| 2007-11-21 17:25:59 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEW: 3RD REVIEW: |
| | |
| | 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND |
| | THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE |
| | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS |
| | 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS |
| | ALL INFORMATION REQUIRED BY FAC 61G1-16.002 & FS |
| | 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON |
| | EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION |
| | IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE |
| | ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE |
| | PLANS. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. FIRM |
| | LICENSE FOR PFVS ARCHITECTS INC. IS NOT INDICATED IN |
| | THE TITLE BLOCK NOR HAS THE INFORMATION REQUIRED WHEN |
| | SEALING THE SHEETS BEEN ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE TITLE BLOCK STILL |
| | INDICATES PFVS ARCHITECTS. ALL REFERENCE TO THE |
| | ARCHITECTURAL COMPANY SHALL BE DELETED FROM THE TITLE |
| | BLOCK OR A FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), WILL BE REQUIRED.--ALSO THE SEAL |
| | BEING USED IS NOT APPROVED. PER FAC 61G1-16.002 THE |
| | SEAL SHALL BE APPROX. 2" IN DIAMETER. FS 481.2055. |
| | |
| | 2.OK |
| | |
| | 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN |
| | THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT ENGINEERING CA# NOT INDICATED |
| | AS WELL AS THE REQUIREMENT FOR THE ARCHITECTURE, |
| | (BUSINESS NUMBER), HAS NOT BEEN ADDRESSED. |
| | ******RESPONSE NOTED, BUT PFVS ARCHITECTS IS STILL |
| | INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL |
| | REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED |
| | FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR |
| | EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA. |
| | ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO |
| | THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING |
| | DRAINED BY EACH DRAIN. |
| | ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND. |
| | PLEASE SUBMIT THE CALCULATIONS REQUESTED. |
| | ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT |
| | SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE |
| | SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR |
| | EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA |
| | SHOWING THE INFORMATION REQUESTED. |
| | |
| | 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN. |
| | PLEASE CLARIFY. SECTION 1106.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE WATER CLOSET IS LOCATED |
| | ON A WALL OPPOSITE OF THE GRAB BARS AND DOES NOT |
| | REFLECT THE FIXTURE LAYONT ON SHT P101.--THE DOOR |
| | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | THE LAV PER SECTION 11-4.22.2(1). THE DOOR IS SHOWN |
| | SWINGING THRU THE CLEAR FLOOR SPACE. |
| | |
| | 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR |
| | EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE |
| | UNITS. SECTIONS 11-4.16. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN FOR THE SHOWER, THE TUB, NOR THE SINK. |
| | |
| | 11. OK |
| | |
| | 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH |
| | CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A |
| | MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE |
| | NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO |
| | BE INSTALLED. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING |
| | IS NOT SHOWN: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.7 FAUCET TYPE |
| | |
| | 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803 |
| | APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE |
| | ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22 |
| | AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS. |
| | ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN. |
| | 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE |
| | THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28 |
| | AND 11-32. |
| | ****NO RESPONSE. SHOW THE FOLLOWING: |
| | SHT A-802.. |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 OK |
| | ___FOR URINALS: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | ******NOT ADDRESSED |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ******NOT ADDRESSED |
| | ____FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES (CLEARANCES) |
| | ******NOT ADDRESSED |
| | B. 11-4.19.4 OK |
| | C. 11-4.19.5 FAUCETS |
| | ******NOT ADDRESSED |
| | SHT A-803 |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 OK |
| | ___FOR LAVS: |
| | A. 11-4.19.3 OK |
| | B. 11-4.19.5 FAUCETS |
| | ******NOT ADDRESSED |
| | ___FOR TUBS: |
| | A. 11-4.20.2 CLEAR FLOOR SPACE |
| | ******NOT ADDRESSED |
| | B. 11-4.20.5 CONTROLS |
| | ******NOT ADDRESSED |
| | ___FOR TOILET ROOMS |
| | A. 11-4.22.3 OK |
| | OK |
| | |
| | 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING: |
| | A. 11-4.24.4 OK |
| | B. 11-4.24.5 CLEAR FLOOR SPACE |
| | ******NOT ADDRESSED |
| | C. 11-4.24.7 FAUCETS (TYPE) |
| | ******NOT ADDRESSED |
| | ****NO RESPONSE, NOT ADDRESSED |
| | ******RESPONSE NOTED, NOT COMPLETLY ADDRESSED |
| | |
| | |
| | 15. N/A |
| | 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE. |
| | MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER |
| | SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE |
| | WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM. |
| | PLEASE CLARIFY.SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT PLEASE EXPLAIN KEYNOTES #47 & |
| | #48 ON SHT P101 AND RELATED WATER PIPING THAT INDICATES |
| | WATER TO THE WATER WALL FEATURE? BACKFLOW PREVENTION IS |
| | REQUIRED FOR THE WATER SUPPLY. PLEASE INDICATE METHOD. |
| | SECTION 608.--PLEASE INDICATE THE DRAINAGE PIPING |
| | ON THE FLOOR PLAN AND MAKE SURE IT IS REFLECTED IN AN |
| | ISOMETRIC RISER DIAGRAM. |
| | |
| | 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING: |
| | A. 11-4.19.2 CLEARANCE |
| | ******RESPONSE NOTED, NOT CORRECT 29" REQUIRED |
| | B. 11-4.19.5 FAUCETS |
| | ******RESPONSE NOTED, FAUCET TYPE NOT ADDRESSED ****NO |
| | RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, COMMENTS NOT ADDRESSED |
| | CORRECTLY. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | |
| | 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES |
| | SHOW NO PIPING OR BRANCH LINES CONNECTING THE |
| | RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THERE IS STILL SANITARY |
| | PIPING NOT SHOWN. THE PIPING FOR ALL SYSTEMS IS NOT |
| | VERY LEGIBLE. THE PIPING IS NOT SHOWN TO MANY RISERS, |
| | AND IN MANY CASES THE PIPING IS HARD TO FOLLOW BECAUSE |
| | IS IS COVERED BY DARKER/BOLDER LINES OR OTHER SYSTEMS. |
| | IN SOME CASES IT IS NOT CLEAR WHAT SYSTEM CONNECTS TO |
| | WHAT RISER. SOME FIXTURES HAVE NO WATER PIPING SHOWN. |
| | SEE NEW COMMENTS FOR SHT P101 AT THE END OF THESE |
| | COMMENTS. |
| | |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | |
| | 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT |
| | VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT |
| | REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE |
| | THE FLOOR PLANS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE PLANS NOW SHOW A 3" VENT |
| | THAT APPEARS TO BE A DRY HORIZONTAL VENT. THIS IS NOT |
| | SHOWN ON THE SANITARY RISER DIAGRAM SO ITS NOT CLEAR. |
| | PLEASE INDICATE ALL PIPING ON THE HORIZONTAL PIPING |
| | ISOMETRIC FOR ALL PIPING UP TO ALL RISERS AND |
| | FIXTURES/FIXTURE GROUPS ON THE FIRST FLOOR TO REFLECT |
| | THE FLOOR PLAN. |
| | ******RESPONSE NOTED, BUT THIS SANITARY & VENT PIPING |
| | IS NOT SHOWN ON ANY ISOMETRIC RISE DIAGRAM SHOWING PIPE |
| | SIZES, ETC. |
| | |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | |
| | 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN |
| | ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A |
| | VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE |
| | BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP |
| | ROOM ETC.). |
| | ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES |
| | GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL |
| | SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS |
| | WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET |
| | ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM, |
| | VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE |
| | SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC. |
| | ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT |
| | ADDRESSED. |
| | |
| | 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS, |
| | WASH MACHINES, AND DISHWASHERS). |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THERE IS STILL NO WATER |
| | ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH |
| | MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER |
| | ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL |
| | INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING |
| | THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT |
| | THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION |
| | 606.1(3). |
| | |
| | 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC |
| | RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL |
| | PIPE SIZES AND INDICATE THE TERMINATION POINT. |
| | ****RESPONSE NOTED, BUT IF THE CONDENSATE IS CONNECTING |
| | TO THE STORM LINE, A RELIEF VENT WILL BE REQUIRED AS |
| | THE CONDENSATE LINE EXITS THE BUILDING. PLEASE SHOW THE |
| | RELIEF VENT AND THE TERMINATION POINT ON THE RISER |
| | DIAGRAM. |
| | ******RESPONSE NOTED, BUT PLEASE EXPLAIN "TO SPILL TO |
| | GRADE". THE CONDENSATE SHALL NOT DRAIN ON TO THE |
| | SIDEWALK, PARKING LOT, STREET, ALLEY OR ANY PLACE WHERE |
| | IS CAN CREATE A HAZARD OR NUISANCE.SECTION M307.2.1. |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETAIL 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED BY HAVING |
| | MULTIPLE RISERS WITH THE SAME DESIGNATION, SUCH AS |
| | RISER 2 OR RISER 8. ALL RISER NUMBERS SHALL BE SHOWN ON |
| | THE HORIZONTAL ISOMETRIC AND THE FLOOR PLANS OF EACH |
| | FLOOR. |
| | ******RESPONSE NOTED, BUT THE RISERS ARE NOT TYPICAL IF |
| | THEY HAVE DIFFERENT FIXTURES. SOME FLOOR PLANS SHOW |
| | TUBS BACK TO BACK, OTHER FLOOR PLANS SHOW TUB & SHOWERS |
| | BACK TO BACK. WHERE AS OTHER FLOOR PLANS SHOW SHOWERS |
| | BACK TO BACK. OTHER RISERS SHOW FIXTURES ON ALL 5 |
| | FLOORS BUT ONLY HAVE FIXTURES ON 4 FLOORS AS THE FIRST |
| | FLOOR DOES NOT HAVE A SUITE. EACH RISER SHALL REFLECT |
| | THE FIXTURES SHOWN ON THE FLOOR PLAN FOR EACH FLOOR. |
| | |
| | 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO |
| | SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE |
| | "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION |
| | 102.2.1. |
| | ****RESPONSE NOTED, BUT "REVIEWED, STAMPED" PLANS AND |
| | ATTACHED "TWO PAGE WORKSHEET" SHALL BE REQUIRED FOR |
| | EACH SET OF PLANS AT THE TIME OF RESUBMITTING FOR |
| | REVIEW TO THE CITY. |
| | ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION |
| | WORKSHEETS" FOR SPRINGHILL HAS BEEN ATTACHED TO THE |
| | HOMEWOOD PLANS AND THE HOMEWOOD WORKSHEETS HAS BEEN |
| | ATTACHED TO THE SPRINGHILL PLANS. |
| | |
| | 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE |
| | FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION |
| | 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL. |
| | INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE |
| | GREASE INTERCEPTOR. CONTACT HER BY PHONE (561) |
| | 822-2271, FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. |
| | ****RESPONSE NOTED, NO COMMENT FROM ENVIRONMENTAL AS OF |
| | YET. |
| | ******RESPONSE NOTED, BUT STILL AWAITING CONFIRMATION |
| | OF INTERCEPTOR SIZE FROM ENVIRONMENTAL COMPLIANCE. I |
| | HAVE SENT AN E-MAIL AND WILL PURSUE CONFIRMATION ON |
| | THIS END. |
| | |
| | 37. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | 2B. OK |
| | |
| | 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL. |
| | SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE |
| | THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE |
| | TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE |
| | TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE |
| | NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL |
| | BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH |
| | RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION |
| | 106.1.3.5.1.3(7)(13). |
| | ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE. |
| | SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING |
| | STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL |
| | PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8, |
| | OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS |
| | ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE |
| | WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS |
| | HAVE BEEN SUBMITTED AND VERIFIED. |
| | |
| | 4B. OK |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | 1C. SHT P101 PLUMBING KEYNOTES, 18, 30 & 31 WERE NOT |
| | FOUND. PLEASE CLARIFY.--KEYNOTES 41 & 43 STATE "NOT |
| | USED" BUT WERE FOUND ON THE FLOOR PLAN. PLEASE CLARIFY. |
| | --KEYNOTE 14 IS SHOWN CONNECTING TO THE BUILDING |
| | SANT. DRAIN. PLEASE CLARIFY.--KEYNOTE 20, ONE |
| | APPEARS TO BE CONNECTING TO STORM DRAIN LINE AND ONE |
| | APPEARS TO BE SHOWN TO A HOT WATER LINE. PLEASE |
| | CLARIFY.--KEYNOTE 25 STILL SHOWS 7" W.C. FOR THE |
| | GAS PRESSURE. RISER CHANGED TO 12" - 14" W.C. PLEASE |
| | CORRELATE.--KEYNOTE 47 INDICATES WATER SUPPLY TO |
| | WATER WALL. BACKFLOW PREVENTION IS REQUIRED. PLEASE |
| | INDICATE METHOD. (A VACUUM BREAKER AT THE HIGHES POINT |
| | WILL SUFFICE).SECTION 608.--KEYNOTE 1 INDICATES |
| | SANT./HOT/COLD BUT MOST KEYNOTES ON THE FLOOR PLAN ONLY |
| | SHOW THE HOT & COLD WATER BUT NO SANITARY. CLARIFY. -- |
| | KEYNOTE 9 IS SHOWING THE WATER SUPPLY TO AN ICE MACHINE |
| | CONNECTING TO A 2-1/2" FIRE LINE IN THE STAILWELL. THE |
| | FIRE LINE IS NOT CONSIDERED A POTABLE WATER LINE, AND |
| | ONLY THE PIPING REQUIRED FOR THE FIGHTING OF FIRES |
| | SHALL BE LOCATED IN THE STAIRWELLS. NFPA-101 SECTION |
| | 7.1.3.2.1(6). PLEASE DELETE THE CONNECTION AND SHOW THE |
| | ICE MAKER CONNECTING TO THE POTABLE WATER SYSTEM.-- |
| | REFERENCES TO SHT P402 & P403 ARE SHOWN WHEN CALLING |
| | OUT ENLARGED SECTIONS. SHEETS P402 & P403 HAVE NOT BEEN |
| | SUBMITTED. PLEASE CLARIFY.--KEYNOTE 48 DOES NOT |
| | SHOW SANITARY PIPING.PLEASE CLARIFY.--KEYNOTE 40 |
| | & 26 IN THE GAS SYSTEM. PLEASE INDICATE WHERE THE |
| | CONTINUANCE OF THE GAS LINE AFTER KEYNOTES IS LOCATED. |
| | --KEYNOTE 21, (SANT.),APPEARS TO CONNECT TO THE GAS |
| | SYSTEM. PLEASE CLARIFY.--KEYNOTE 22 SHOWS NO |
| | SANITARY. PLEASE CLARIFY.--KEYNOTE 4 AT SOME SHOW |
| | NO HOT WATER SUPPLY. PLEASE CLARIFY.--KEYNOTE 3 AT |
| | ONE 1/P402 SHOWS NOT WATER SUPPLY LINES. PLEASE |
| | CLARIFY. --STORM DRAIN IS SHOWN ENTERING THE |
| | BUILDING ON THE EAST SIDE OF THE BUILDING AND EXITING |
| | BY THE PORTE COCHERE. PLEASE INDICATED WHERE THE STORM |
| | LINE CONTINUES EAST OF THE BUILDING AND INDICATE WHERE |
| | THE RISER DIAGRAM IS FOR THIS STORM PIPING.--A |
| | WATER LINE IS SHOWN CONNECTING TO A 3/4" NFWH. PLEASE |
| | INDICATE WHERE THIS LINE CONTIUES AND INDICATE WHERE ON |
| | THE RISER DIAGRAM THIS IS SHOWN.--KEYNOTES 20, 21 & |
| | 22 EAST OF THE PUBLIC TOILET ROOMS DO NOT SHOW SANITARY |
| | CONNTECTING TO THE RISERS. PLEASE CLARIFY.--4" SAN |
| | A/C IS NOT INDICATED ON THE PLUMBING LEGEND ON SHT |
| | P601. PLEASE INDICATE WHAT THE A/C STANDS FOR. PLEASE |
| | SHOW ON THE PLUMBING LEGEND.--THE 4" SAN A/C ABOVE |
| | THE KITCHEN AREA DOES NOT APPEAR TO CONNECT TO THE |
| | SANITARY BUILDING DRAIN. PLEASE CLARIFY.--TWO WAY |
| | CLEANOUTS ARE REQUIRED AT THE ENTRANCE AND EXIT PIPING |
| | OF THE GREASE INTERCEPTOR AS WELL AS NEAR THE JUNCTION |
| | OF THE BUILDING DRAIN AND THE BUILDING SEWER AS THE |
| | PIPING EXITS THE BUILDING. WPB UTILITY STANDARD AND |
| | SECTION 708.3.5. (IF THE 2-WAY C/O'S ARE INSTALLED AT |
| | THE GREASE INTERCEPTOR THEY WILL SUFFICE FOR BOTH |
| | REQUIREMENTS). SECTION 106.1.1. |
| | |
| | 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE |
| | SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR |
| | THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR |
| | THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS ECT. SECTION 106.3.5.1.3. |
| | |
| | 3C. SHT P401 DETAILS 2 & 3 SHOW TYPICAL BACK TO BACK & |
| | SINGLE TOILET PLUMBING. NOT ALL UNITS ARE TYPICAL AS |
| | SOME BACK TO BACK HAVE TUB/TUB OR TUB/SHOWER OR |
| | SHOWER/SHOWER. PLEASE SHOW ALL TYPE FLOOR PLANS. |
| | SECTION 106.1.2. |
| | |
| | 4C. SHT P501 SHOW TYPICAL RISER DIAGRAMS. NOT ALL UNITS |
| | ARE TYPICAL AND A RISER IS REQUIRED FOR EACH FLOOR |
| | PLAN. SECTION 106.3.5.1.3. |
| | |
| | 5C. SHT P501 RISER DIAGRAM 9/501 IS NOT SHOWN ON THE |
| | FIRST FLOOR PLAN. PLEASE INDICATE WHERE THE VENDING |
| | MACHINE FLOOR DRAIN ARE LOCATED. PLEASE INDICATE IF |
| | THERE IS AN ICE MACHINE ON EACH FLOOR BY THE VENDING |
| | MACHINES. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE |
| | RECPTORS AND FLOOR SINKS OR HUB WILL BE REQUIRED TO |
| | DRAIN THE ICE MACHINES. SECTIONS 802.3 & 802.3.2. |
| | PLEASE CLARIFY. |
| | |
| | 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER |
| | RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER |
| | ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE |
| | EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT |
| | SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502 |
| | INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A |
| | WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION. |
| | ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY |
| | AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE |
| | FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER |
| | 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5 |
| | FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP |
| | SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER |
| | 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY. |
| | --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON |
| | THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502 |
| | SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE |
| | SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE |
| | FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR |
| | PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS |
| | REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN |
| | ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER |
| | RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN. |
| | DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER |
| | DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT |
| | RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN. |
| | |
| | 7C. SHT P503 SANITARY AND VENT RISER SHOWS NO VENT |
| | PIPING & DOES NOT RELFECT THE FLOOR PLAN WHERE MANY OF |
| | THE BRANCH LINES CONNECT TO THE BUILDING SANITARY DRAIN |
| | LINE. SHOW ALL PIPING ON THE RISER DIAGRAM THAT |
| | REFLECTS THE FLOOR PLAN. SHOW THE PIPING FROM THE |
| | BUILDING DRAIN TO THE RISER DIAGRAM SHOWING ALL OFFSETS |
| | AND SHOW ALL FIRST FLOOR FIXTURES ON THE RISER DIAGRAM |
| | INCLUDING ALL PIPING FROM THE BUILDING SANT. DRAIN TO |
| | THE FIXTURES. SHOW ALL CLEANOUTS REQUIRED BY SECTION |
| | 708 & ALL SUBSECTIONS. SECTION 106.1.1. |
| | |
| | 8C. SHT P504 HOT & COLD WATER RISER DIAGRAM. SHOW THE |
| | PIPING FROM THE WATER MAINS TO EACH FIXTURE ON THE |
| | FIRST FLOOR AND TO EACH RISER. SHOW ALL PIPE SIZES, |
| | OFFSETS, VALVES AND WATER HAMMER ARRESTORS. SECTIONS |
| | 604.9, 606 & TABLES 603.1, 604.3 & 604.5. |
| | |
| | 9C. SHT P504 REFERES TO SHT P501 FOR WATER RISERS. SHT |
| | P501 ONLY HAS WASTE AND VENT RISERS. PLEASE CLARIFY. -- |
| | PLEASE INDICATE WHERE THE WATER ISOMETRIC RISER |
| | DIAGRAMS FOR THE EMPLOYEE TOILET ROOM, THE LAUNDRY |
| | ROOM, THE WATER HEATER ROOM, THE GUEST LAUNDRY ROOM, |
| | THE KITCHEN AND ANY OTHER AREA THAT HAS HOT & COLD |
| | WATER PIPING THAT IS NOT SHOWN BY THE WATER ISOMETRIC |
| | RISER DIAGRAMS. SECTION 106.3.5.1.3. |
| | |
| | 10C. SHT P505 THE FLOOR PLAN SHOWS SOME ROOF DRAINS |
| | CONNECTING IN THE BUILDING STORM DRAIN PRIOR TO EXITING |
| | THE BUILDING. PLEASE SUBMIT STORM ISOMETRIC RISER |
| | DIAGRAMS FOR ALL RISER DIAGRAMS THAT ARE NOT TYPICAL. |
| | SHOW ALL PIPE SIZES, OFFSETS, CLEANOUTS REQUIRED BY |
| | SECTION 1101.8 AND INDICATE THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | |
| | OK |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |