Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-30 11:15:202007-09-30 11:15:20
  
 ** DENIED 3RD REVIEW ***
 SPRINGHILLSUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS AND/OR REVISIONS TO PLANS WHICH INFORMATION IS
 ONLY NOW BEING SUBMITTED. DUE TO CHANGES AND
 INFORMATION WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW,
 THESE ITEMS COULD NOT HAVE COMMENTED ON AS SOME ITEMS
 AND INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE
 ITEMS WILL BE CLEARLY NOTED.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH REQUESTED
 FOR THE PRODUCT APPROVALS ETC NOT TO BE ATTACHED TO
 ROLLS. THIS WAS OK, AND THESE WERE NOT ATTACHED HOWEVER
 OF THE TWO ROLLS OF PLANS THIS REVIEWER REVIEWED, ALL
 SHEETS IN BOTH ROLLS WERE LOOSE AND NOT ATTACHED INTO
 SECURED ROLLS.
 PLEASE DO NOT SUBMIT ROLLS OF PLANS IN WHICH THE SHEETS
 ARE LOOSE AND NOT ATTACHED.THESE TWO ROLLS WERE
 SECURED BY THIS OFFICE.
 PLEASE SEE SOME SHEETS IN SETS ARE ACTUALLY INSERTED
 BACKWARDS AND UPSIDE DOWN. (S-SHEETS).
 FBC ADMIN SECTION 106.1, 106.5 ETC.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WITH
 RESPECT TO SIGNATURE VERIFICATION LETTER(S). THIS WAS
 SUBMITTED HOWEVER WAS NOT SEALED AS PREVIOUSLY
 REQUESTED.
 THIS CAN BE SUBMITTED AT ANY TIME.
 FS 471.025, 481.025 AND FAC 61G15-23.002, 61G1-16.004
  
 THIS WAS COMPLETELY STATED ON PREVIOUS NOTE #2.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #4 WHICH MENTIONED
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER. AS
 PLANS WERE REVISED REMOVING ARCHITECTURAL FIRM MOST
 SHEETS ARE CORRECT HOWEVER PLEASE SEE THAT SOME SHEETS
 IN SOME SETS STILL CONTAIN PFVS (HOMEWOOD) AND COVER
 SHEETS (SPRINGHILL) STILL CALL FOR PFVS ARCHITECTS
 INC.
  
 THIS REVIEWER HAS SPOKEN WITH MR. KEY AND IT IS THE
 UNDERSTANDING THE FIRM NOW HAS OBTAINED THE REQUIRED
 LICENSING THROUGH THE STATE. PLEASE KNOW THAT ALL
 INFORMATION ON TITLE BLOCKS MAY BE REVISED AND
 CORRECTED ONCE ALL REVIEWS ARE COMPLETED AND PLANS ARE
 PICKED UP FOR CORRECTIONS.
 PLEASE SEE FS481.219, FAC 61G1-16.004
  
 4) NOTE: THIS IS A NEW COMMENT: PLEASE SEE THE SEAL
 WHICH IS NOW BEING USED ON ALL THREE SETS FOR BOTH
 HOTELS FOR THE ARCHITECT OF RECORD MR. GREG PORTMAN IS
 NO LONGER ACCEPTED IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FAC61G1-16.002 WHICH CHANGED SEVERAL
 YEARS AGO, WHICH NOW REQUIRES A MINIMUM SEAL SIZE OF
 2INCHES. PLEASE SEE THE NEW SHEETS NOW SUBMITTED
 CONTAINS AN OLD SEAL.
 IF THIS WAS THE ONLY COMMENT ON PLANS, THE ARCHITECT OF
 RECORD WOULD BE ABLE TO COME INTO THIS OFFICE AND
 RE-SIGN, DATE AND SEAL PLANS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO
 FBC CHAPTER 13.
  
 A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED
 STILL NEED SOME COORDINATION WITH ELECTRICAL LIGHTING
 ON PLANS. PLEASE THE INPUT DATA REPORT WHICH WILL BE
 NOTED AS IDR ON THE FOLLOWING DOES NOT CORRELATE WITH
 ALL LIGHTING ON PLANS AND FIXTURE LIGHTING LEGEND.
 PLEASE SEE SOME OF THE FOLLOWING EXAMPLES: EXTERIOR
 LIGHTING WHICH IS ON PLANS DOES NOT MATCH WITH THE IDR
 FOR THE SAME NUMBER OF FIXTURES, TYPE(S) AND WATTAGE.
 PLEASE SEE FRONT ENTRANCE AREA Z-21, 32WATT ON IDR AND
 100WATTS ON FIXTURE LEGEND.
 PLEASE SEE FOR EXAMPLE THE WATTAGE WHICH IS REQUIRED
 FOR THE IDR FOR TRACK LIGHT IF LINE VOLTAGE OR LOW
 VOLTAGE IS REQUIRED TO MEET 13-415.2.ABC .1.2. THIS
 INFORMATION ON THE IDR DOES NOT COORDINATE WITH THE
 NOTES ON E-402 AS THE WATTAGE BEING LISTED FOR MAXIMUM
 IS NOT THAT WHICH IS LISTED ON THE IDR FOR THE GREAT
 ROOM. D-58 ETC.
 PLEASE ALSO SEE OTHER FIXTURES WHICH DOE NOT MATCH FOR
 THE GREAT ROOM ALONE: W, W-2, S, WHERE ARE THESE?
 PLEASE SE ANOTHER EXAMPLE IS THE FIXTURE WATTAGES FOR
 MEETING ROOM. THE FIXTURE COUNTS ARE OK, HOWEVER THE
 WATTAGE FOR R22 IS 32WATTS ON THE IDR AND 75WATTS ON
 FIXTURE LEGEND.
 PLEASE ALSO SEE R22D WHICH THE WATTAGE ON FIXTURE
 LEGEND ALONE INDICATES 32 AND 75.?
 PLEASE SEE MISSING 5TH FLOOR LINEN CLOSET.
 PLEASE SEE THE TYPICAL FLOOR LIGHTING PLANS WHICH
 INDICATES 3-FIXTURES FOR STORAGE ROOMS, YET THIS SAME
 ROOM DETAIL ON THE SAME PAGE E-104 INDICATES 2-FIXTURES
 IN ROOMS FOR 3RD, 4TH AND 5TH FLOORS? PLEASE SEE THE
 IDR WHICH INDICATES THREE FIXTURES?
 PLEASE SEE ELECTRICAL ROOMS/CLOSETS FOR EACH FLOOR ARE
 SHOWN AS TYPICAL ON PLANS, YET THE WATTAGE 7SHOWN FOR
 WHAT SHOULD BE THE SAME F7 FIXTURE IS SHOWN AS TWO
 DIFFERENT WATTAGES ON THE IDR. (SEE DIFFERENCES IN 233,
 333 AND THEN BACK TO 433_
 WHERE IS ELECTRICAL ROOM/CLOSET FOR 5TH FLOOR ON THE
 IDR?
 PLEASE BE SURE TO VERIFY METHOD OF CONTROLS LISTED ON
 THE IDR, AS DEVICES SUCH AS TIMERS ETC ARE NOT
 CONSIDERED *MANUAL ON/OFF*. PLEASE CORRELATE ALL
 METHODS OF CONTROLS.
 ** PLEASE SEE THAT THE ABOVE IS SOME EXAMPLES OF
 COORDINATION WHICH NEEDS TO TAKE PLACE BETWEEN THE
 ELECTRICAL LIGHTING ON PLANS AND THE LIGHTING WHICH IS
 PLACE IN THE INPUT DATA REPORT. THIS OFFICE CAN NOT
 EMPHASIZE ENOUGH THE NEED FOR COORDINATION.
  
 B) PLEASE CLARIFY RECEPTACLES WHICH ARE SHOWN FOR ROOMS
 ARE SWITCHED OR PROVIDE POWER TO LIGHTING SUCH AS TABLE
 LAMPS/FLOOR LAMPS ETC. AS PLANS DO INDICATE WHAT
 APPEARS TO BE LAMPS ETC IN ROOMS THEN ANY OF THESE
 WHICH ARE PLUGGED INTO THESE RECEPTACLES WOULD BE
 REQUIRED TO BE PART OF THE ROOM LIGHTING CONTROLS. THIS
 WOULD REQUIRE THE SAME CIRCUITS FOR RECEPTACLES OR
 CONTROLS INSTALLED AND PROVIDING HALF SWITCHED
 RECEPTACLES.
 PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3
  
 C) PLEASE SEE NOT ALL THREE SETS OF THE REQUIRED ENERGY
 CALCULATIONS ARE SIGNED, DATED AND SEALED BY TEH
 DESIGNERS. IN FACT PLEASE SEE SOME ARE PHOTO-COPIED
 SIGNATURES AND SEALS. PLEASE ALSO SEE THE OWNER/AGENT
 ON TEH CERTIFICAITON SHEET(S) IS ALSO NOT DONE. FBC
 13-103.1.1.1, FS 471.025, FAC 61G15-23.002
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #15 AS THIS REQUESTED
 ALL HORN, STROBE OR HORN/STROBE DEVICESTO INDICATE
 THE MINIMUM LEVELS FOR ADA PER FBC 11-4.28.1, .2 AND
 .3(4). THE RESPONSE LETTER MENTIONS THIS WAS DONE AT
 ALL LOCATIONS ON PLANS HOWEVER PLEASE CLARIFY WHERE
 THESE LEVELS ARE FOR THE DEVICES LOCATED IN THE ROOMS
 WHICH ARE ON E-411 AND E-412?
 PLEASE SEE THE NOTES ON E-502 WHICH WERE CORRECTED FOR
 THE CANADIAN CODE HOWEVER REFERENCES TO THE REQUIRED
 FLORIDA BUILDING CODE COULD NOT BE FOUND. PLEASE SEE
 CHAPTER 11 OF THE FBC IS SUBSTANTIALLY MORE RESTRICTIVE
 THAN THE NFPA-72 AS NOTED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #22 WHICH REQUESTED
 FOR ALL MANUFACTURES SPECS/CUT SHEETS TO BE SUBMITTED
 FOR THE FIRE PUMP, FIRE PUMP CONTROLLER ETC.
 CODES AND SECTIONS WERE GIVEN FOR THESE ITEMS WHICH AT
 THAT POINT COULD NOT BE REVIEWED AS NO INFORMATION WAS
 SUBMITTED.
 PLEASE SEE THE SPECS/CUT SHEETS WERE SUBMITTED HOWEVER
 COORDINATION WITH PLANS FROM E-401, ELECTRICAL RISER
 E-501, FP SHEETS AND SPECS/CUT SHEETS NEED MUCH
 COORDINATION.
 PLEASE SEE SHEET E-401 WHICH INDICATES THE FP AS 208V,
 60HP AND BEING OF CERTAIN MANUFACTURE. THIS INFORMATION
 ON THE E-501AND MANUFACTURES SPECS/CUT SHEETS SUBMITTED
 DO NOT MATCH. PLEASE SEE THE SPECS INCLUDE A 480V MOTOR
 WHICH IS NOT POSSIBLE WHEN THE SERVICE IS BEING SHOWN
 AS 208V ON RISER.
 PLEASE SEE THE SPECS INDICATE A 75HP WHICH IS ALSO NOT
 THE SAME AS ON RISER AND SHEET 401. THIS WOULD CHANGE
 CONDUCTORS, OVER CURRENT PROTECTION ETC AT 480V AND
 75HP.
 PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS ARE FOR
 DIFFERENT MANUFACTURES THAN THAT LISTED ON E401 AND
 THIS IS THE SAME FOR JOCKEY PUMP AND JP CONTROLLER.
 PLEASE KNOW THAT AS THE SPECIFIC SIZE MOTOR AND VOLTAGE
 HAS NOT YET BEEN DETERMINED, COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE BE SURE
 TO SEE NEC 695, NFPA-20 2003 AS NO SPECIFIC SECTIONS
 WILL BE GIVEN WHICH WAS NOT PREVIOUSLY NOTED. PLEASE
 SEE THE FPC IS LISTED WITH A DIFFERENT MANUFACTURE THAN
 THE PUMPS, PLEASE BE SURE ALL ITEMS ARE LISTED
 ASSEMBLIES AS REQUIRED. NEC 110.3, 90.7. PLEASE BE SURE
 TO COORDINATE WITH INFORMATION TO BE PROVIDED ON FIRE
 SPRINKLER PLANS AND ANY REVIEW COMMENTS FROM THE FIRE
 MARSHAL.
 NOTE #22 FROM PREVIOUS REVIEW IS BEING LEFT BELOW.
  
 ********PREVIOUS NOTE *********
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION
 WAS SUBMITTED FOR REVIEW.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
 NEC 110.3, 90.7
 FBC 106.1.2 **************************************
  
 8) NOTE: PLEASE SEE THERE IS CLARIFICATION NEEDED FOR
 ROOM PTAC UNITS. PLEASE SEE THE PLANS CONTAINS A *FLAG*
 NOTE WHICH MENTIONS THESE UNITS ARE GOING TO BE
 HARDWIRED YET THE SAME PLANS AT THE SAME LOCATION ON
 SHEET E-411 ALSO CONTAINS AN OCTAGONAL NOTE #6 WHICH
 MENTIONS THESE ARE GOING TO BE 30AMP RECEPTACLE FOR
 THIS SAME UNIT? (6-30R).
 ADMIN SECTION 106.1.2, 106.3.5.1.2 FOR COORDINATION.
  
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #34 WITH RESPECT TO
 THE GROUNDING ELECTRODE FOR THE FIRE PUMP SERVICE. AS
 THE SIZE, VOLTAGE AND RATING OF SERVICE IS NOT CLEAR
 THIS NOTE WILL REMAIN. THE RISER SHOWS *2G*, WHAT IS
 THIS?
 PLEASE SEE MISSING SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50, 250.66
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #35 WHICH REQUESTED
 TO CLARIFY AND SHOW ALL CONTINUOUS LOADS AT 125% FOR
 POOL PANEL (PANEL P). PLEASE SEE PANEL P AS SHOWN ON
 E501, WHERE IS THIS IDENTIFIED?
 **PREVIOUS REVIEW NOTE **
 ** PLEASE SEE LOADS FOR CONTINUOUS LOADS IN PANEL "P"
 NEED TO BE SHOWN..
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY
 NOTED FOR CONTINUOUS LOADS.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #44, WHERE IS THE
 TRACK LIGHTING LOADS SHOWN IN THE LOAD CALCULATIONS?
 PLEASE SHOW AND COMPLETE LOAD CALCULATIONS FOR TRACK
 LIGHTING PER 220.12B
  
 ** PLEASE KNOW ONCE ALL REVIEWS ARE DONE, ONE ROLL MAY
 BE RETAINED BY THIS OFFICE DUE TO REPEAT COMMENTS FOR
 CODE COMPLIANCE AND PREVIOUS NOTE TO FS 553.80(2)(B).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-30 08:40:192007-09-30 08:40:19
  
 REVIEW IN PROGRESS
2007-09-28 21:24:582007-09-28 21:24:58
  
 REVIEW IN PROGRESS, NOTES TO FOLLOW ONCE REVIEW IS
 COMPLETED.
2007-09-27 20:01:152007-09-27 20:01:15
  
 ONE SET IN ELECTRICAL FOR REVIEW.