| 2007-10-24 17:18:59 | *****DENIED***** |
| | |
| | THE FOLLOWING COMMENTS OF THE PREVIOUS 29 STILL NEED TO |
| | BE ADDRESSED: |
| | |
| | |
| | 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE |
| | THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.NO ADDRESS |
| | SHOWN ON THE NEW SUBMITTED FIRE SPRINKLER SHEETS |
| | |
| | 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR |
| | KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE |
| | PREVENTION BUREAU AT 561-804-4724.KNOX BOX AS SHOWN |
| | ON SHEET A-101 APPEARS TO BE INSIDE THE GENERAL |
| | MANAGER'S OFFICE. THIS DEVICE SHALL BE INSTALLED IN AN |
| | ACCESSIBLE LOCATION AT THE FRONT ENTRANCE AREA. |
| | |
| | 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING |
| | METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS |
| | ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED, |
| | THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED |
| | BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY |
| | POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A |
| | CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK |
| | FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE |
| | SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON |
| | THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON |
| | THE BUILDING.ADDRESS NOT SHOWN ON SHEET AC-101 AS |
| | PER YOUR RESPONSE LETTER;PLEASE COMPLY |
| | |
| | 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE |
| | DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH |
| | FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS. |
| | ADD TO FIRE SPRINKLER PLAN SHEET; PLEASE COMPLY |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |