Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-21 17:25:59 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEW: 3RD REVIEW:
  
 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC 61G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. FIRM
 LICENSE FOR PFVS ARCHITECTS INC. IS NOT INDICATED IN
 THE TITLE BLOCK NOR HAS THE INFORMATION REQUIRED WHEN
 SEALING THE SHEETS BEEN ADDRESSED.
 ******RESPONSE NOTED, BUT THE TITLE BLOCK STILL
 INDICATES PFVS ARCHITECTS. ALL REFERENCE TO THE
 ARCHITECTURAL COMPANY SHALL BE DELETED FROM THE TITLE
 BLOCK OR A FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), WILL BE REQUIRED.--ALSO THE SEAL
 BEING USED IS NOT APPROVED. PER FAC 61G1-16.002 THE
 SEAL SHALL BE APPROX. 2" IN DIAMETER. FS 481.2055.
  
 2.OK
  
 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****RESPONSE NOTED, BUT ENGINEERING CA# NOT INDICATED
 AS WELL AS THE REQUIREMENT FOR THE ARCHITECTURE,
 (BUSINESS NUMBER), HAS NOT BEEN ADDRESSED.
 ******RESPONSE NOTED, BUT PFVS ARCHITECTS IS STILL
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL
 REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED
 FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED.
  
 4. OK
 5. OK
 6. OK
 7. OK
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
 ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND.
 PLEASE SUBMIT THE CALCULATIONS REQUESTED.
 ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT
 SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE
 SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR
 EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA
 SHOWING THE INFORMATION REQUESTED.
  
 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN.
 PLEASE CLARIFY. SECTION 1106.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE WATER CLOSET IS LOCATED
 ON A WALL OPPOSITE OF THE GRAB BARS AND DOES NOT
 REFLECT THE FIXTURE LAYONT ON SHT P101.--THE DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 THE LAV PER SECTION 11-4.22.2(1). THE DOOR IS SHOWN
 SWINGING THRU THE CLEAR FLOOR SPACE.
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE SHOWER, THE TUB, NOR THE SINK.
  
 11. OK
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING
 IS NOT SHOWN:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCET TYPE
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
 ****NO RESPONSE. SHOW THE FOLLOWING:
 SHT A-802..
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 B. 11-4.18.4 FLUSH CONTROLS
 ******NOT ADDRESSED
 ____FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES (CLEARANCES)
 ******NOT ADDRESSED
 B. 11-4.19.4 OK
 C. 11-4.19.5 FAUCETS
 ******NOT ADDRESSED
 SHT A-803
 ___FOR W/C'S:
 A. 11-4.16.2 OK
 ___FOR LAVS:
 A. 11-4.19.3 OK
 B. 11-4.19.5 FAUCETS
 ******NOT ADDRESSED
 ___FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 B. 11-4.20.5 CONTROLS
 ******NOT ADDRESSED
 ___FOR TOILET ROOMS
 A. 11-4.22.3 OK
 OK
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 OK
 B. 11-4.24.5 CLEAR FLOOR SPACE
 ******NOT ADDRESSED
 C. 11-4.24.7 FAUCETS (TYPE)
 ******NOT ADDRESSED
 ****NO RESPONSE, NOT ADDRESSED
 ******RESPONSE NOTED, NOT COMPLETLY ADDRESSED
  
  
 15. N/A
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN KEYNOTES #47 &
 #48 ON SHT P101 AND RELATED WATER PIPING THAT INDICATES
 WATER TO THE WATER WALL FEATURE? BACKFLOW PREVENTION IS
 REQUIRED FOR THE WATER SUPPLY. PLEASE INDICATE METHOD.
 SECTION 608.--PLEASE INDICATE THE DRAINAGE PIPING
 ON THE FLOOR PLAN AND MAKE SURE IT IS REFLECTED IN AN
 ISOMETRIC RISER DIAGRAM.
  
 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 ******RESPONSE NOTED, NOT CORRECT 29" REQUIRED
 B. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, FAUCET TYPE NOT ADDRESSED ****NO
 RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, COMMENTS NOT ADDRESSED
 CORRECTLY.
  
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL SANITARY
 PIPING NOT SHOWN. THE PIPING FOR ALL SYSTEMS IS NOT
 VERY LEGIBLE. THE PIPING IS NOT SHOWN TO MANY RISERS,
 AND IN MANY CASES THE PIPING IS HARD TO FOLLOW BECAUSE
 IS IS COVERED BY DARKER/BOLDER LINES OR OTHER SYSTEMS.
 IN SOME CASES IT IS NOT CLEAR WHAT SYSTEM CONNECTS TO
 WHAT RISER. SOME FIXTURES HAVE NO WATER PIPING SHOWN.
 SEE NEW COMMENTS FOR SHT P101 AT THE END OF THESE
 COMMENTS.
  
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
  
 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT
 VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT
 REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE
 THE FLOOR PLANS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE PLANS NOW SHOW A 3" VENT
 THAT APPEARS TO BE A DRY HORIZONTAL VENT. THIS IS NOT
 SHOWN ON THE SANITARY RISER DIAGRAM SO ITS NOT CLEAR.
 PLEASE INDICATE ALL PIPING ON THE HORIZONTAL PIPING
 ISOMETRIC FOR ALL PIPING UP TO ALL RISERS AND
 FIXTURES/FIXTURE GROUPS ON THE FIRST FLOOR TO REFLECT
 THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT THIS SANITARY & VENT PIPING
 IS NOT SHOWN ON ANY ISOMETRIC RISE DIAGRAM SHOWING PIPE
 SIZES, ETC.
  
 29. OK
 30. OK
 31. OK
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES
 GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL
 SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS
 WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET
 ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM,
 VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE
 SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC.
 ******RESPONSE NOTED, BUT THE COMMENT IS STILL NOT
 ADDRESSED.
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THERE IS STILL NO WATER
 ISOMETRICS FOR THE EMPLOYEE TOILET ROOM, THE WASH
 MACHINE ROOM, THE FOOD PREP AREA, THE WATER HEATER
 ROOM, GUEST LAUNDRY, MOP SINK/WASH MACHINE. RISER SHALL
 INDICATE THE PIPING AS IT ENTERS THE BUILDING SHOWING
 THE FULL OPEN VALVE REQUIRED BY SECTION 606.1(2) AND AT
 THE BASE OF EACH RISER DIAGRAM REQUIRED BY SECTION
 606.1(3).
  
 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
 ****RESPONSE NOTED, BUT IF THE CONDENSATE IS CONNECTING
 TO THE STORM LINE, A RELIEF VENT WILL BE REQUIRED AS
 THE CONDENSATE LINE EXITS THE BUILDING. PLEASE SHOW THE
 RELIEF VENT AND THE TERMINATION POINT ON THE RISER
 DIAGRAM.
 ******RESPONSE NOTED, BUT PLEASE EXPLAIN "TO SPILL TO
 GRADE". THE CONDENSATE SHALL NOT DRAIN ON TO THE
 SIDEWALK, PARKING LOT, STREET, ALLEY OR ANY PLACE WHERE
 IS CAN CREATE A HAZARD OR NUISANCE.SECTION M307.2.1.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETAIL 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED BY HAVING
 MULTIPLE RISERS WITH THE SAME DESIGNATION, SUCH AS
 RISER 2 OR RISER 8. ALL RISER NUMBERS SHALL BE SHOWN ON
 THE HORIZONTAL ISOMETRIC AND THE FLOOR PLANS OF EACH
 FLOOR.
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT TYPICAL IF
 THEY HAVE DIFFERENT FIXTURES. SOME FLOOR PLANS SHOW
 TUBS BACK TO BACK, OTHER FLOOR PLANS SHOW TUB & SHOWERS
 BACK TO BACK. WHERE AS OTHER FLOOR PLANS SHOW SHOWERS
 BACK TO BACK. OTHER RISERS SHOW FIXTURES ON ALL 5
 FLOORS BUT ONLY HAVE FIXTURES ON 4 FLOORS AS THE FIRST
 FLOOR DOES NOT HAVE A SUITE. EACH RISER SHALL REFLECT
 THE FIXTURES SHOWN ON THE FLOOR PLAN FOR EACH FLOOR.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT "REVIEWED, STAMPED" PLANS AND
 ATTACHED "TWO PAGE WORKSHEET" SHALL BE REQUIRED FOR
 EACH SET OF PLANS AT THE TIME OF RESUBMITTING FOR
 REVIEW TO THE CITY.
 ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION
 WORKSHEETS" FOR SPRINGHILL HAS BEEN ATTACHED TO THE
 HOMEWOOD PLANS AND THE HOMEWOOD WORKSHEETS HAS BEEN
 ATTACHED TO THE SPRINGHILL PLANS.
  
 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE
 FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION
 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****RESPONSE NOTED, NO COMMENT FROM ENVIRONMENTAL AS OF
 YET.
 ******RESPONSE NOTED, BUT STILL AWAITING CONFIRMATION
 OF INTERCEPTOR SIZE FROM ENVIRONMENTAL COMPLIANCE. I
 HAVE SENT AN E-MAIL AND WILL PURSUE CONFIRMATION ON
 THIS END.
  
 37. OK
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
  
 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL.
 SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE
 THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE
 TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE
 TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE
 NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL
 BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH
 RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION
 106.1.3.5.1.3(7)(13).
 ******RESPONSE NOTED, BUT THE RISERS ARE NOT COMPLETE.
 SHOW THE RISERS FROM THE ROOF DRAIN THRU THE BUILDING
 STORM DRAIN PIPING AND EXITING THE BUILDING SHOWING ALL
 PIPE SIZE, CLEANOUTS REQUIRED BY SECTION 1101.8,
 OFFSETS AND IF RISERS COMBINE IN THE BUILDING SHOW THIS
 ON THE RISER ALSO. THE SQUARE FOOTAGE AND PIPE SIZE
 WILL BE VERIFIDE WHEN THE ROOF DRAINAGE CALCULATIONS
 HAVE BEEN SUBMITTED AND VERIFIED.
  
 4B. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT P101 PLUMBING KEYNOTES, 18, 30 & 31 WERE NOT
 FOUND. PLEASE CLARIFY.--KEYNOTES 41 & 43 STATE "NOT
 USED" BUT WERE FOUND ON THE FLOOR PLAN. PLEASE CLARIFY.
 --KEYNOTE 14 IS SHOWN CONNECTING TO THE BUILDING
 SANT. DRAIN. PLEASE CLARIFY.--KEYNOTE 20, ONE
 APPEARS TO BE CONNECTING TO STORM DRAIN LINE AND ONE
 APPEARS TO BE SHOWN TO A HOT WATER LINE. PLEASE
 CLARIFY.--KEYNOTE 25 STILL SHOWS 7" W.C. FOR THE
 GAS PRESSURE. RISER CHANGED TO 12" - 14" W.C. PLEASE
 CORRELATE.--KEYNOTE 47 INDICATES WATER SUPPLY TO
 WATER WALL. BACKFLOW PREVENTION IS REQUIRED. PLEASE
 INDICATE METHOD. (A VACUUM BREAKER AT THE HIGHES POINT
 WILL SUFFICE).SECTION 608.--KEYNOTE 1 INDICATES
 SANT./HOT/COLD BUT MOST KEYNOTES ON THE FLOOR PLAN ONLY
 SHOW THE HOT & COLD WATER BUT NO SANITARY. CLARIFY. --
 KEYNOTE 9 IS SHOWING THE WATER SUPPLY TO AN ICE MACHINE
 CONNECTING TO A 2-1/2" FIRE LINE IN THE STAILWELL. THE
 FIRE LINE IS NOT CONSIDERED A POTABLE WATER LINE, AND
 ONLY THE PIPING REQUIRED FOR THE FIGHTING OF FIRES
 SHALL BE LOCATED IN THE STAIRWELLS. NFPA-101 SECTION
 7.1.3.2.1(6). PLEASE DELETE THE CONNECTION AND SHOW THE
 ICE MAKER CONNECTING TO THE POTABLE WATER SYSTEM.--
 REFERENCES TO SHT P402 & P403 ARE SHOWN WHEN CALLING
 OUT ENLARGED SECTIONS. SHEETS P402 & P403 HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY.--KEYNOTE 48 DOES NOT
 SHOW SANITARY PIPING.PLEASE CLARIFY.--KEYNOTE 40
 & 26 IN THE GAS SYSTEM. PLEASE INDICATE WHERE THE
 CONTINUANCE OF THE GAS LINE AFTER KEYNOTES IS LOCATED.
 --KEYNOTE 21, (SANT.),APPEARS TO CONNECT TO THE GAS
 SYSTEM. PLEASE CLARIFY.--KEYNOTE 22 SHOWS NO
 SANITARY. PLEASE CLARIFY.--KEYNOTE 4 AT SOME SHOW
 NO HOT WATER SUPPLY. PLEASE CLARIFY.--KEYNOTE 3 AT
 ONE 1/P402 SHOWS NOT WATER SUPPLY LINES. PLEASE
 CLARIFY. --STORM DRAIN IS SHOWN ENTERING THE
 BUILDING ON THE EAST SIDE OF THE BUILDING AND EXITING
 BY THE PORTE COCHERE. PLEASE INDICATED WHERE THE STORM
 LINE CONTINUES EAST OF THE BUILDING AND INDICATE WHERE
 THE RISER DIAGRAM IS FOR THIS STORM PIPING.--A
 WATER LINE IS SHOWN CONNECTING TO A 3/4" NFWH. PLEASE
 INDICATE WHERE THIS LINE CONTIUES AND INDICATE WHERE ON
 THE RISER DIAGRAM THIS IS SHOWN.--KEYNOTES 20, 21 &
 22 EAST OF THE PUBLIC TOILET ROOMS DO NOT SHOW SANITARY
 CONNTECTING TO THE RISERS. PLEASE CLARIFY.--4" SAN
 A/C IS NOT INDICATED ON THE PLUMBING LEGEND ON SHT
 P601. PLEASE INDICATE WHAT THE A/C STANDS FOR. PLEASE
 SHOW ON THE PLUMBING LEGEND.--THE 4" SAN A/C ABOVE
 THE KITCHEN AREA DOES NOT APPEAR TO CONNECT TO THE
 SANITARY BUILDING DRAIN. PLEASE CLARIFY.--TWO WAY
 CLEANOUTS ARE REQUIRED AT THE ENTRANCE AND EXIT PIPING
 OF THE GREASE INTERCEPTOR AS WELL AS NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING SEWER AS THE
 PIPING EXITS THE BUILDING. WPB UTILITY STANDARD AND
 SECTION 708.3.5. (IF THE 2-WAY C/O'S ARE INSTALLED AT
 THE GREASE INTERCEPTOR THEY WILL SUFFICE FOR BOTH
 REQUIREMENTS). SECTION 106.1.1.
  
