| 2008-01-30 09:45:52 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06111067 |
| | ADD: 2437 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | SPRINGHILL SUITES BY MARIOTT |
| | FIVE STORY/ 130 UNITS |
| | |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1-17C COMPLIED |
| | |
| | 17-D) NOTE THE ELEVATOR DOORS ON THE DOOR SCHEDULE |
| | (*34) NOW INDICATE THIS TO BE A STORAGE CLOSET. |
| | |
| | 18-29A) COMPLIED. |
| | |
| | 29B-30 CAN NOT BE REVIEWED FOR WIND PRESSURES, SHEET |
| | S-101 ASCE 7-02 ANALYSIS INDICATES A "C" EXPOSURE WHICH |
| | IS CORRECT, THE BUILDINGS ROOF HEIGTH IS 54'-0, THE |
| | EXPOSURE COEFFICIENT IS 1.59( 1609..2.1(4) NOT 1.09. |
| | THIS WILL INCREASE PRESSURES SHOWN IN THE COMPENTS AND |
| | CLADDING TABLE!!! PLEASE RECALCULATE AND RE-REVIEW THE |
| | PRODUCT APPROVALS FOR POSITIVE AND NEGATIVE PRESSURES. |
| | |
| | 31-32) BOTH WILL RELATE BACK TOTHE RECALCULATING |
| | PRESSURES TO THE EXPOSURE COEFFICIENT OF 1.59 PER |
| | 1609.2.1.(4). |
| | |
| | 33-34) COMPLIED. |
| | |
| | NEW COMMENT: |
| | 35) SHEET A-401, FIRST FLOOR, THE R2 UNITS ON THE FIRST |
| | FLOOR REQUIRE 2 EXITS AND THE EXIT ACCESS FOR ONE WAY |
| | IS THROUGH THE FRONT LOBBYBUT THE WALLS THERE ARE |
| | LOCATED BEHIND THE REGISTRATION DESK ARE INDICATED AS |
| | NON-RATED WALLS. PLEASE SEE 1016.5 CORRIDOR CONTINUITY, |
| | EXCEPTIONS: FOYERS, LOBBIES OR RECEPTION ROOMS |
| | CONSTRUCTED AS REQUIED FOR CORRIDORS SHALL NOT BE |
| | CONSTRUED AS INTERVENING ROOMS.THE LOBBY OR FOYEER |
| | ARE OK AS LONG AS THE WALL RATINGS ARE MAINTAINED. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |