECTION AND SHOW THE
 ICE MAKER CONNECTING TO THE POTABLE WATER SYSTEM.--
 REFERENCES TO SHT P402 & P403 ARE SHOWN WHEN CALLING
 OUT ENLARGED SECTIONS. SHEETS P402 & P403 HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY.--KEYNOTE 48 DOES NOT
 SHOW SANITARY PIPING.PLEASE CLARIFY.--KEYNOTE 40
 & 26 IN THE GAS SYSTEM. PLEASE INDICATE WHERE THE
 CONTINUANCE OF THE GAS LINE AFTER KEYNOTES IS LOCATED.
 --KEYNOTE 21, (SANT.),APPEARS TO CONNECT TO THE GAS
 SYSTEM. PLEASE CLARIFY.--KEYNOTE 22 SHOWS NO
 SANITARY. PLEASE CLARIFY.--KEYNOTE 4 AT SOME SHOW
 NO HOT WATER SUPPLY. PLEASE CLARIFY.--KEYNOTE 3 AT
 ONE 1/P402 SHOWS NOT WATER SUPPLY LINES. PLEASE
 CLARIFY. --STORM DRAIN IS SHOWN ENTERING THE
 BUILDING ON THE EAST SIDE OF THE BUILDING AND EXITING
 BY THE PORTE COCHERE. PLEASE INDICATED WHERE THE STORM
 LINE CONTINUES EAST OF THE BUILDING AND INDICATE WHERE
 THE RISER DIAGRAM IS FOR THIS STORM PIPING.--A
 WATER LINE IS SHOWN CONNECTING TO A 3/4" NFWH. PLEASE
 INDICATE WHERE THIS LINE CONTIUES AND INDICATE WHERE ON
 THE RISER DIAGRAM THIS IS SHOWN.--KEYNOTES 20, 21 &
 22 EAST OF THE PUBLIC TOILET ROOMS DO NOT SHOW SANITARY
 CONNTECTING TO THE RISERS. PLEASE CLARIFY.--4" SAN
 A/C IS NOT INDICATED ON THE PLUMBING LEGEND ON SHT
 P601. PLEASE INDICATE WHAT THE A/C STANDS FOR. PLEASE
 SHOW ON THE PLUMBING LEGEND.--THE 4" SAN A/C ABOVE
 THE KITCHEN AREA DOES NOT APPEAR TO CONNECT TO THE
 SANITARY BUILDING DRAIN. PLEASE CLARIFY.--TWO WAY
 CLEANOUTS ARE REQUIRED AT THE ENTRANCE AND EXIT PIPING
 OF THE GREASE INTERCEPTOR AS WELL AS NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING SEWER AS THE
 PIPING EXITS THE BUILDING. WPB UTILITY STANDARD AND
 SECTION 708.3.5. (IF THE 2-WAY C/O'S ARE INSTALLED AT
 THE GREASE INTERCEPTOR THEY WILL SUFFICE FOR BOTH
 REQUIREMENTS). SECTION 106.1.1.
 ********RESPONSE NOTED, BUT NOW KEYNOTES 9 & 26 STATE
 "NOT USED" BUT ARE SHOWN ON THE FLOOR PLAN. ALSO
 KEYNOTE 40 HAS NOT BEEN FOUND ON THE FLOOR PLAN. PLEASE
 CLARIFY.
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3. ********RESPONSE
 NOTED, BUT THE RISER DIAGRAMS FOR DETAILS 5 & 6 ARE NOT
 SHOWN ON SHTS P507 OR P508. NO WATER TO THE HAND SINK
 NOR TO THE 3 COMPARTMENT SINK. NO SANITARY SHOWN TO THE
 HAND SINK, THE 3 COMPARTMENT SINK OR THE FLOOR DRAIN
 SHOWN IN DETAIL 5 SHT P401. THE FLOOR DRAIN SHALL
 CONNECT TO THE GREASE LINE, NOT THE SANITARY LINE.
  
 3C. OK
 4C. OK
 5C. OK
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
 ********RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE NOT SHOWN ON THE WATER RISER DIAGRAMS. RISER 5/502
 NOW SHOWS P-7, (BREAK SINK), AND P-8, (LAUNDRY ROOM
 SINK), WHERE AS THE FLOOR PLAN SHOWS SHOWER/TUB.ALSO
 ON SANITARY RISER 48 FIRST FLOOR SHOWS TWO FIXTURES, P4
 & P-13, BUT ON THE FLOOR PLAN NO FIXTURES ARE SHOWN.
 PLEASE CORRELATE. SANITARY RISER 48 APPEARS TO RUN
 THROUGH THE BASE CABINET ON THE FIRST FLOOR. PLEASE
 CLARIFY.
  
 7C. SHT P503 SANITARY AND VENT RISER SHOWS NO VENT
 PIPING & DOES NOT RELFECT THE FLOOR PLAN WHERE MANY OF
 THE BRANCH LINES CONNECT TO THE BUILDING SANITARY DRAIN
 LINE. SHOW ALL PIPING ON THE RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW THE PIPING FROM THE
 BUILDING DRAIN TO THE RISER DIAGRAM SHOWING ALL OFFSETS
 AND SHOW ALL FIRST FLOOR FIXTURES ON THE RISER DIAGRAM
 INCLUDING ALL PIPING FROM THE BUILDING SANT. DRAIN TO
 THE FIXTURES. SHOW ALL CLEANOUTS REQUIRED BY SECTION
 708 & ALL SUBSECTIONS. SECTION 106.1.1.
 ********RESPONSE NOTED, BUT NO BRANCH LINE SHOWN FOR
 SANT. RISERS 13,14,16,17 & 18.
  
 8C. OK
 9C. OK
  
 10C. SHT P505 THE FLOOR PLAN SHOWS SOME ROOF DRAINS
 CONNECTING IN THE BUILDING STORM DRAIN PRIOR TO EXITING
 THE BUILDING. PLEASE SUBMIT STORM ISOMETRIC RISER
 DIAGRAMS FOR ALL RISER DIAGRAMS THAT ARE NOT TYPICAL.
 SHOW ALL PIPE SIZES, OFFSETS, CLEANOUTS REQUIRED BY
 SECTION 1101.8 AND INDICATE THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.
 ********RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 **********NEW COMMENT**********
  
 1D. SHTS P504 & P505 THE WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS THE WATER
 PIPING FOR THE MAINS IN THE CEILING OF THE FIRST FLOOR,
 BUT THE RISER DIAGRAMS SHOW THE WATER RISERS CONNECTING
 TO THE MAIN UNDERGROUND. PLEASE CORRELATE. SECTIONS
 106.1.1 & 604.
  
 2D. PER FS 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE A FEE OF $99,000 IS DUE BEFORE
 RESUBMITTING THE PLANS FOR REVIEW. THIS IS NOT ACCESSED
 TO THE OWNER OR CONTRACTOR. ONE SET OF PLANS IS BEING
 RETAINED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  