 2C. SHT P401 PLEASE SUBMIT RISER DIAGRAMS FOR THE
 SANITARY AND WATER PIPING IN DETAILS 1, 4, 5 & 6. FOR
 THE SANITARY SHOW ALL PIPE SIZES, TRAPS, & VENTS. FOR
 THE WATER SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ECT. SECTION 106.3.5.1.3.
  
 3C. SHT P401 DETAILS 2 & 3 SHOW TYPICAL BACK TO BACK &
 SINGLE TOILET PLUMBING. NOT ALL UNITS ARE TYPICAL AS
 SOME BACK TO BACK HAVE TUB/TUB OR TUB/SHOWER OR
 SHOWER/SHOWER. PLEASE SHOW ALL TYPE FLOOR PLANS.
 SECTION 106.1.2.
  
 4C. SHT P501 SHOW TYPICAL RISER DIAGRAMS. NOT ALL UNITS
 ARE TYPICAL AND A RISER IS REQUIRED FOR EACH FLOOR
 PLAN. SECTION 106.3.5.1.3.
  
 5C. SHT P501 RISER DIAGRAM 9/501 IS NOT SHOWN ON THE
 FIRST FLOOR PLAN. PLEASE INDICATE WHERE THE VENDING
 MACHINE FLOOR DRAIN ARE LOCATED. PLEASE INDICATE IF
 THERE IS AN ICE MACHINE ON EACH FLOOR BY THE VENDING
 MACHINES. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECPTORS AND FLOOR SINKS OR HUB WILL BE REQUIRED TO
 DRAIN THE ICE MACHINES. SECTIONS 802.3 & 802.3.2.
 PLEASE CLARIFY.
  
 6C. SHT P502 PLEASE INDICATE THE LOCATION OF THE WATER
 RISER DIAGRAMS FOR THE KITCHEN AREA, THE WATER HEATER
 ROOM, THE GUEST LAUNDRY ROOMS, THE LAUNDRY ROOM, THE
 EMPLOYEE TOILET ROOM AND ANY OTHER COMMON AREA NOT
 SUBMITTED. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS ETC. SECTION 106.3.5.1.3.--RISER 1/502
 INDICATES A MOP SINK AND A SHOWER ON ONE PORTION AND A
 WASH MACHINE AND WATER CLOSET ON THE OTHER PORTION.
 ALSO IT SHOWS FIXTURES ON ALL 5 FLOORS. PLEASE CLARIFY
 AS THERE ARE NOT FIXTURES ON THE FIRST FLOOR AND THESE
 FIXTURES ARE NOT SHOWN ON THE FLOOR PLAN.--RISER
 2/502 SHOWS WASH MACHINES AND WATER CLOSETS ON ALL 5
 FLOORS. PLEASE CLARIFY.--RISER 3/502 SHOWS MOP
 SINKS ON THE LAV RISER. PLEASE CLARIFY.--RISER
 4/502 SHOWS SHOWERS ON THE SINK RISER. PLEASE CLARIFY.
 --RISER 4/502 SHOW FIXTURE 4A WHICH IS NOT SHOWN ON
 THE FIXTURE SCHEDULE. PLEASE CLARIFY.--RISER 5/502
 SHOWS FIXTURE 9A WHICH IS NOT INDICATED ON THE FIXTURE
 SCHEDULE. PLEASE CLARIFY.--RISER 6/502 NONE OF THE
 FIXTURES ON THE RISE REFLECT WHAT IS SHOWN ON THE FLOOR
 PLAN. PLEASE CLARIFY.--PLEASE MAKE SURE ALL RISERS
 REFLECT THE FLOOR PLAN AND REFLECT THE FIXTURES SHOWN
 ON THE FLOOR PLAN. SECTION 106.1.1.--TYPICAL WATER
 RISER DIAGRAMS ARE NOT TYPICAL ON THE FLOOR PLAN.
 DIFFERENT FIXTURES ON THE FLOOR REQUIRE DIFFERENT RISER
 DIAGRAMS THAT REFLECT THE FLOOR PLAN. PLEASE SUBMIT
 RISER DIAGRAMS THAT REFLECT THE FLOOR PLAN.
  
 7C. SHT P503 SANITARY AND VENT RISER SHOWS NO VENT
 PIPING & DOES NOT RELFECT THE FLOOR PLAN WHERE MANY OF
 THE BRANCH LINES CONNECT TO THE BUILDING SANITARY DRAIN
 LINE. SHOW ALL PIPING ON THE RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN. SHOW THE PIPING FROM THE
 BUILDING DRAIN TO THE RISER DIAGRAM SHOWING ALL OFFSETS
 AND SHOW ALL FIRST FLOOR FIXTURES ON THE RISER DIAGRAM
 INCLUDING ALL PIPING FROM THE BUILDING SANT. DRAIN TO
 THE FIXTURES. SHOW ALL CLEANOUTS REQUIRED BY SECTION
 708 & ALL SUBSECTIONS. SECTION 106.1.1.
  
 8C. SHT P504 HOT & COLD WATER RISER DIAGRAM. SHOW THE
 PIPING FROM THE WATER MAINS TO EACH FIXTURE ON THE
 FIRST FLOOR AND TO EACH RISER. SHOW ALL PIPE SIZES,
 OFFSETS, VALVES AND WATER HAMMER ARRESTORS. SECTIONS
 604.9, 606 & TABLES 603.1, 604.3 & 604.5.
  
 9C. SHT P504 REFERES TO SHT P501 FOR WATER RISERS. SHT
 P501 ONLY HAS WASTE AND VENT RISERS. PLEASE CLARIFY. --
 PLEASE INDICATE WHERE THE WATER ISOMETRIC RISER
 DIAGRAMS FOR THE EMPLOYEE TOILET ROOM, THE LAUNDRY
 ROOM, THE WATER HEATER ROOM, THE GUEST LAUNDRY ROOM,
 THE KITCHEN AND ANY OTHER AREA THAT HAS HOT & COLD
 WATER PIPING THAT IS NOT SHOWN BY THE WATER ISOMETRIC
 RISER DIAGRAMS. SECTION 106.3.5.1.3.
  
 10C. SHT P505 THE FLOOR PLAN SHOWS SOME ROOF DRAINS
 CONNECTING IN THE BUILDING STORM DRAIN PRIOR TO EXITING
 THE BUILDING. PLEASE SUBMIT STORM ISOMETRIC RISER
 DIAGRAMS FOR ALL RISER DIAGRAMS THAT ARE NOT TYPICAL.
 SHOW ALL PIPE SIZES, OFFSETS, CLEANOUTS REQUIRED BY
 SECTION 1101.8 AND INDICATE THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
 OK
  
  