Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop M
Sequence Number 4
Notes
Date Text
2008-01-08 14:13:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-15-07 NOTE #3. SEE
 MECHANICAL PLAN PAGE M101, THE YELLOW HIGH LIGHTS THAT
 ARE SHOWINGING THE RATED WALLS WERE THE DUCTS PENETRATE
 THEM FIRE DAMPERS WILL BE REQUIRED (SEE RED LINE ON
 PLAN) OR STATE HOW THEY ARE COMPLYING WITH 2004 FBC/M
 607.5.1. ALSO SEE WALL ASSEMBLY TYPES PLAN PAGES A-401
 AND A-601.
  
 2)PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL
 LOCATION CHANGES WITH ARCHITECT AND MECHANICAL
 ENGINEER.
  
 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]