Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop G
Sequence Number 2
Notes
Date Text
2007-04-16 18:23:21DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ***FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE FIRST THREE CUT SECTIONS
 DOWNSTREAM OF THE METER, AND TWO SECTIONS OF PIPE IN
 THE CEILING DO NOT SHOW THE LENGHTS OF PIPES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRSSED. PIPE SIZES SHALL BE
 SHOWN FOR ALL SECTIONS OF PIPE AND VALVES SHALL BE FULL
 SIZE FOR THE PIPE SIZE INDICATED TO THE GAS EQUIPMENT.
  
 3. OK - NATURAL
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE TOTAL BTU'S ADDS UP TO
 1,785,000, BUT IS SHOWN AS TOTAL OF 2,100,000 BTU'S.
 PLEASE CLARIFY. - PLEASE IDENTIFY ALL APPLIANCES ON THE
 ISOMETRIC.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (CLOTHS DRYERS).
 ****NO RESPONSE, NOT ADDRESSED.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT THE UTILITY COMPANY DOES NOT
 DELEVER 1PSI. PLANS SHOW 7" TO 14" WC. AND 1PSI. PLEASE
 CHECK WITH GAS PROVIDER.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ****NO RESPONSE, NOT ADDRESSED.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. N/A (NATURAL GAS)
 11. N/A (NATURAL GAS)
  
 **********NEW COMMENTS**********
  
 1B. SHT P502 RISER SHOWS VALVES IN THE CEILING. THESE
 VALVES ARE NOT REQUIRED, BUT IF THE VALVES ARE LEFT IN,
 A UNION IS REQUIRED FOR EACH VALVE, AND THE VALVE AND
 UNION ARE NOT APPROVED IN THE CEILING.--A NOTE
 INDICATES "SOLENOID VALVE TYPICAL" PLEASE CLARIFY.
 SECTION 106.1.1.
  
 2B. SHT P502 DETAIL 7 INDICATES "DESIGNED ACCORDING TO
 THE 2000 IFGC" & "DESIGNED ACCORDING TO THE 2003 IFGC".
 THE CODE ADOPTED AND IN EFFECT IS THE FBC-2004. PLEASE
 CHANGE CODE REFERENCES. SECTION 106.1.1.
  
 3B. PER ELECTRICAL REVIEW COMMENT #47 SEE ATTACHED
 SHEET CONCERNING THE DESIGN PROFESSIONAL AND FS
 533.80(2)(B). THIS IS GIVEN AS A NOTICE ONLY & ONE TIME
 ONLY.
  
 4B. ALL MEP SHEETS. THE ENGINEERING COMPANY'S
 CERTIFICATE OF AUTHORIZATION NUMBER SHOWS DELINQUENT ON
 THE FLORIDA DBPR WEBSITE. SEE SHEET ATTACHED TO
 ELECTRICAL PLAN REVIEW NOTES. THIS SHALL BE TAKEN CARE
 OF PRIOR TO ISSUING THE PERMIT.FAC 61G15-23.002 & FS
 471.023
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]