| Date |
Text |
| 2007-04-16 16:51:07 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND |
| | THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE |
| | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS |
| | 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS |
| | ALL INFORMATION REQUIRED BY FAC 61G1-16.002 & FS |
| | 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON |
| | EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION |
| | IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE |
| | ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE |
| | PLANS. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. FIRM |
| | LICENSE FOR PFVS ARCHITECTS INC. IS NOT INDICATED IN |
| | THE TITLE BLOCK NOR HAS THE INFORMATION REQUIRED WHEN |
| | SEALING THE SHEETS BEEN ADDRESSED. |
| | |
| | 2.OK |
| | |
| | 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN |
| | THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | ****RESPONSE NOTED, BUT ENGINEERING CA# NOT INDICATED |
| | AS WELL AS THE REQUIREMENT FOR THE ARCHITECTURE, |
| | (BUSINESS NUMBER), HAS NOT BEEN ADDRESSED. |
| | |
| | 4. OK |
| | |
| | 5. SHT G-000 GUESTROOM MATRIX INDICATES 2 HEARING |
| | IMPAIRED UNITS, STANDARD DOUBLE/DOUBLE, BUT THE FLOOR |
| | PLANS SHTS A-101 THRU A-105 ONLY SHOW 1 ON THE 4TH |
| | FLOOR. PLEASE CLARIFY & CORRELATE INFORMATION BETWEEN |
| | THE FLOOR PLANS & MATRIX. SECTION 106.1.1 & SECTION |
| | 11-9.1.3.-PLEASE INDICATE WHICH ROOMS COMPLY WITH |
| | SECTION 11-9.1.3. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED. |
| | |
| | 6. SHT G-000 PLEASE CLARIFY THE DIFFERENCE BETWEEN A |
| | KING STANDARD, A KING CONNECTOR, A KING SUITE, AND |
| | INDICATE HOW THE ACCESSIBLE UNITS ARE DISPERSED AMONG |
| | THE VARIOUS CLASSES. ALSO PLEASE CLARIFY DIFFERENCE |
| | BETWEEN THE KING TYPE A, KING ALTERNATE, THE KING & THE |
| | KING ALT B AND INDICATE HOW THE ACCESSIBLE UNITS ARE |
| | DIAPERSED AMONG THE VARIOUS CLASSES.--PLEASE |
| | CLARIFY THE DIFFERENCE BETWEEN THE DOUBLE/DOUBLE |
| | STANDARD, THE DOUBLE/DOUBLE CONNECTOR STANDARD, THE |
| | DOUBLE/DOUBLE TYPE "A", THE DOUBLE/DOUBLE TYPE "B", THE |
| | DOUBLE/DOUBLE TYPE "C", THE DOUBLE/DOUBLE SUITE TYPE |
| | "A", THE DOUBLE/DOUBLE SUITE TYPE "B", AND THE |
| | DOUBLE/DOUBLE ALTERNATE.--THE DIFFERENCES SHALL BE |
| | CALLED OUT ON THE PLANS.-- OF CONCERN ALSO IS THE |
| | MATRIX DOES NOT MENTION THE PRESIDENTIAL SUITE SHOWN ON |
| | SHT A-411, AND IS INDICATED AS A DOUBLE/DOUBLE ON SHTS |
| | A-103, A-104 & A-105. PLEASE INDICATE WHY AN ACCESSIBLE |
| | UNIT FOR THE PRESIDENTIAL SUIT IS NOT PROVIDED.-- |
| | ALSO OF CONCERN IS THE GUESTROOM MATRIX SHOWS |
| | ACCESSIBLE KING UNITS UNDER THE SECTION OF THE MATRIX |
| | INDICATED AS "KING GUESTROOMS", BUT UNDER THE SECTION |
| | INDICATED AS "DOUBLE/DOUBLE GUESTROOMS" THE ACCESSIBLE |
| | UNITS ARE "KING ACCESSIBLE UNITS". PLEASE CLARIFY. |
| | PLEASE COMPLY WITH SECTION 11-9.1.2. |
| | ****NO RESPONSE, COMMENT NOT ADDRESSED.- 4TH FLOOR |
| | SHOWS 2 ACCESSIBLE KINGS & KING CONN., BUT THE MATRIX |
| | SHOWS 2 KING'S WITH ROLL-IN SHOWERS. PLEASE CLARIFY.- |
| | THE MATRIX INDICATES A KING-SUITE ON THE 4TH FLOOR, BUT |
| | THE FLOOR PLAN DOES NOT SHOW A KING SUITE. PLEASE |
| | INDICATE THE ROOM NUMBER & INDICATE WHY IT IS NOT |
| | ACCESSIBLE. |
| | |
| | 7. SHT G-000 GUESTROOM MATRIX DOES NOT REFLECT THE |
| | FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX |
| | INDICATES A TOTAL OF 7 ACCESSIBLE UNITS, BUT THE FLOOR |
| | PLANS INDICATE A TOTAL OF 12 UNITS. PLEASE CORRELATE |
| | THE INFORMATION ON THE MATRIX AND THE FLOOR PLANS. |
| | SECTIONS 106.1.1 AND 11-9.1.2. |
| | ****RESPONSE NOTED, BUT THE FLOOR PLAN SHOWS 12 |
| | ACCESSIBLE UNITS, WITH 4 UNITS FOR THE HEARING |
| | IMPAIRED. THE MATRIX, (NOW ON SHT G-002), SHOWS ONLY 8 |
| | ACCESSIBLE UNITS, AND 5 UNITS FOR THE HEARING IMPAIRED |
| | ARE REQUIRED.-SECTION 11-9.2.3 INDICATES 2 UNITS |
| | REQUIRED. PLEASE INDICATE WHICH UNITS MEET THIS |
| | REQUIREMENT. (GIVE ROOM NUMBERS). |
| | |
| | 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR |
| | EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA. |
| | ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO |
| | THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING |
| | DRAINED BY EACH DRAIN. |
| | ****RESPONSE NOTED, BUT NO CALCULATION WERE FOUND. |
| | PLEASE SUBMIT THE CALCULATIONS REQUESTED. |
| | |
| | 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN. |
| | PLEASE CLARIFY. SECTION 1106.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR |
| | EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE |
| | UNITS. SECTIONS 11-4.16. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 11. SHT A-600 FINISH SCHEDULE FOR ROOMS 134, 150, & 151 |
| | SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2 |
| | CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT |
| | AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT. |
| | PLEASE COMPLY. |
| | ****NO RESPONSE, SHEET DELETED. PLEASE SUBMIT FINISH |
| | SCHEDULE SHOWING REQUIRED INFORMATION. |
| | |
| | 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH |
| | CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A |
| | MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE |
| | NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO |
| | BE INSTALLED. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803 |
| | APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE |
| | ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22 |
| | AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS. |
| | ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN. |
| | 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE |
| | THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28 |
| | AND 11-32. |
| | ****NO RESPONSE. SHOW THE FOLLOWING: |
| | SHT A-802.. |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ___FOR URINALS: |
| | A. 11-4.18.3 CLEAR FLOOR SPACE |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | ____FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES (CLEARANCES) |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | SHT A-803 |
| | ___FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | ___FOR LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | ___FOR TUBS: |
| | A. 11-4.20.2 CLEAR FLOOR SPACE |
| | B. 11-4.20.5 CONTROLS |
| | ___FOR TOILET ROOMS |
| | A. 11-4.22.3 TURNING AREA (ALL ACCESSIBLE |
| | BATHROOMS). |
| | W/C'S NOT SHOWN AT 18" TO THE CENTERLINE OF THE FIXTURE |
| | OFF THE WALLS. |
| | |
| | |
| | 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE |
| | C. 11-4.24.7 FAUCETS |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | |
| | 15. N/A |
| | |
| | 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE. |
| | MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER |
| | SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE |
| | WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM. |
| | PLEASE CLARIFY.SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING: |
| | A. 11-4.19.2 CLEARANCE |
| | B. 11-4.19.5 FAUCETS |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | |
| | 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES |
| | SHOW NO PIPING OR BRANCH LINES CONNECTING THE |
| | RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | |
| | 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT |
| | VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT |
| | REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE |
| | THE FLOOR PLANS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE PLANS NOW SHOW A 3" VENT |
| | THAT APPEARS TO BE A DRY HORIZONTAL VENT. THIS IS NOT |
| | SHOWN ON THE SANITARY RISER DIAGRAM SO ITS NOT CLEAR. |
| | PLEASE INDICATE ALL PIPING ON THE HORIZONTAL PIPING |
