| 2009-04-06 09:54:38 | BUILDING PLAN REVIEW |
| | PERMIT: 06111067 |
| | ADD: 2437 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | SPRINGHILL SUITES BY MARIOTT |
| | FIVE STORY/ 130 UNITS |
| | |
| | 1ST REVIEW REVISION# 4 |
| | ACTION: DENIED |
| | A101, A101A, AR101, AR101A, A401 & AR401 |
| | |
| | THE ORIGINAL ISSUED PLANS INDICATED A 1 HR RATED WALL |
| | THAT SEPERATED THE LAUNDRY WORK ROOM, THE SALES OFFICE |
| | FROM THE LOBBY AREAS. THE LOBBY IS A CONTINUATION OF |
| | THE FIRE RATED CORRIDOR |
| | REQUIRED UNDER TABLE 1016.1 OCCUPANT LOADS SERVED |
| | GREATER THAN 30 WITH OR WITHOUT SPRINKLERS REQUIRES A 1 |
| | HR FIRE SEPERATION WALL. 1016.5 CORRIDOR CONTINUITY |
| | DOES ALLOW THE FOYER, LOBBY TO BE PART OF THE CORRIDOR |
| | SEE EXCEPTION. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE |
| | APPLICABLE. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |