| 2007-09-30 11:15:20 | 2007-09-30 11:15:20 |
| | |
| | ** DENIED 3RD REVIEW *** |
| | SPRINGHILLSUITES |
| | 5-STORY 130 UNITS. |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON |
| | PLANS AND/OR REVISIONS TO PLANS WHICH INFORMATION IS |
| | ONLY NOW BEING SUBMITTED. DUE TO CHANGES AND |
| | INFORMATION WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW, |
| | THESE ITEMS COULD NOT HAVE COMMENTED ON AS SOME ITEMS |
| | AND INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE |
| | ITEMS WILL BE CLEARLY NOTED. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH REQUESTED |
| | FOR THE PRODUCT APPROVALS ETC NOT TO BE ATTACHED TO |
| | ROLLS. THIS WAS OK, AND THESE WERE NOT ATTACHED HOWEVER |
| | OF THE TWO ROLLS OF PLANS THIS REVIEWER REVIEWED, ALL |
| | SHEETS IN BOTH ROLLS WERE LOOSE AND NOT ATTACHED INTO |
| | SECURED ROLLS. |
| | PLEASE DO NOT SUBMIT ROLLS OF PLANS IN WHICH THE SHEETS |
| | ARE LOOSE AND NOT ATTACHED.THESE TWO ROLLS WERE |
| | SECURED BY THIS OFFICE. |
| | PLEASE SEE SOME SHEETS IN SETS ARE ACTUALLY INSERTED |
| | BACKWARDS AND UPSIDE DOWN. (S-SHEETS). |
| | FBC ADMIN SECTION 106.1, 106.5 ETC. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WITH |
| | RESPECT TO SIGNATURE VERIFICATION LETTER(S). THIS WAS |
| | SUBMITTED HOWEVER WAS NOT SEALED AS PREVIOUSLY |
| | REQUESTED. |
| | THIS CAN BE SUBMITTED AT ANY TIME. |
| | FS 471.025, 481.025 AND FAC 61G15-23.002, 61G1-16.004 |
| | |
| | THIS WAS COMPLETELY STATED ON PREVIOUS NOTE #2. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE #4 WHICH MENTIONED |
| | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER. AS |
| | PLANS WERE REVISED REMOVING ARCHITECTURAL FIRM MOST |
| | SHEETS ARE CORRECT HOWEVER PLEASE SEE THAT SOME SHEETS |
| | IN SOME SETS STILL CONTAIN PFVS (HOMEWOOD) AND COVER |
| | SHEETS (SPRINGHILL) STILL CALL FOR PFVS ARCHITECTS |
| | INC. |
| | |
| | THIS REVIEWER HAS SPOKEN WITH MR. KEY AND IT IS THE |
| | UNDERSTANDING THE FIRM NOW HAS OBTAINED THE REQUIRED |
| | LICENSING THROUGH THE STATE. PLEASE KNOW THAT ALL |
| | INFORMATION ON TITLE BLOCKS MAY BE REVISED AND |
| | CORRECTED ONCE ALL REVIEWS ARE COMPLETED AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS. |
| | PLEASE SEE FS481.219, FAC 61G1-16.004 |
| | |
| | 4) NOTE: THIS IS A NEW COMMENT: PLEASE SEE THE SEAL |
| | WHICH IS NOW BEING USED ON ALL THREE SETS FOR BOTH |
| | HOTELS FOR THE ARCHITECT OF RECORD MR. GREG PORTMAN IS |
| | NO LONGER ACCEPTED IN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING FAC61G1-16.002 WHICH CHANGED SEVERAL |
| | YEARS AGO, WHICH NOW REQUIRES A MINIMUM SEAL SIZE OF |
| | 2INCHES. PLEASE SEE THE NEW SHEETS NOW SUBMITTED |
| | CONTAINS AN OLD SEAL. |
| | IF THIS WAS THE ONLY COMMENT ON PLANS, THE ARCHITECT OF |
| | RECORD WOULD BE ABLE TO COME INTO THIS OFFICE AND |
| | RE-SIGN, DATE AND SEAL PLANS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO |
| | FBC CHAPTER 13. |
| | |
| | A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED |
| | STILL NEED SOME COORDINATION WITH ELECTRICAL LIGHTING |
| | ON PLANS. PLEASE THE INPUT DATA REPORT WHICH WILL BE |
| | NOTED AS IDR ON THE FOLLOWING DOES NOT CORRELATE WITH |
| | ALL LIGHTING ON PLANS AND FIXTURE LIGHTING LEGEND. |
| | PLEASE SEE SOME OF THE FOLLOWING EXAMPLES: EXTERIOR |
| | LIGHTING WHICH IS ON PLANS DOES NOT MATCH WITH THE IDR |
| | FOR THE SAME NUMBER OF FIXTURES, TYPE(S) AND WATTAGE. |
| | PLEASE SEE FRONT ENTRANCE AREA Z-21, 32WATT ON IDR AND |
| | 100WATTS ON FIXTURE LEGEND. |
| | PLEASE SEE FOR EXAMPLE THE WATTAGE WHICH IS REQUIRED |
| | FOR THE IDR FOR TRACK LIGHT IF LINE VOLTAGE OR LOW |
| | VOLTAGE IS REQUIRED TO MEET 13-415.2.ABC .1.2. THIS |
| | INFORMATION ON THE IDR DOES NOT COORDINATE WITH THE |
| | NOTES ON E-402 AS THE WATTAGE BEING LISTED FOR MAXIMUM |
| | IS NOT THAT WHICH IS LISTED ON THE IDR FOR THE GREAT |
| | ROOM. D-58 ETC. |
| | PLEASE ALSO SEE OTHER FIXTURES WHICH DOE NOT MATCH FOR |
| | THE GREAT ROOM ALONE: W, W-2, S, WHERE ARE THESE? |
| | PLEASE SE ANOTHER EXAMPLE IS THE FIXTURE WATTAGES FOR |
| | MEETING ROOM. THE FIXTURE COUNTS ARE OK, HOWEVER THE |
| | WATTAGE FOR R22 IS 32WATTS ON THE IDR AND 75WATTS ON |
| | FIXTURE LEGEND. |
| | PLEASE ALSO SEE R22D WHICH THE WATTAGE ON FIXTURE |
| | LEGEND ALONE INDICATES 32 AND 75.? |
| | PLEASE SEE MISSING 5TH FLOOR LINEN CLOSET. |
| | PLEASE SEE THE TYPICAL FLOOR LIGHTING PLANS WHICH |
| | INDICATES 3-FIXTURES FOR STORAGE ROOMS, YET THIS SAME |
| | ROOM DETAIL ON THE SAME PAGE E-104 INDICATES 2-FIXTURES |
| | IN ROOMS FOR 3RD, 4TH AND 5TH FLOORS? PLEASE SEE THE |
| | IDR WHICH INDICATES THREE FIXTURES? |
| | PLEASE SEE ELECTRICAL ROOMS/CLOSETS FOR EACH FLOOR ARE |
| | SHOWN AS TYPICAL ON PLANS, YET THE WATTAGE 7SHOWN FOR |
| | WHAT SHOULD BE THE SAME F7 FIXTURE IS SHOWN AS TWO |
| | DIFFERENT WATTAGES ON THE IDR. (SEE DIFFERENCES IN 233, |
| | 333 AND THEN BACK TO 433_ |
| | WHERE IS ELECTRICAL ROOM/CLOSET FOR 5TH FLOOR ON THE |
| | IDR? |
| | PLEASE BE SURE TO VERIFY METHOD OF CONTROLS LISTED ON |
| | THE IDR, AS DEVICES SUCH AS TIMERS ETC ARE NOT |
| | CONSIDERED *MANUAL ON/OFF*. PLEASE CORRELATE ALL |
| | METHODS OF CONTROLS. |
| | ** PLEASE SEE THAT THE ABOVE IS SOME EXAMPLES OF |
| | COORDINATION WHICH NEEDS TO TAKE PLACE BETWEEN THE |
| | ELECTRICAL LIGHTING ON PLANS AND THE LIGHTING WHICH IS |
| | PLACE IN THE INPUT DATA REPORT. THIS OFFICE CAN NOT |
| | EMPHASIZE ENOUGH THE NEED FOR COORDINATION. |
| | |
| | B) PLEASE CLARIFY RECEPTACLES WHICH ARE SHOWN FOR ROOMS |
| | ARE SWITCHED OR PROVIDE POWER TO LIGHTING SUCH AS TABLE |
| | LAMPS/FLOOR LAMPS ETC. AS PLANS DO INDICATE WHAT |
| | APPEARS TO BE LAMPS ETC IN ROOMS THEN ANY OF THESE |
| | WHICH ARE PLUGGED INTO THESE RECEPTACLES WOULD BE |
| | REQUIRED TO BE PART OF THE ROOM LIGHTING CONTROLS. THIS |
| | WOULD REQUIRE THE SAME CIRCUITS FOR RECEPTACLES OR |
| | CONTROLS INSTALLED AND PROVIDING HALF SWITCHED |
| | RECEPTACLES. |
| | PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3 |
| | |
| | C) PLEASE SEE NOT ALL THREE SETS OF THE REQUIRED ENERGY |
| | CALCULATIONS ARE SIGNED, DATED AND SEALED BY TEH |
| | DESIGNERS. IN FACT PLEASE SEE SOME ARE PHOTO-COPIED |
| | SIGNATURES AND SEALS. PLEASE ALSO SEE THE OWNER/AGENT |
| | ON TEH CERTIFICAITON SHEET(S) IS ALSO NOT DONE. FBC |
| | 13-103.1.1.1, FS 471.025, FAC 61G15-23.002 |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #15 AS THIS REQUESTED |
| | ALL HORN, STROBE OR HORN/STROBE DEVICESTO INDICATE |
| | THE MINIMUM LEVELS FOR ADA PER FBC 11-4.28.1, .2 AND |
| | .3(4). THE RESPONSE LETTER MENTIONS THIS WAS DONE AT |
| | ALL LOCATIONS ON PLANS HOWEVER PLEASE CLARIFY WHERE |
| | THESE LEVELS ARE FOR THE DEVICES LOCATED IN THE ROOMS |
| | WHICH ARE ON E-411 AND E-412? |
| | PLEASE SEE THE NOTES ON E-502 WHICH WERE CORRECTED FOR |
| | THE CANADIAN CODE HOWEVER REFERENCES TO THE REQUIRED |
| | FLORIDA BUILDING CODE COULD NOT BE FOUND. PLEASE SEE |
| | CHAPTER 11 OF THE FBC IS SUBSTANTIALLY MORE RESTRICTIVE |
| | THAN THE NFPA-72 AS NOTED. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #22 WHICH REQUESTED |
| | FOR ALL MANUFACTURES SPECS/CUT SHEETS TO BE SUBMITTED |
| | FOR THE FIRE PUMP, FIRE PUMP CONTROLLER ETC. |
| | CODES AND SECTIONS WERE GIVEN FOR THESE ITEMS WHICH AT |
| | THAT POINT COULD NOT BE REVIEWED AS NO INFORMATION WAS |
| | SUBMITTED. |
| | PLEASE SEE THE SPECS/CUT SHEETS WERE SUBMITTED HOWEVER |
| | COORDINATION WITH PLANS FROM E-401, ELECTRICAL RISER |
| | E-501, FP SHEETS AND SPECS/CUT SHEETS NEED MUCH |
| | COORDINATION. |
| | PLEASE SEE SHEET E-401 WHICH INDICATES THE FP AS 208V, |
| | 60HP AND BEING OF CERTAIN MANUFACTURE. THIS INFORMATION |
| | ON THE E-501AND MANUFACTURES SPECS/CUT SHEETS SUBMITTED |
| | DO NOT MATCH. PLEASE SEE THE SPECS INCLUDE A 480V MOTOR |
| | WHICH IS NOT POSSIBLE WHEN THE SERVICE IS BEING SHOWN |
| | AS 208V ON RISER. |
| | PLEASE SEE THE SPECS INDICATE A 75HP WHICH IS ALSO NOT |
| | THE SAME AS ON RISER AND SHEET 401. THIS WOULD CHANGE |
| | CONDUCTORS, OVER CURRENT PROTECTION ETC AT 480V AND |
| | 75HP. |
| | PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS ARE FOR |
| | DIFFERENT MANUFACTURES THAN THAT LISTED ON E401 AND |
| | THIS IS THE SAME FOR JOCKEY PUMP AND JP CONTROLLER. |
| | PLEASE KNOW THAT AS THE SPECIFIC SIZE MOTOR AND VOLTAGE |
| | HAS NOT YET BEEN DETERMINED, COMPLETE REVIEW FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE |
| | TO SEE NEC 695, NFPA-20 2003 AS NO SPECIFIC SECTIONS |
| | WILL BE GIVEN WHICH WAS NOT PREVIOUSLY NOTED. PLEASE |
| | SEE THE FPC IS LISTED WITH A DIFFERENT MANUFACTURE THAN |
| | THE PUMPS, PLEASE BE SURE ALL ITEMS ARE LISTED |
| | ASSEMBLIES AS REQUIRED. NEC 110.3, 90.7. PLEASE BE SURE |
| | TO COORDINATE WITH INFORMATION TO BE PROVIDED ON FIRE |
| | SPRINKLER PLANS AND ANY REVIEW COMMENTS FROM THE FIRE |
| | MARSHAL. |
| | NOTE #22 FROM PREVIOUS REVIEW IS BEING LEFT BELOW. |
| | |
| | ********PREVIOUS NOTE ********* |
