| 2007-11-24 12:42:09 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ***FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. PLEASE SUBMIT THE FOLLOWING: |
| | |
| | 1. OK |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ****NO RESPONSE, NOT ADDRSSED. PIPE SIZES SHALL BE |
| | SHOWN FOR ALL SECTIONS OF PIPE AND VALVES SHALL BE FULL |
| | SIZE FOR THE PIPE SIZE INDICATED TO THE GAS EQUIPMENT. |
| | ******RESPONSE NOTED, BUT 1-1/4" SUPPLY AND SHUT OFF |
| | VALVE IS REQUIRED FOR THE DRYERS, 1-1/4" SUPPLY AND |
| | SHUT OFF VALVE IS REQUIRED FOR THE POOL HEATER, 2" IS |
| | REQUIRED FOR THE SUPPLY TO THE FIRST WATER HEATER, AND |
| | 1" SUPPLY AND SHUT OFF VALVE IS REQUIRED TO EACH WATER |
| | HEATER. TABLE 402.4(2). PLEASE CORRECT PIPE SIZING AND |
| | SHUT OFF VALVE SIZE. |
| | |
| | 3. OK - NATURAL |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED. GAS REVIEW WILL STAY IN FAILED |
| | STATUS UNTIL MANUF. SPECIFICATION SHEETS WITH LISTING |
| | AND BTU'S THAT REFLECT THE RISER DIAGRAM ARE |
| | SUBMITTED. |
| | |
| | 10. N/A (NATURAL GAS) |
| | 11. N/A (NATURAL GAS) |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |