| Date |
Text |
| 2007-04-25 16:38:52 | *****DENIED***** |
| | |
| | NOTICE:THE INFORMATION ON THE SUBMITTED PLAN SHEETS |
| | ARE INCONSISTENT WHICH MAKE THE PLAN REVIEW PROCESS |
| | MORE TEDIOUS, TIME CONSUMING , AND CONFUSING FOR THE |
| | REVIEWERS.FOR EXAMPLE -THE FIRE PUMP ROOM MAY BE |
| | INDICATED AS FIRST FLOOR EAST END OF THE BUILDING ON A |
| | PLAN SHEET, BUT ON ANOTHER SHEET FOR THE SAME LOCATION |
| | AN ELECTRICAL ROOM IS OUTLINED.SEE COMMENTS #16 AND |
| | #18 FOR OTHER EXAMPLES OF THIS OCCURRING. |
| | |
| | 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE |
| | THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE |
| | COMPLY |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | TO THE APPROPIATE PLAN(S) |
| | |
| | 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | ADD TO THE APPROPIATE PLAN SHEET(S) |
| | |
| | 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR |
| | KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE |
| | PREVENTION BUREAU AT 561-804-4724.ACCESS(KNOX) BOXIS |
| | TO BE INSTALLED IN AN ACCESSIBLE LOCATION SHERE ACCESS |
| | TO OR WITHIN THE STRUCTURE MAY BE GAINED |
| | |
| | 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING |
| | METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS |
| | ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED, |
| | THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED |
| | BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY |
| | POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A |
| | CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK |
| | FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE |
| | SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON |
| | THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON |
| | THE BUILDING.PLEASE COMPLY |
| | |
| | 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT. |
| | ADD TO AN APPROPIATE PLAN SHEET |
| | |
| | 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| | ADD TO SHEET A-604 |
| | |
| | 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL |
| | NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING. |
| | THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING. |
| | ADD TO SHEET A-604 |
| | |
| | 10.HORIZONTAL-SLIDING DOORS THAT ARE PART OF THE |
| | REQUIRED MEANS OF EGRESS SHALL COMPLY WITH 7.2.1.4.1.4 |
| | OF NFPA 101.ADD TO SHEET A-604 |
| | |
| | 11.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND |
| | CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A |
| | OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C |
| | FOR OTHER SPACES.ADD TO SHEET A-606;BE SPECIFIC AS |
| | WHATTHESE AREAS WILL BE CLASSIFIED |
| | |
| | 12.PROVIDE PRESCRIPTIVE DETAIL STRENGHTS FOR ALL |
| | HANDRAILS AND GUARDRAILS. ADD TO SHEET A-701 |
| | |
| | 13.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE |
| | LOBBIES. ADD TO SHEET A-702 |
| | |
| | 14.AT LEAST ONE IDENTIFIBLE ELEVATOR SHALL BE |
| | AVAILABLE FOR USE BY THE FIRE DEPARTMENT IN CASE OF |
| | EMERGENCY. ADD TO SHEET A-702 |
| | |
| | 16.THERE IS NO INDICATION OF THE LOCATION FOR THE |
| | HEARING IMPAIRED ROOM ON THE FIFTH FLOOR (SHEET A-105) |
| | , BUT IS INDICATED AS ROOM 503 ON SHEET AR-105.SHOW |
| | CONSISTENCY OF PLAN SHEETS |
| | |
| | 17.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR |
| | ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION |
| | SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO |
| | THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST |
| | ROOM IN THE HOTEL.ADD TO SHEET A-411AND A-412 |
| | |
| | 18.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR |
| | LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101, |
| | E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON |
| | SHEETS E-203 AND E-204.SHOW CONSISTENCY OF PLAN |
| | SHEETS |
| | |
| | 19.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM |
| | INDEPENDENT OF THE ELECTRICAL SHEETS.PLEASE COMPLY; |
| | SEE ELECTRICAL PLAN NOTE #14 |
| | |
| | 20.THE FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE |
| | AND U.L. CETIFICATED FOR CENTRAL STATION SERVICE.ADD |
| | TO THE FIRE ALARM PLAN SHEET |
| | |
| | 21.ALL GUESTROOMS FOR HEARING IMPAIRED SHALL BE |
| | PROVIDED WITH FIRE ALARM VISUAL DEVICES. |
| | |
| | 22.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM AS PER WEST PALM BEACH FIRE PREVENTION.ADD |
| | TO THE FIRE ALARM PLAN SHEET |
| | |
| | 23.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER |
| | SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE |
| | LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE |
| | DOUBLE DETECTOR CHECK VALVE ASSEMBLY.PLEASE COMPLY; |
| | SEE ELECTRICAL NOTE #14 |
| | |
| | 24.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | IS REQUIRED FOR THE DOUBLE DETECTOR CHECK VALVE |
| | ASSEMBLY.ADD COMMENT TO CIVIL SHEET (8 OF 9) OR TO |
| | THE FIRE SPRINKLER PLAN SHEET |
| | |
| | 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE |
| | DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH |
| | FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS. |
| | ADD TO FIRE SPRINKLER PLAN SHEET |
| | |
| | 26.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND |
| | ASSOCIATED EQUIPMENT.PLEASE COMPLY |
| | |
| | 27.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR |
| | IDENTITY.ADD TO SHEET A-701 |
| | |
| | 28.FIRE EXTINGUISHERS ARE TO BE 2A:10 BC.ADDITIONAL |
| | EXTINGUISHERS MAY BE NEEDED IF THE TRAVEL DISTANCE TO |
| | THIS EQUIPMENT IS GREATER THAN 75 FEET FROM A ROOM IN |
| | THE BUILDING OR ON THE FLOOR OF THE BUILDING. |
| | |
| | 29.SEPARATE PLAN AND PERMITS WILL BEREQUIRED FOR |
| | ANY COOKING HOOD INSTALLATION ANDASSOCIATED FIRE |
| | SUPPRESSION SYSTEM PLANNED.PLEASE ACKNOWLEDGE |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |