| Plan Review Notes For Permit 06111067 |
| Permit Number |
06111067 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-01-08 14:13:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 10-15-07 NOTE #3. SEE | | | MECHANICAL PLAN PAGE M101, THE YELLOW HIGH LIGHTS THAT | | | ARE SHOWINGING THE RATED WALLS WERE THE DUCTS PENETRATE | | | THEM FIRE DAMPERS WILL BE REQUIRED (SEE RED LINE ON | | | PLAN) OR STATE HOW THEY ARE COMPLYING WITH 2004 FBC/M | | | 607.5.1. ALSO SEE WALL ASSEMBLY TYPES PLAN PAGES A-401 | | | AND A-601. | | | | | | 2)PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL | | | LOCATION CHANGES WITH ARCHITECT AND MECHANICAL | | | ENGINEER. | | | | | | 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING | | | FOUR TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|