| | ISOMETRIC FOR ALL PIPING UP TO ALL RISERS AND |
| | FIXTURES/FIXTURE GROUPS ON THE FIRST FLOOR TO REFLECT |
| | THE FLOOR PLAN. |
| | |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | |
| | 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN |
| | ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A |
| | VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE |
| | BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP |
| | ROOM ETC.). |
| | ****RESPONSE NOTED, BUT NOT ALL FIXTURES OR FIXTURES |
| | GROUPS FOR THE FIRST FLOOR ARE SHOWN ON THE HORIZONTAL |
| | SANITARY RISER ISOMETRIC DIAGRAM. THE 1ST FLOOR IS |
| | WHERE THE BRANCH LINE CONNECTS ALL RISERS, TOILET |
| | ROOMS, PUMP ROOMS, LAUNDRY, FOOD PREP ROOM, BREAK ROOM, |
| | VENDING, VENTING ETC. AND ALL THIS PIPING SHALL BE |
| | SHOWN CONNECTING TO THE HORIZONTAL ISOMETRIC. |
| | |
| | 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS, |
| | WASH MACHINES, AND DISHWASHERS). |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC |
| | RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL |
| | PIPE SIZES AND INDICATE THE TERMINATION POINT. |
| | ****RESPONSE NOTED, BUT IF THE CONDENSATE IS CONNECTING |
| | TO THE STORM LINE, A RELIEF VENT WILL BE REQUIRED AS |
| | THE CONDENSATE LINE EXITS THE BUILDING. PLEASE SHOW THE |
| | RELIEF VENT AND THE TERMINATION POINT ON THE RISER |
| | DIAGRAM. |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETAIL 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED BY HAVING |
| | MULTIPLE RISERS WITH THE SAME DESIGNATION, SUCH AS |
| | RISER 2 OR RISER 8. ALL RISER NUMBERS SHALL BE SHOWN ON |
| | THE HORIZONTAL ISOMETRIC AND THE FLOOR PLANS OF EACH |
| | FLOOR. |
| | |
| | 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO |
| | SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE |
| | "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION |
| | 102.2.1. |
| | ****RESPONSE NOTED, BUT "REVIEWED, STAMPED" PLANS AND |
| | ATTACHED "TWO PAGE WORKSHEET" SHALL BE REQUIRED FOR |
| | EACH SET OF PLANS AT THE TIME OF RESUBMITTING FOR |
| | REVIEW TO THE CITY. |
| | |
| | 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE |
| | FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION |
| | 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL. |
| | INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE |
| | GREASE INTERCEPTOR. CONTACT HER BY PHONE (561) |
| | 822-2271, FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. |
| | ****RESPONSE NOTED, NO COMMENT FROM ENVIRONMENTAL AS OF |
| | YET. |
| | |
| | 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND |
| | MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING |
| | ON THE REVISIONS OR COMMENT RESPONSES. |
| | ****MORE INFORMATION IS STILL REQUIRED. SEE COMMENTS. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHT A-101AIS MISLABELED AS 2ND FLOOR PLAN. PLEASE |
| | CORRECT. SECTION 106.1.1. |
| | |
| | 2B. SHT A-401 THE TURNING AREA IS TO BE IN THE TOILET |
| | ROOM, NOT THE ACCESSIBLE STALL. SECTION 11-4.22.3. (SEE |
| | ROOMS 150 & 151). |
| | |
| | 3B. SUBMIT ISOMETRIC STORM RISER DIAGRAMS FOR EACH RWL. |
| | SHOW ALL PIPE SIZES, OFFSETS, SQUARE FOOTAGE & INDICATE |
| | THE TERMINATION POINT FOR EACH ROOF DRAIN. IF THERE ARE |
| | TYPICAL RWL'S, INDICATE THE ROOF DRAINS THAT ARE |
| | TYPICAL OF WHICH RWL. EACH RWL AND ROOF DRAIN SHALL BE |
| | NUMBERED SUCH AS RWL-1, RWL-2 AND RD-1, RD-2 AND SHALL |
| | BE INDICATED ON EACH FLOOR PLAN SO AS TO TRACK EACH |
| | RWL/RD THROUGH THE BUILDING. TABLE 1106.3 AND SECTION |
| | 106.1.3.5.1.3(7)(13). |
| | |
| | 4B. RESPONSE SHEETS DO NOT REFLECT THE COMMENTS FROM |
| | THE PREVIOUS REVIEW. SOME COMMENT RESPONSES DO NO |
| | REFLECT ANY COMMENTS FROM THE PREVIOUS REVIEW, AND THE |
| | COMMENT RESPONSE NUMBERS DO NOT REFLECT ALL COMMENT |
| | NUMBERS FROM THE PREVIOUS REVIEW. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |