Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop B
Sequence Number 22
Notes
Date Text
2009-04-06 09:54:38BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 1ST REVIEW REVISION# 4
 ACTION: DENIED
 A101, A101A, AR101, AR101A, A401 & AR401
  
 THE ORIGINAL ISSUED PLANS INDICATED A 1 HR RATED WALL
 THAT SEPERATED THE LAUNDRY WORK ROOM, THE SALES OFFICE
 FROM THE LOBBY AREAS. THE LOBBY IS A CONTINUATION OF
 THE FIRE RATED CORRIDOR
 REQUIRED UNDER TABLE 1016.1 OCCUPANT LOADS SERVED
 GREATER THAN 30 WITH OR WITHOUT SPRINKLERS REQUIRES A 1
 HR FIRE SEPERATION WALL. 1016.5 CORRIDOR CONTINUITY
 DOES ALLOW THE FOYER, LOBBY TO BE PART OF THE CORRIDOR
 SEE EXCEPTION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.