| | 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS |
| | SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT |
| | SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS. |
| | PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT |
| | AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION |
| | WAS SUBMITTED FOR REVIEW. |
| | PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10. |
| | PLEASE ALSO SEE NEC 695.4 |
| | ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND |
| | NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST. |
| | DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR, |
| | ETC. |
| | PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING |
| | FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1. |
| | NEC 110.3, 90.7 |
| | FBC 106.1.2 ************************************** |
| | |
| | 8) NOTE: PLEASE SEE THERE IS CLARIFICATION NEEDED FOR |
| | ROOM PTAC UNITS. PLEASE SEE THE PLANS CONTAINS A *FLAG* |
| | NOTE WHICH MENTIONS THESE UNITS ARE GOING TO BE |
| | HARDWIRED YET THE SAME PLANS AT THE SAME LOCATION ON |
| | SHEET E-411 ALSO CONTAINS AN OCTAGONAL NOTE #6 WHICH |
| | MENTIONS THESE ARE GOING TO BE 30AMP RECEPTACLE FOR |
| | THIS SAME UNIT? (6-30R). |
| | ADMIN SECTION 106.1.2, 106.3.5.1.2 FOR COORDINATION. |
| | |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTE #34 WITH RESPECT TO |
| | THE GROUNDING ELECTRODE FOR THE FIRE PUMP SERVICE. AS |
| | THE SIZE, VOLTAGE AND RATING OF SERVICE IS NOT CLEAR |
| | THIS NOTE WILL REMAIN. THE RISER SHOWS *2G*, WHAT IS |
| | THIS? |
| | PLEASE SEE MISSING SIZE OF THE GROUNDING ELECTRODE |
| | CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50, 250.66 |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #35 WHICH REQUESTED |
| | TO CLARIFY AND SHOW ALL CONTINUOUS LOADS AT 125% FOR |
| | POOL PANEL (PANEL P). PLEASE SEE PANEL P AS SHOWN ON |
| | E501, WHERE IS THIS IDENTIFIED? |
| | **PREVIOUS REVIEW NOTE ** |
| | ** PLEASE SEE LOADS FOR CONTINUOUS LOADS IN PANEL "P" |
| | NEED TO BE SHOWN.. |
| | PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC. |
| | PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY |
| | NOTED FOR CONTINUOUS LOADS. |
| | 220, 215.3, 230.42. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS NOTE #44, WHERE IS THE |
| | TRACK LIGHTING LOADS SHOWN IN THE LOAD CALCULATIONS? |
| | PLEASE SHOW AND COMPLETE LOAD CALCULATIONS FOR TRACK |
| | LIGHTING PER 220.12B |
| | |
| | ** PLEASE KNOW ONCE ALL REVIEWS ARE DONE, ONE ROLL MAY |
| | BE RETAINED BY THIS OFFICE DUE TO REPEAT COMMENTS FOR |
| | CODE COMPLIANCE AND PREVIOUS NOTE TO FS 553.80(2)(B). |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-30 08:40:19 | 2007-09-30 08:40:19 |
| | |
| | REVIEW IN PROGRESS |
| 2007-09-28 21:24:58 | 2007-09-28 21:24:58 |
| | |
| | REVIEW IN PROGRESS, NOTES TO FOLLOW ONCE REVIEW IS |
| | COMPLETED. |
| 2007-09-27 20:01:15 | 2007-09-27 20:01:15 |
| | |
| | ONE SET IN ELECTRICAL FOR REVIEW. |