| Date |
Text |
| 2007-04-06 16:04:21 | *** UNSAT2ND REVIEW *** |
| | |
| | SPRINGHILLSUITES |
| | 5-STORY 130 UNITS. |
| | |
| | ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | |
| | ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN |
| | ABBREVIATIONS FOR REQUIRED ITEMS. |
| | PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON * |
| | ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE |
| | ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES |
| | WILL BE DONE AS FS. |
| | * PLEASE SEE MANY REFERENCES TO THE FLORIDA |
| | ADMINISTRATIVE CODE WILL BE FAC. |
| | |
| | 1) NOTE: PLEASE KNOW THAT A WRITTEN RESPONSE FROM THE |
| | DESIGN TEAM WILL HELP IN THE REVIEW PROCESS.THE |
| | RESPONSES WHICH WERE ATTACHED TO THE SPRING HILL SUITES |
| | PLANS WERE THAT OF THE SAME RESPONSES WHICH WERE |
| | ATTACHED TO THE HOMEWOOD SUITES PLANS. THEY ARE IN FACT |
| | THE SAME RESPONSE WITH THE SAME PERMIT NUMBER. |
| | ** ALL ADDITIONAL INFORMATION BY WAY OF PRODUCT |
| | APPROVALS, DATA, REPORTS, RESPONSES ETC SHOULD NOT BE |
| | ATTACHED/STAPLED TO ROLLS OF PLANS. PLEASE PLACE IN |
| | FOLDERS/BINDERS OF SOME SORT AND LABEL ACCORDINGLY. |
| | |
| | 2) NOTE: PLEASE SEE FS 471.025, 481.025 AND FAC |
| | 61G15-23.002, 61G1-16.004 AS ALL PLANS SHALL BEAR THE |
| | ORIGINAL AND LEGAL SIGNATURE OF ALL DESIGNERS OF |
| | RECORD. PLEASE SEE THE ARCHITECTURAL SHEETS WHICH |
| | CONTAIN A RAISED SEAL OVER A *PRINTED* OR |
| | *PHOTO-COPIED* SIGNATURE. THIS SIGNATURE AND DATE IS |
| | NOT ORIGINAL AS REQUIRED. |
| | **PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS |
| | OFFICE. |
| | ** PLEASE SEE THE ELECTRICAL SHEETS SEEMED TO BE SIGNED |
| | WITH WHAT APPEARS TO BE *INITIALS*? IF THIS IS INDEED |
| | THE LEGAL SIGNATURE OF THE DESIGNER, PLEASE SUBMIT AN |
| | ORIGINAL SIGNED, DATED AND SEALED LETTER FROM THE |
| | ENGINEER ATTESTING TO THE LEGAL SIGNATURE. THIS WILL BE |
| | PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. ** |
| | PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE |
| | NOTARIZED. PLEASE SEE FS 117.05 FOR CORRECT NOTARY |
| | REQUIRED STATEMENTSETC. |
| | |
| | 3) NOTE: PLEASE SEE THE NEW LICENSE INFORMATIONKNOWN |
| | AS THE CERTIFICATE OF AUTHORIZATION NUMBER WHICH HAS |
| | NOW BEEN ADDED TO THE TITLE BLOCKS ON ALL ENGINEERING |
| | SHEETS IS CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. PLEASE SEE A |
| | PRINT OUT FROM THE STATE OF FLORIDA WEBSITE WHICH IS |
| | BEING ATTACHED TO THE NOTES WHICH WAS PRINTED ON 4/5/07 |
| | SHOWS THE LICENSE FOR FIRM AS BEING DELINQUENT SINCE |
| | 2/28/07. |
| | PLEASE SEE FAC 61G15-23.002 AND FS 471.023 WHICH |
| | REQUIRES THIS NUMBER TO BE CURRENT AND IN FULL EFFECT |
| | FOR SAID FIRM. |
| | PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF |
| | THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC |
| | 61G1-16.004, FS 481.219 |
| | PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS ARE NOT |
| | COMPLETE AT THIS TIME. PLEASE SEE THAT THIS IS REQUIRED |
| | FOR ALL SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID |
| | FIR, *PFVS* |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ARCHITECT. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE |
| | NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE:PLEASE SEE THE PREVIOUS NOTES AS FOR THE |
| | REQUIRED STATEMENT FOR ALL DESIGNERS. PLEASE SEE THAT |
| | SOME SHEETS CONTAIN THIS STATEMENT HOWEVER NOT ALL. |
| | PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH |
| | REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON ALL |
| | ARCH AND ENG SHEETS. |
| | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 OF THE FLORIDA STATUTES". |
| | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| | PLANS. |
| | |
| | 6) NOTE: PLEASE SEE THE *S* SHEETS WHICH DO NOT CONTAIN |
| | THE REQUIRED LICENSE INFORMATION FOR THE ENGINEERING |
| | FIRM AS REQUIRED PER FAC 61G15-23.002, FS 471.023. |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | |
| | 7) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT HAS NOT |
| | BEEN INCLUDE IN THE TITLE BLOCKS AS PREVIOUSLY |
| | REQUESTED. PLEASE SEE BY SIMPLY STATING THE CLOSEST |
| | MAIN INTERSECTION DOES NOT PROVIDE THE REQUIRED |
| | INFORMATION. |
| | PLEASE SEE THAT ONCE THE ADDRESS FOR SAID PROJECT IS |
| | FINALIZED; PLEASE BE SURE THE TITLE BLOCKS FOR ALL |
| | SHEETS CONTAIN THE CORRECT ADDRESS. THE ADDRESS GIVEN |
| | BY THE ADDRESSING REVIEWER ON THE PREVIOUS REVIEW IS |
| | THAT AS NOTED BELOW. |
| | PLEASE SEE A PRELIMINARY ADDRESS OF 2437 METROCENTRE |
| | BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL |
| | CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS |
| | ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING |
| | REVIEWER AND THE FIRE MARSHAL?S OFFICE. AT THIS TIME |
| | THE ADDRESSING REVIEW HAS ASSIGNED THE ABOVE 2437. FAC |
| | 61G1-16.004, FAC 61G15-23.002 |
| | * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES. |
| | |
| | 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND |
| | VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY |
| | READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003 |
| | PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF |
| | SHADOWING WITH LEAD/DUST RUB. |
| | PLEASE SEE SOME SHEETS ARE STILL LIKE THIS IN SETS, |
| | PLEASE SEE THE *A* SHEETS AS THESE WERE SEALED ON THE |
| | BACK OF EACH SHEET. THE SHEET FACING WITH INFORMATION, |
| | DESIGNS ETC SHALL BEAR THE SEAL FACING THE FRONT FOR |
| | READING, SCANNING ETC OF DOCUMENTS. |
| | |
| | 9) NOTE: PLEASE SEE SOME OF THE SP SHEETS ARE MISSING |
| | INFORMATION ON THE TITLE BLOCKS FOR THE PRINTED NAME |
| | AND LICENSE INFORMATION AS REQUIRED PER FAC 61G1-16.004 |
| | AND FS 481.219 |
| | |
| | 10) NOTE: PLEASE SEE THE SURVEY SHEETS WHICH DO NOT |
| | CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FAC |
| | 61G17-7.002, AND FS 472.025 |
| | |
| | 11) NOTE: PLEASE SEE THE PHOTO-METRICS PROVIDED ARE NOT |
| | CLEAR OR READABLE WITH MINIMUM LEVELS AS REQUIRED. |
| | PLEASE ALSO SEE THAT THE PLANS DO NOT CONTAIN ANY |
| | STAMPS FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT. ** |
| | PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A POOL, |
| | PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT WITH |
| | PLANS, FEES AND PERMIT APPLICATION. |
| | PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC |
| | SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF |
| | COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING. |
| | PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY |
| | ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE |
| | PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME. |
| | |
| | 12) NOTE: PLEASE SEE THAT MUCH OF THE INFORMATION |
| | NEEDED FOR REVIEW FOR CODE COMPLIANCE FOR CHAPTER 13 |
| | HAS NOT YET BEEN SUBMITTED. PLEASE SEE THE ENERGY |
| | CALCULATIONS PER FBC 2004 CHAPTER 13 THAT WERE |
| | SUBMITTED FOR REVIEW. 13-415.1.AB.1 DO NOT FULLY |
| | CORRELATE WITH THE FIXTURES, TYPES, NUMBERS, WATTAGES |
| | AS SHOWN ON PLANS AND FIXTURE LEGENDS. PLEASE BE SURE |
| | TO GO THROUGH PLANS AND ENERGY CALCULATIONS AND |
| | COORDINATE ALL INFORMATION. |
| | **PLEASE SEE THE 2004 FBC CHAPTER 13. |
| | **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE |
| | VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND |
| | BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE |
| | IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED. |
| | PLEASE SEE THIS VOLTAGE DROP INFORMATION COULD NOT BE |
| | LOCATED FOR THE FEEDERS. |
| | **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE |
| | SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER |
| | METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED. |
| | PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED, |
| | REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE |
| | DONE AT THIS TIME. |
| | A RESPONSE IN THE PLAN REVIEW NOTES FOR THE OTHER HOTEL |
| | CONTAIN A NOTE THAT THIS IS A 24/7/365 OPERATION AND |
| | DOES NOT NEED TO MEET ANY AUTOMATED LIGHTING CONTROLS. |
| | PLEASE SEE THERE ARE SOME AREAS IN WHICH CAN BE |
| | CONSIDERED 24HR OPERATION HOWEVER PLEASE SEE .1.3 (3) |
| | AS THE ROOMS MUST CONTAIN AUTOMATED SHUT OFF FOR ALL |
| | LIGHTING CIRCUITS IN THESE ROOMS INCLUDING ANY SWITCHED |
| | RECEPTACLES CIRCUITS. |
| | PLEASE SEE ALL OTHER LOCATIONS SUCH AS STORAGE ROOMS |
| | ETC WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS |
| | WILL BE REQUIRED TO CONTAIN AUTOMATED DEVICES. PLEASE |
| | KNOW THAT THIS WAS FEDERALLY MANDATED IN JULY 04 WHICH |
| | REQUIRED FOR ALL STATES BY THE NEXT CODE CYCLE TO ADOPT |
| | THE 1999 ASHAE 90.1 STANDARDS OR BETTER. THE STATE OF |
| | FLORIDA ADOPTED THE FBC ENERGY CODE ON OCT 1ST, 2005. |
| | THIS IS REQUIRED STATEWIDE. |
| | PLEASE KNOW THAT SOME OF THE LOCATIONS WHICH WOULD BE |
| | CONSIDERED FOR 24HR OPERATION MAY BE THE LOBBY, FRONT |
| | DESK, RECEPTION OFFICE LOCATIONS ALONG WITH HALLWAYS. |
| | ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE |
| | CALCULATIONS REQUIRED. |
| | ** PLEASE SEE TRACK LIGHTING REQUIREMENTS PER |
| | 13-415.2.ABC.1.2 |
| | ** PLEASE SEE NOTE #16 WITH RESPECT TO STAIRWELLS AND |
| | FAILURE OF DEVICES AS PER NFPA-101. |
| | ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE |
| | GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE |
| | SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES |
| | STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE. |
| | PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS |
| | MAXIMUM FOR TIMER TYPE DEVICES. |
| | PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR |
| | EXTERIOR BUILDING LIGHTING ALLOWANCES. |
| | |
| | ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS |
| | REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE |
| | SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO |
| | COMPLY. |
| | |
| | 13) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL |
| | SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS |
| | 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE |
| | REQUIRED TO BE STATED ON PLANS AND STRUCTURAL |
| | CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE |
| | PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED |
| | BASED ON THE FIXTURES AS NOTED ON PLANS. |
| | NO RESPONSE WAS SUBMITTED FOR THIS. PLEASE SEE THE |
| | INFORMATION ON PLANS MENTIONS THE MINIMUM RATING AND |
| | MENTIONS INFORMATION TO THE ELECTRICAL INSPECTOR. |
| | PLEASE KNOW THAT THIS INFORMATION IS AND WILL BE |
| | REQUIRED BE DONE ON PLANS AND SUBMITTED FOR REVIEW |
| | BEFORE ANY INSTALLATION. PLEASE KNOW THAT IF THE WIND |
| | LOAD CALCULATIONS AND INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME, THIS WILL BE PART OF THE CONDITIONS OF |
| | ISSUANCE WHICH MAY BE DONE.. |
| | |
| | 14) NOTE: PLEASE SEE THE ONLY SOME INFORMATION WAS |
| | SHOWN FOR THE FIRE ALARM INFORMATION AND NO FIRE |
| | SPRINKLER INFORMATION WAS SUBMITTED.PLEASE SEE THE |
| | BASE PLANS FOR THIS BUILDING SHALL CONTAIN THE COMPLETE |
| | FIRE SPRINKLER LAYOUT AND BASE FIRE ALARM SYSTEM PLEASE |
| | KNOW THAT BOTH OF THESE WILL STILL BE SUBMITTED FOR |
| | SEPARATE PERMITS PLANS AND FEES AT A LATER DATE ONCE |
| | THE BUILDING PERMIT IS ISSUED. BASE SYSTEM FOR FIRE |
| | ALARM IS SHOWN; HOWEVER PLEASE SEE COMMENTS WITH |
| | RESPECT TO PLANS SUBMITTED FOR THIS AND DEVICES MISSING |
| | ETC. |
| | PLEASE KNOW THAT EVEN THOUGH THESE WILL BE UNDER |
| | SEPARATE PERMIT, THE MINIMUM REQUIREMENTS FOR THE CODE |
| | SHALL BE SHOWN ON PLANS. |
| | FBC ADMIN SECTION 106.3.5.1.1 (5). |
| | |
| | 15) NOTE: PLANS DID NOT CHANGE. COMPLIANCE FOR ADA |
| | DEVICES, LOCATIONS, LEVELS ETC HAVE NOT BEEN MET. |
| | PLEASE SEE PLANS STILL INDICATE BEING DONE UNDER THE |
| | CANADIAN NATIONAL BUILDING CODE. |
| | PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL |
| | MINIMUM LEVELS AS REQUIRED FOR ALL AREAS. PLEASE KNOW |
| | IS NOTED THAT THE LEVELS FOR ACCESSIBLE UNITS ARE NOTED |
| | ON PLANS, HOWEVER THIS IS REQUIRED FOR ALL OTHER AREAS |
| | AS STATED IN 11-4.28.1 |
| | PLEASE SEE PLANS CURRENTLY STATE THE 1995 CANADA |
| | NATIONAL BUILDING CODE. PLEASE SEE THAT THESE PLANS ARE |
| | BEING SUBMITTED IN THE STATE OF FLORIDA IN THE US. |
| | PLEASE ADJUST PLANS AND ALL CODE REFERENCES. PLEASE BE |
| | SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN DEVICES |
| | FROM THE FBC AND PLEASE ALSO SEE NFPA-72. PLEASE KNOW |
| | THAT THE FBC CHAPTER 11 REQUIREMENTS ARE MORE STRINGENT |
| | AND THE MORE STRINGENT SHALL APPLY. |
| | THIS IS THE SAME COMMENT AS NO CHANGES HAVE BEEN MADE. |
| | |
| | |
| | 16) NOTE: THIS COMMENT WILL REMAIN AS THE LOCATIONS OF |
| | ALL DEVICES WHICH MAY BE STATED BY THE FIRE REVIEW MAY |
| | ALSO AFFECT THE ELECTRICAL PLANS. |
| | *PREVIOUS REVIEW NOTE * PLEASE SEE FIRE REVIEW COMMENTS |
| | AS THERE SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS |
| | ARE MISSING AND WILL BE REQUIRED. |
| | PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS |
| | ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH |
| | DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL |
| | REQUIRE THESE.(PUMP ROOM, ELEVATOR MACHINE ROOM ) ETC |
| | PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905 |
| | |
| | 17) NOTE:PLEASE BE SURE THESE CODES AS PREVIOUSLY |
| | NOTED ARE ON THE ARCHITECTURAL PLANS TITLE SHEETS FOR |
| | CODES AND THE ELECTRICAL PLANS AT A MINIMUM. PLEASE SEE |
| | SOME OF THE CODES REFLECTED ON PLANS ARE NO LONGER IN |
| | USE IN THE STATE OF FLORIDA. PLEASE SEE THE FOLLOWING |
| | CODES SHALL BE LISTED ON ALL PLANS AND ANY CODES |
| | RELEVANT TO THE SPECIFIC TRADES SHEETS SHALL BE STATED |
| | ON THOSE SHEETS. (ELECTRICAL) PLEASE LIST THE FOLLOWING |
| | AT A MINIMUM AS REQUIRED FOR ELECTRICAL REVIEW. 2002 |
| | NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD ALSO |
| | BE STATED ON E-TITLE SHEET. |
| | 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20 |
| | NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY |
| | CODE. |
| | |
| | 18) NOTE:PLEASE SEE THAT SOME OF THE PHOTO-METRICS |
| | SUBMITTED DO NOT COMPLY WITH THE MINIMUM LEVELS |
| | REQUIRED FOR LIFE SAFETY. PLEASE SEE THE LEVELS AS |
| | STATED IN PREVIOUS REVIEW. (SEE STAIRS WHICH SHOW ONLY |
| | 2.9FC WHEN A MINIMUM OF 10FC IS REQUIRED.). |
| | PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL EGRESS |
| | PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER EMERGENCY |
| | LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY OUT AND AWAY |
| | FROM BUILDING. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL |
| | INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE |
| | ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO |
| | 1FT CANDLE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 19) NOTE: PLEASE SEE THIS COMMENT WILL REMAIN AS THE |
| | DISCONNECTING MEANS FOR EQUIPMENT AND LOCATIONS IN THE |
| | ELEVATOR EQUIPMENT ROOM NEEDS TO BE MORE DETAILED. |
| | PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR ALL THE |
| | REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR |
| | EQUIPMENT ROOMS. PLEASE 620.23 AND .24 WHICH MORE |
| | SPECIFICALLY SHOWS THE LIGHTING AND RECEPTACLES ALSO |
| | BEING SHOWN CIRCUITED TO OTHER AREAS AND ROOMS WHICH |
| | ARE NOT PERMITTED. |
| | PLEASE ALSO SEE 620.51 FOR REQUIRED DISCONNECTING MEANS |
| | FOR ALL AS NOTED AND LOCATIONS REQUIRED. |
| | |
| | 20) NOTE:SEE NOTE ABOVE, LABEL EQUIPMENT, |
| | DISCONNECTS, CIRCUITING. |
| | PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE ELEVATOR |
| | EQUIPMENT A NOT COMPLETE ON PLANS AT THIS TIME. PLEASE |
| | SEE KNOW THAT REVIEW OF THIS CAN NOT BE DONE AT THIS |
| | TIME. PLEASE SEE THE FOLLOWING COMMENT. |
| | FBC 106.1.2, NEC 408.4, 310.16 ETC |
| | |
| | 21) NOTE:SAME AS PREVIOUSLY NOTED. |
| | PLEASE LIST THE CIRCUITING ON THE MDP WITH THE |
| | RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL |
| | SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS |
| | SUBMITTED. |
| | 1,3,5,7,9 / 2,4,6,8, ETC. |
| | PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE |
| | ITEMS SHALL CORRELATE. |
| | FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC |
| | |
| | |
| | 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS |
| | SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT |
| | SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS. |
| | PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT |
| | AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION |
| | WAS SUBMITTED FOR REVIEW. |
| | PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10. |
| | PLEASE ALSO SEE NEC 695.4 |
| | ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND |
| | NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST. |
| | DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR, |
| | ETC. |
| | PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING |
| | FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1. |
| | NEC 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | |
| | 23) NOTE:SAME NOTE TO REMAIN AS THE SYMBOLS ON PLANS |
| | WILL CHANGE AND SOME ARE NOT CLEAR AT THIS TIME. SEE |
| | PLANS. |
| | PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD NOT BE |
| | LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE COMPLETE |
| | FOR REVIEW OF THESE ITEMS. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 24) NOTE:SAME NOTE TO REMAIN AS SYMBOL AND LEGEND |
| | WILL CHANGE. |
| | PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY OF THE |
| | REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN KEYNOTES |
| | WILL MOST LIKELY BE ADJUSTED. |
| | PLEASE BE SURE TO CORRELATE. |
| | |
| | 25) NOTE: PLEASE CORRELATE ARCHITECTURAL PLANS WITH |
| | THAT OF THE ELECTRICAL PLANS FOR ALL ROOM LAYOUTS AND |
| | FOOT PRINTS OF ROOMS/BUILDING. PLEASE SEE THE MAIN |
| | ELECTRICAL ROOM FOR ONE EXAMPLE. PLEASE SEE THE FLOOR |
| | LAYOUTS DO NOT CORRELATE AND REVIEW FOR SOME ITEMS FOR |
| | CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE |
| | SEE THE ELECTRICAL PLANS DO NOT SHOW ANY ELECTRICAL |
| | ROOMS FOR THE TYPICAL LAYOUTS AND THE ELECTRICAL |
| | PANELS. PLEASE SEE NO DOORS ARE BEING SHOWN TO ACCESS |
| | ANY PANELS? PLEASE SEE ARCHITECTURAL SHEETS AND |
| | CORRELATE. |
| | PLEASE SEE 240.24, 110.26 ETC |
| | ** PLEASE SEE THE ELECTRICAL ROOM WHICH ALSO CONTAINS |
| | BATHROOM FIXTURES ON PLANS. |
| | ** PLEASE SEE THE DOOR SWING IN THE MAIN ELECTRICAL |
| | ROOM SHALL FACE OUTWARD, ALONG WITH PANIC HARDWARE |
| | ETC. |
| | PLEASE ADJUST PLANS AND BEAR IN MIND THE REQUIREMENTS |
| | FOR THE DOOR SWINGS IN THE EGRESS CORRIDOR FOR BUILDING |
| | CODE. |
| | PLEASE SEE THE PLANS SHALL ALSO CONTAIN A NOTE FOR DOOR |
| | HARDWARE. |
| | |
| | |
| | |
| | 26) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. |
| | PLEASE SEE 210.60 WHICH REFERENCES TO 210.52 FOR ITEMS |
| | REQUIRED. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. PLEASE |
| | KNOW AT THIS TIME IT SEEMS THESE MICROWAVE UNITS ARE |
| | BEING PERMANENTLY INSTALLED AT AN UPPER LEVEL. PLEASE |
| | SEE SOME OF THE FOLLOWING COMMENTS WHICH MAY VERY WELL |
| | APPLY. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT TO THE HEIGHT OF |
| | THE MICROWAVE IN ACCESSIBLE UNITS. |
| | |
| | 27) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. |
| | PLEASE SEE MISSING THE SMALL APPLIANCE CIRCUITS AS |
| | REQUIRED PER 210.52B1, 210.11C1 AND 220.16. PLEASE KNOW |
| | THAT NO OTHER OUTLETS MAY BE FED FROM THESE CIRCUITS. |
| | (IF APPLICABLE) |
| | |
| | 28) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. |
| | PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES LOCATED IN |
| | THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE FED FROM |
| | THE LIGHTING CIRCUITS WHICH ARE NOT PERMITTED. PLEASE |
| | SEE 210.11C1, 220.16 AS NOTED IN NOTE #31 |
| | (WHERE APPLICABLE AS NOTE IN NOTE #30) |
| | |
| | 29) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. PLEASE ALSO |
| | SEE THERE ARE SOME WALL AREAS WHICH ARE MISSING |
| | RECEPTACLES AS NOTED. |
| | |
| | PLEASE SEE MISSING RECEPTSPER 210.52 FOR 2FT OF WALL |
| | , KITCHEN AREA, KITCHEN WALL OVER 2FT, WITHIN 6FT OF |
| | DOORS ETC. |
| | PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR |
| | HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE |
| | LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF |
| | RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE |
| | INSTALLED. |
| | PLEASE SEE MOST UNITS SEEM TO BE OK, HOWEVER THERE ARE |
| | SOME UNITS WHICH DO NOT HAVE ANY RECEPTS LOCATE DON |
| | WALLS. PLEASE KNOW IF THIS IS NOT A UNIT WITH PERMANENT |
| | COOKING WHICH IS NOT YET DETERMINED THEN, SPACING MAY |
| | FALL UNDER GUEST ROOMS/SUITES AND NOT DWELLING. 210.60 |
| | |
| | 30) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. |
| | HEIGHTS, AND USE IS NOT CLEAR AT THIS TIME. |
| | PLEASE SEE THE HEIGHTS FOR THE MICROWAVES IN ACCESSIBLE |
| | UNITS ARE AT 62INCHES, WHERE ARE THESE UNITS GOING TO |
| | BE MOUNTED? AND SHOW DETAIL. |
| | FBC CHAPTER 11, FHAR 24CFR100.205 |
| | |
| | 31) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND |
| | PERMANENT MEANS OF COOKING IS NOT CLEAR. |
| | PLEASE KNOW THAT IN EITHER CASE WHETHER OR NOT THE |
| | FACILITY CONTAINS PERMANENT MEANS FOR COOKING THE |
| | RECEPTACLES SERVING KITCHEN COUNTER SPACE SHALL BE |
| | GFI/GFI PROTECTED. |
| | PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING KITCHEN |
| | COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI |
| | PROTECTED. |
| | |
| | |
| | 32) NOTE:PLEASE SEE THE 2002 NEC AS ARC FAULT |
| | PROTECTION IS NO LONGER ONLY FOR RECEPTACLES IN |
| | SLEEPING ROOMS. PLEASE SEE THE NOTES ON PLANS WHICH |
| | MENTION AFCI PROTECTION ONLY FOR RECEPTACLES. |
| | * PREVIOUS NOTE. |
| | PLEASE CLARIFY THE ARC FAULT PROTECTION WHICH IS NOT |
| | CURRENTLY BEING SHOWN. PLEASE SEE NOTE #30 AND IF UNITS |
| | CONTAIN PERMANENT COOKING MOUNTED EQUIPMENT THEN THESE |
| | WILL BE REQUIRED FOR PROTECTION IN SLEEPING ROOMS. |
| | 210.12 |
| | |
| | 33) NOTE:SAME NOTE. |
| | PLEASE EITHER PROVIDE SCHEDULE FOR OCP AND AWG RATINGS, |
| | OR COMPLETE PANEL SCHEDULES AS PREVIOUSLY NOTED. PLEASE |
| | COMPLETE ALL PANEL BOARDS WITH THE CONDUCTOR SIZES FOR |
| | ALL BRANCH CIRCUITS. |
| | PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2 |
| | REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME. |
| | |
| | 34) NOTE: PLEASE SEE MISSING SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50 |
| | |
| | 35) NOTE: PLEASE SEE LOADS FOR CONTINUOUS LOADS IN |
| | PANEL "P" NEED TO BE SHOWN.. |
| | PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC. |
| | PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY |
| | NOTED FOR CONTINUOUS LOADS. |
| | 220, 215.3, 230.42. |
| | FBC 106.1.2 |
| | |
| | 36) NOTE: THIS NOTE WILL REMAIN AND THERE WILL BE |
| | CHANGES ON PLANS. |
| | * PREVIOUS NOTE * PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS AND SUMMARY FOR ALL LOADS AND SHOW ALL |
| | CONTINUOUS/LARGEST MOTOR LOADS AT 125%. |
| | 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC. |
| | |
| | 37) NOTE: PLEASE ALSO CORRELATE ALL PLANS AND SHEETS AS |
| | THE PANEL P IS BEING SHOWN IN MULTIPLE LOCATIONS. ONE |
| | SHEET PANEL IS SHOWN IN ONE ROOM AND ANOTHER SHEET |
| | SHOWS THIS SAME PANEL LOCATED AT ANOTHER ROOM. PLEASE |
| | CORRELATE. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION/CLARIFICATION. |
| | |
| | 38) NOTE:PLEASE SEE ROOF TOP PLANS WHICH INDICATE A |
| | RTU HOWEVER NO CIRCUITING IS BEING SHOWN ETC. PLEASE |
| | SEE 440.11 AND 210.63 FOR OTHER REQUIRED DISCONNECTS |
| | AND WP GFI REQUIRED. |
| | THIS WAS NOTED ON PREVIOUS PLANS AND SOME INFORMATION |
| | ON THE MDP WAS PROVIDED HOWEVER DISCONNECTING MEANS AND |
| | GFI CAN NOT BE DETERMINED AT THIS TIME. PLEASE SEE THE |
| | NOTES ON PLANS MENTION THE EQUIPMENT CONTAINS INTERNAL |
| | DISCONNECTING MEANS YET THIS CAN NOT BE VERIFIED. |
| | PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS WHICH SHOWS |
| | THIS AS REQUIRED PER 440.11. |
| | PLEASE SEE THE NOTE ALSO MENTIONS THE GFI REQUIRED WILL |
| | BE FED FROM THE RTU. HOW IS THIS POSSIBLE WHEN THE |
| | CIRCUITING DOES NOT INDICATE ANY NEUTRAL CONDUCTOR |
| | BEING FED FROM THE MDP TO UNIT. THE LOAD FOR THE GFI |
| | CAN NOT BE FED FROM THE UNIT. |
| | THE FOLLOWING SCENARIO IS AN EXAMPLE, THE UNIT NEEDS TO |
| | BE SERVICED AND THE POWER TO THE UNIT IS SHUT DOWN, HOW |
| | WILL A RECEPTACLE WHICH IS FED FROM THIS UNIT STILL |
| | CONTAIN POWER FOR SERVICING OR ANY OTHER NEEDS WHEN |
| | THERE IS NO POWER? |
| | PLEASE ALSO EXPLAIN WHO THE NEUTRAL IS BEING DERIVED? |
| | THERE ARE SEVERAL UNANSWERED QUESTIONS AT THIS TIME. |
| | PLEAS COORDINATE AND ADJUST PLANS. |
| | |
| | 39) NOTE: PLEASE EXPLAIN WHERE NOTES AND INFORMATION |
| | FOR THE BELOW AS PREVIOUSLY NOTED IS MET. |
| | PLEASE SEE NFPA-72 FOR REQUIREMENTS OF THE FACP |
| | CIRCUIT(S). |
| | 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND |
| | CONNECTIONS SHALL BE MECHANICALLY PROTECTED. |
| | 4.4.1.4.2.2 CIRCUIT DISCONNECTING MEANS SHALL HAVE A |
| | RED MARKING SHALL BE ACCESSIBLE ONLY TO AUTHORIZED |
| | PERSONNEL, AND SHALL BE IDENTIFIED AS ?FIRE ALARM |
| | CIRCUIT.? |
| | 4.4.1.4.2.3 THE LOCATION OF THE CIRCUIT DISCONNECTING |
| | MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM |
| | CONTROL UNIT |
| | PLEASE KNOW ANY NOTATION FOR THE REQUIRED LOCK OFF TYPE |
| | BREAKER SHALL STATE "ANY LOCK-OFF DEVICE SHALL HAVE THE |
| | HANDLE/LOCK AN INTEGRAL PART OF THE BREAKER" OR WORDS |
| | TO THAT AFFECT. PLEASE KNOW DEVICES SUCH AS THE |
| | SNAP/CLIP ON TYPE ARE NOT PERMITTED AS THEY ARE EASILY |
| | REMOVED OR FALL OFF WHEN A PANEL COVER IS REMOVED WHICH |
| | THEN NO LONGER PROVIDES THE NEEDED PROTECTION OF THE |
| | CIRCUITS(S). |
| | |
| | |
| | 40) NOTE:PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE |
| | FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE |
| | 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS |
| | REQUIRED. |
| | PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING |
| | CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | THIS WOULD CREATE OBJECTIONABLE CURRENTS. |
| | THIS IS THE SAME COMMENT AS THE RISER SHOWS TWO |
| | DIFFERENT SETS OF SERVICE ENTRANCE CONDUCTORS?? |
| | |
| | 41) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD |
| | ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1, |
| | 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL |
| | OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY |
| | FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE |
| | ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS. |
| | |
| | 42) NOTE: THIS NOTE REMAINS AS ALL LOCATIONS HAVE NOT |
| | YET BEEN CONFIRMED AND LOCATIONS ON CEILINGS NEED TO BE |
| | VERIFIED. |
| | * PREVIOUS REVIEW NOTE* |
| | PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES LOCATIONS OF |
| | SMOKE DETECTORS TO BE INSTALLED WITH MINIMUM CRITERIA. |
| | PLEASE SEE AREAS WHERE THERE ARE SLOPED CEILINGS AS |
| | SHOWN ON THE ARCHITECTURAL SHEETS, THE SD SHALL BE |
| | INSTALLED WITHIN 3FT OF THE PEAK OF THAT SLOPE. |
| | (LOUNGE) ETC OR WITHIN 12 INCHES OF THE HIGHEST POINT |
| | ON A FLAT CEILING. PLEASE NOTE THE REQUIREMENTS AS |
| | LISTED. (3FT FROM BATH ROOM AND KITCHEN DOORS/OPENINGS |
| | ETC. PLANS DO ALREADY CONTAIN A NOTE FOR THE SMOKE |
| | DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS. THIS COMMENT |
| | MAYBE EXPANDED UPON. |
| | PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION |
| | MISSING WHICH WILL REQUIRE ADDITIONAL. |
| | |
| | 43) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS. THIS IS REQUIRED FOR ALL ENLARGED LAYOUT |
| | SHEETS AS WELL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 44) NOTE: PLEASE SHOW AND COMPLETE LOAD CALCULATIONS |
| | FOR TRACK LIGHTING PER 220.12B |
| | |
| | 45) NOTE: NOTE FROM PREVIOUS REVIEW TO REMAIN AS NOTES |
| | ABOVE MENTION THIS. PLEASE KNOW DOORS SHALL BE SHOWN |
| | FOR ALL ROOMS, MORE SPECIFICALLY THE MAIN ELECTRICAL |
| | ROOM(S), ELEVATOR ROOMS ETC. PLEASE KNOW THE LAYOUTS |
| | FROM THE ARCHITECTURAL SHEETS AND THE ELECTRICAL SHEETS |
| | DO NOT CORRELATE, THE DOOR SWINGS MAY BE AN ISSUE IF |
| | THE DOORS ARE ACTUALLY ON THE INSIDE AND LOCATED IN AN |
| | EGRESS CORRIDOR. PLEASE SEE FBC AND LS101 FOR DOOR |
| | SWINGS IN EGRESS PATHS.7.2.1.4 ETC |
| | |
| | 46) NOTE:SAME NOTE, SEE KITCHEN AREAS AND THE LIKE. |
| | PLEASE SEE 210.8B3 FOR BRANCH CIRCUITS IN KITCHEN AREAS |
| | AND THE LIKE WHICH REQUIRES PROTECTION FOR ALL 15/20 |
| | AMP 120 CIRCUITS. |
| | |
| | 47) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES |
| | 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | ** ONE COMPLETE SET OF PLANS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | 48) NOTE: PLEASE SEE THE LOADS ON THE MDP'S AS NOTED ON |
| | PLANS DO NOT CORRELATE. PLEASE SEE ONE MDP SHOWS ONE |
| | LOAD AND THE LOAD SHOWN FOR TEH SAME MDP IN OTHER |
| | LOCATIONS IS YET ANOTHER LOAD? |
| | PLEASE CORRDINATE ONCE ALL LOADS ARE DONE. |
| | FBC 106.1.3.5.1.2, 106.1.2 |
| | NEC 220 |
| | |
| | 49) NOTE:PLEASE PROVIDE THE UL DETAILS FOR ANY AND |
| | ALL FIRE RATED PENETRATIONS. |
| | NEC 300.21, NFPA-221, 4.2 ETC. |
| | PLEASE PROVIDE DETAIL SHEET. |
| | |
| | |
| | |
| | *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED |
| | FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC, |
| | THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP |
| | REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-06 11:23:50 | 1-ROLL IN ELEC FOR REVIEW. |
| | NOTES TO FOLLOW |