| 2007-04-16 18:23:21 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ***FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. PLEASE SUBMIT THE FOLLOWING: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THE FIRST THREE CUT SECTIONS |
| | DOWNSTREAM OF THE METER, AND TWO SECTIONS OF PIPE IN |
| | THE CEILING DO NOT SHOW THE LENGHTS OF PIPES. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ****NO RESPONSE, NOT ADDRSSED. PIPE SIZES SHALL BE |
| | SHOWN FOR ALL SECTIONS OF PIPE AND VALVES SHALL BE FULL |
| | SIZE FOR THE PIPE SIZE INDICATED TO THE GAS EQUIPMENT. |
| | |
| | 3. OK - NATURAL |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | ****RESPONSE NOTED, BUT THE TOTAL BTU'S ADDS UP TO |
| | 1,785,000, BUT IS SHOWN AS TOTAL OF 2,100,000 BTU'S. |
| | PLEASE CLARIFY. - PLEASE IDENTIFY ALL APPLIANCES ON THE |
| | ISOMETRIC. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. (CLOTHS DRYERS). |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, BUT THE UTILITY COMPANY DOES NOT |
| | DELEVER 1PSI. PLANS SHOW 7" TO 14" WC. AND 1PSI. PLEASE |
| | CHECK WITH GAS PROVIDER. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 10. N/A (NATURAL GAS) |
| | 11. N/A (NATURAL GAS) |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHT P502 RISER SHOWS VALVES IN THE CEILING. THESE |
| | VALVES ARE NOT REQUIRED, BUT IF THE VALVES ARE LEFT IN, |
| | A UNION IS REQUIRED FOR EACH VALVE, AND THE VALVE AND |
| | UNION ARE NOT APPROVED IN THE CEILING.--A NOTE |
| | INDICATES "SOLENOID VALVE TYPICAL" PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 2B. SHT P502 DETAIL 7 INDICATES "DESIGNED ACCORDING TO |
| | THE 2000 IFGC" & "DESIGNED ACCORDING TO THE 2003 IFGC". |
| | THE CODE ADOPTED AND IN EFFECT IS THE FBC-2004. PLEASE |
| | CHANGE CODE REFERENCES. SECTION 106.1.1. |
| | |
| | 3B. PER ELECTRICAL REVIEW COMMENT #47 SEE ATTACHED |
| | SHEET CONCERNING THE DESIGN PROFESSIONAL AND FS |
| | 533.80(2)(B). THIS IS GIVEN AS A NOTICE ONLY & ONE TIME |
| | ONLY. |
| | |
| | 4B. ALL MEP SHEETS. THE ENGINEERING COMPANY'S |
| | CERTIFICATE OF AUTHORIZATION NUMBER SHOWS DELINQUENT ON |
| | THE FLORIDA DBPR WEBSITE. SEE SHEET ATTACHED TO |
| | ELECTRICAL PLAN REVIEW NOTES. THIS SHALL BE TAKEN CARE |
| | OF PRIOR TO ISSUING THE PERMIT.FAC 61G15-23.002 & FS |
| | 471.023 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |