| 2007-04-13 15:32:47 | PLEASE PROVIDE FOLLOWING INFO: |
| | |
| | 1. PLEASE SHOW ON DRAWINGS STANDARDS NOTES OF CITY OF |
| | WPB(WHICH YOU CAN GET IN A CD FROM 45TH STREET ENG) FOR |
| | SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, PARKING, HANDICAP |
| | PARKING, PAINTPER CITY CODES ETC.,, MUST MEET PER |
| | ADA,,ETC., |
| | 2. PLEASE SHOW ON DRAWINGS STANDARDS NOTES OF CITY OF |
| | WPB(WHICH YOU CAN GET FROM 45TH STREET ENG) FOR |
| | DUMPSTER & ITS ENCLOSURE PER CITY OF WPB, &LOCATION |
| | ON DWG, LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK. |
| | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , |
| | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA & FLORIDA |
| | BLDG CODE, PLEASE SHOW ON THE DRAWINGS. |
| | 4. PLEASE SHOW CALCULATION FOR EXFILTRATION TRENCH |
| | LENGTH. WHAT SAFETY FACTOR YOU USED IN LENGTH? |
| | 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA |
| | YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE |
| | OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN, |
| | LAKES, ETC,IMPERVIOUS AREA CAL., |
| | 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS |
| | PROJECT ? PLEASE SHOW TOTAL PERVIOUS, IMPERVIOUS AREA |
| | ON SEPARATE SHEET. |
| | 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR |
| | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES |
| | AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO |
| | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM |
| | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL |
| | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING |
| | ELEVATION, ETC PLEASE SHOW CALCULATIONS FOR |
| | EXFILTRATION TRENCH. |
| | 8.PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR |
| | SITE FOR STORM WATER DRAIN. |
| | 9. PLEASE GET UTILITY APPROVAL FROM MANNY G. 45TH |
| | STREET ENG DEPT. |
| | |
| | PLEASE RESPOND EACHITEM IN DETAIL TO EXPEDITE YOUR |
| | PERMITTING PROCESS |
| | |
| | RASIK CHOKSHI805-6723 |