2007-04-09 14:19:11*** DENIED ***
 1) MINICK ENGINEERING INC. CERTIFICATE OF AUTHORIZATION
 NUMBER EXPIRED 2-28-07, PLEASE CORRECT.
  
 2) ARCHITECT FIRM'S LICENSE NUMBER IS MISSING FROM THE
 TITLE BLOCK, SEE FAC 61G1-16.004. PLEASE CORRECT.
  
 3) PLEASE ADD A NOTE TO PAGE M-106 MECH. ROOF PLAN. NO
 PLUMBING VENT PIPES OR OTHER EXHAUST VENTS WITH IN 10
 FEET OF THE OUTSIDE AIR INTAKE OF THE A/C PACKAGE
 UNITS. SEE 2004 FBC/M 401.5.1.
  
 4) PLEASE SUBMIT THREE SETS OF THE ENERGY
 CALCULATIONS.
  
 5) THE SUBMITTAL FOR THE RUSKIN WALL LOUVERS NOTICE OF
 ACCEPTANCE EXPIRED ON 7-9-01, PLEASE CORRECT.
  
 6) AS REQUESTED IN LAST REVIEW 1-26-07 NOTE #5 PLEASE
 PROVIDE PRODUCT APPROVALS FOR 18"X18" HURRICANE LOUVER
 VENTS ON POOL EQUIPMENT ROOM #166, AND FOR THE
 PER-ENGINEERED A/CCONDENSER STANDS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.