| 2007-04-09 14:19:11 | *** DENIED *** |
| | 1) MINICK ENGINEERING INC. CERTIFICATE OF AUTHORIZATION |
| | NUMBER EXPIRED 2-28-07, PLEASE CORRECT. |
| | |
| | 2) ARCHITECT FIRM'S LICENSE NUMBER IS MISSING FROM THE |
| | TITLE BLOCK, SEE FAC 61G1-16.004. PLEASE CORRECT. |
| | |
| | 3) PLEASE ADD A NOTE TO PAGE M-106 MECH. ROOF PLAN. NO |
| | PLUMBING VENT PIPES OR OTHER EXHAUST VENTS WITH IN 10 |
| | FEET OF THE OUTSIDE AIR INTAKE OF THE A/C PACKAGE |
| | UNITS. SEE 2004 FBC/M 401.5.1. |
| | |
| | 4) PLEASE SUBMIT THREE SETS OF THE ENERGY |
| | CALCULATIONS. |
| | |
| | 5) THE SUBMITTAL FOR THE RUSKIN WALL LOUVERS NOTICE OF |
| | ACCEPTANCE EXPIRED ON 7-9-01, PLEASE CORRECT. |
| | |
| | 6) AS REQUESTED IN LAST REVIEW 1-26-07 NOTE #5 PLEASE |
| | PROVIDE PRODUCT APPROVALS FOR 18"X18" HURRICANE LOUVER |
| | VENTS ON POOL EQUIPMENT ROOM #166, AND FOR THE |
| | PER-ENGINEERED A/CCONDENSER STANDS. |
| | PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |