Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-04-25 16:38:52*****DENIED*****
  
 NOTICE:THE INFORMATION ON THE SUBMITTED PLAN SHEETS
 ARE INCONSISTENT WHICH MAKE THE PLAN REVIEW PROCESS
 MORE TEDIOUS, TIME CONSUMING , AND CONFUSING FOR THE
 REVIEWERS.FOR EXAMPLE -THE FIRE PUMP ROOM MAY BE
 INDICATED AS FIRST FLOOR EAST END OF THE BUILDING ON A
 PLAN SHEET, BUT ON ANOTHER SHEET FOR THE SAME LOCATION
 AN ELECTRICAL ROOM IS OUTLINED.SEE COMMENTS #16 AND
 #18 FOR OTHER EXAMPLES OF THIS OCCURRING.
  
 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE
 THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE
 COMPLY
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO THE APPROPIATE PLAN(S)
  
 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
 ADD TO THE APPROPIATE PLAN SHEET(S)
  
 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR
 KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.ACCESS(KNOX) BOXIS
 TO BE INSTALLED IN AN ACCESSIBLE LOCATION SHERE ACCESS
 TO OR WITHIN THE STRUCTURE MAY BE GAINED
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED,
 THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED
 BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY
 POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A
 CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK
 FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS ( THE
 SAME DIMENSIONS AS PER WPB CODE) SHALL BE REQUIRED ON
 THE MONUMENT SIGN OR MARQUEE IN ADDITION TO THOSE ON
 THE BUILDING.PLEASE COMPLY
  
 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT.
 ADD TO AN APPROPIATE PLAN SHEET
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
 ADD TO SHEET A-604
  
 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
 THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
 ADD TO SHEET A-604
  
 10.HORIZONTAL-SLIDING DOORS THAT ARE PART OF THE
 REQUIRED MEANS OF EGRESS SHALL COMPLY WITH 7.2.1.4.1.4
 OF NFPA 101.ADD TO SHEET A-604
  
 11.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND
 CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A
 OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C
 FOR OTHER SPACES.ADD TO SHEET A-606;BE SPECIFIC AS
 WHATTHESE AREAS WILL BE CLASSIFIED
  
 12.PROVIDE PRESCRIPTIVE DETAIL STRENGHTS FOR ALL
 HANDRAILS AND GUARDRAILS. ADD TO SHEET A-701
  
 13.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE
 LOBBIES. ADD TO SHEET A-702
  
 14.AT LEAST ONE IDENTIFIBLE ELEVATOR SHALL BE
 AVAILABLE FOR USE BY THE FIRE DEPARTMENT IN CASE OF
 EMERGENCY. ADD TO SHEET A-702
  
 16.THERE IS NO INDICATION OF THE LOCATION FOR THE
 HEARING IMPAIRED ROOM ON THE FIFTH FLOOR (SHEET A-105)
 , BUT IS INDICATED AS ROOM 503 ON SHEET AR-105.SHOW
 CONSISTENCY OF PLAN SHEETS
  
 17.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION
 SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO
 THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST
 ROOM IN THE HOTEL.ADD TO SHEET A-411AND A-412
  
 18.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR
 LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101,
 E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON
 SHEETS E-203 AND E-204.SHOW CONSISTENCY OF PLAN
 SHEETS
  
 19.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM
 INDEPENDENT OF THE ELECTRICAL SHEETS.PLEASE COMPLY;
 SEE ELECTRICAL PLAN NOTE #14
  
 20.THE FIRE ALARM SYSTEM SHALL BE FULLY ADDRESSABLE
 AND U.L. CETIFICATED FOR CENTRAL STATION SERVICE.ADD
 TO THE FIRE ALARM PLAN SHEET
  
 21.ALL GUESTROOMS FOR HEARING IMPAIRED SHALL BE
 PROVIDED WITH FIRE ALARM VISUAL DEVICES.
  
 22.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER WEST PALM BEACH FIRE PREVENTION.ADD
 TO THE FIRE ALARM PLAN SHEET
  
 23.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE
 LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.PLEASE COMPLY;
 SEE ELECTRICAL NOTE #14
  
 24.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR THE DOUBLE DETECTOR CHECK VALVE
 ASSEMBLY.ADD COMMENT TO CIVIL SHEET (8 OF 9) OR TO
 THE FIRE SPRINKLER PLAN SHEET
  
 25.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
 ADD TO FIRE SPRINKLER PLAN SHEET
  
 26.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND
 ASSOCIATED EQUIPMENT.PLEASE COMPLY
  
 27.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR
 IDENTITY.ADD TO SHEET A-701
  
 28.FIRE EXTINGUISHERS ARE TO BE 2A:10 BC.ADDITIONAL
 EXTINGUISHERS MAY BE NEEDED IF THE TRAVEL DISTANCE TO
 THIS EQUIPMENT IS GREATER THAN 75 FEET FROM A ROOM IN
 THE BUILDING OR ON THE FLOOR OF THE BUILDING.
  
 29.SEPARATE PLAN AND PERMITS WILL BEREQUIRED FOR
 ANY COOKING HOOD INSTALLATION ANDASSOCIATED FIRE
 SUPPRESSION SYSTEM PLANNED.PLEASE ACKNOWLEDGE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722