Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-06 16:04:21*** UNSAT2ND REVIEW ***
  
 SPRINGHILLSUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE: PLEASE KNOW THAT A WRITTEN RESPONSE FROM THE
 DESIGN TEAM WILL HELP IN THE REVIEW PROCESS.THE
 RESPONSES WHICH WERE ATTACHED TO THE SPRING HILL SUITES
 PLANS WERE THAT OF THE SAME RESPONSES WHICH WERE
 ATTACHED TO THE HOMEWOOD SUITES PLANS. THEY ARE IN FACT
 THE SAME RESPONSE WITH THE SAME PERMIT NUMBER.
 ** ALL ADDITIONAL INFORMATION BY WAY OF PRODUCT
 APPROVALS, DATA, REPORTS, RESPONSES ETC SHOULD NOT BE
 ATTACHED/STAPLED TO ROLLS OF PLANS. PLEASE PLACE IN
 FOLDERS/BINDERS OF SOME SORT AND LABEL ACCORDINGLY.
  
 2) NOTE: PLEASE SEE FS 471.025, 481.025 AND FAC
 61G15-23.002, 61G1-16.004 AS ALL PLANS SHALL BEAR THE
 ORIGINAL AND LEGAL SIGNATURE OF ALL DESIGNERS OF
 RECORD. PLEASE SEE THE ARCHITECTURAL SHEETS WHICH
 CONTAIN A RAISED SEAL OVER A *PRINTED* OR
 *PHOTO-COPIED* SIGNATURE. THIS SIGNATURE AND DATE IS
 NOT ORIGINAL AS REQUIRED.
 **PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS
 OFFICE.
 ** PLEASE SEE THE ELECTRICAL SHEETS SEEMED TO BE SIGNED
 WITH WHAT APPEARS TO BE *INITIALS*? IF THIS IS INDEED
 THE LEGAL SIGNATURE OF THE DESIGNER, PLEASE SUBMIT AN
 ORIGINAL SIGNED, DATED AND SEALED LETTER FROM THE
 ENGINEER ATTESTING TO THE LEGAL SIGNATURE. THIS WILL BE
 PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. **
 PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE
 NOTARIZED. PLEASE SEE FS 117.05 FOR CORRECT NOTARY
 REQUIRED STATEMENTSETC.
  
 3) NOTE: PLEASE SEE THE NEW LICENSE INFORMATIONKNOWN
 AS THE CERTIFICATE OF AUTHORIZATION NUMBER WHICH HAS
 NOW BEEN ADDED TO THE TITLE BLOCKS ON ALL ENGINEERING
 SHEETS IS CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION. PLEASE SEE A
 PRINT OUT FROM THE STATE OF FLORIDA WEBSITE WHICH IS
 BEING ATTACHED TO THE NOTES WHICH WAS PRINTED ON 4/5/07
 SHOWS THE LICENSE FOR FIRM AS BEING DELINQUENT SINCE
 2/28/07.
 PLEASE SEE FAC 61G15-23.002 AND FS 471.023 WHICH
 REQUIRES THIS NUMBER TO BE CURRENT AND IN FULL EFFECT
 FOR SAID FIRM.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE THE ARCHITECTURAL FIRM TITLE BLOCKS ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE THAT THIS IS REQUIRED
 FOR ALL SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID
 FIR, *PFVS*
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE:PLEASE SEE THE PREVIOUS NOTES AS FOR THE
 REQUIRED STATEMENT FOR ALL DESIGNERS. PLEASE SEE THAT
 SOME SHEETS CONTAIN THIS STATEMENT HOWEVER NOT ALL.
 PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH
 REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON ALL
 ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE SEE THE *S* SHEETS WHICH DO NOT CONTAIN
 THE REQUIRED LICENSE INFORMATION FOR THE ENGINEERING
 FIRM AS REQUIRED PER FAC 61G15-23.002, FS 471.023.
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 7) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT HAS NOT
 BEEN INCLUDE IN THE TITLE BLOCKS AS PREVIOUSLY
 REQUESTED. PLEASE SEE BY SIMPLY STATING THE CLOSEST
 MAIN INTERSECTION DOES NOT PROVIDE THE REQUIRED
 INFORMATION.
 PLEASE SEE THAT ONCE THE ADDRESS FOR SAID PROJECT IS
 FINALIZED; PLEASE BE SURE THE TITLE BLOCKS FOR ALL
 SHEETS CONTAIN THE CORRECT ADDRESS. THE ADDRESS GIVEN
 BY THE ADDRESSING REVIEWER ON THE PREVIOUS REVIEW IS
 THAT AS NOTED BELOW.
 PLEASE SEE A PRELIMINARY ADDRESS OF 2437 METROCENTRE
 BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL
 CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS
 ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING
 REVIEWER AND THE FIRE MARSHAL?S OFFICE. AT THIS TIME
 THE ADDRESSING REVIEW HAS ASSIGNED THE ABOVE 2437. FAC
 61G1-16.004, FAC 61G15-23.002
 * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES.
  
 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY
 READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
 PLEASE SEE SOME SHEETS ARE STILL LIKE THIS IN SETS,
 PLEASE SEE THE *A* SHEETS AS THESE WERE SEALED ON THE
 BACK OF EACH SHEET. THE SHEET FACING WITH INFORMATION,
 DESIGNS ETC SHALL BEAR THE SEAL FACING THE FRONT FOR
 READING, SCANNING ETC OF DOCUMENTS.
  
 9) NOTE: PLEASE SEE SOME OF THE SP SHEETS ARE MISSING
 INFORMATION ON THE TITLE BLOCKS FOR THE PRINTED NAME
 AND LICENSE INFORMATION AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219
  
 10) NOTE: PLEASE SEE THE SURVEY SHEETS WHICH DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FAC
 61G17-7.002, AND FS 472.025
  
 11) NOTE: PLEASE SEE THE PHOTO-METRICS PROVIDED ARE NOT
 CLEAR OR READABLE WITH MINIMUM LEVELS AS REQUIRED.
 PLEASE ALSO SEE THAT THE PLANS DO NOT CONTAIN ANY
 STAMPS FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT. **
 PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A POOL,
 PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT WITH
 PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 12) NOTE: PLEASE SEE THAT MUCH OF THE INFORMATION
 NEEDED FOR REVIEW FOR CODE COMPLIANCE FOR CHAPTER 13
 HAS NOT YET BEEN SUBMITTED. PLEASE SEE THE ENERGY
 CALCULATIONS PER FBC 2004 CHAPTER 13 THAT WERE
 SUBMITTED FOR REVIEW. 13-415.1.AB.1 DO NOT FULLY
 CORRELATE WITH THE FIXTURES, TYPES, NUMBERS, WATTAGES
 AS SHOWN ON PLANS AND FIXTURE LEGENDS. PLEASE BE SURE
 TO GO THROUGH PLANS AND ENERGY CALCULATIONS AND
 COORDINATE ALL INFORMATION.
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 PLEASE SEE THIS VOLTAGE DROP INFORMATION COULD NOT BE
 LOCATED FOR THE FEEDERS.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 A RESPONSE IN THE PLAN REVIEW NOTES FOR THE OTHER HOTEL
 CONTAIN A NOTE THAT THIS IS A 24/7/365 OPERATION AND
 DOES NOT NEED TO MEET ANY AUTOMATED LIGHTING CONTROLS.
 PLEASE SEE THERE ARE SOME AREAS IN WHICH CAN BE
 CONSIDERED 24HR OPERATION HOWEVER PLEASE SEE .1.3 (3)
 AS THE ROOMS MUST CONTAIN AUTOMATED SHUT OFF FOR ALL
 LIGHTING CIRCUITS IN THESE ROOMS INCLUDING ANY SWITCHED
 RECEPTACLES CIRCUITS.
 PLEASE SEE ALL OTHER LOCATIONS SUCH AS STORAGE ROOMS
 ETC WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS
 WILL BE REQUIRED TO CONTAIN AUTOMATED DEVICES. PLEASE
 KNOW THAT THIS WAS FEDERALLY MANDATED IN JULY 04 WHICH
 REQUIRED FOR ALL STATES BY THE NEXT CODE CYCLE TO ADOPT
 THE 1999 ASHAE 90.1 STANDARDS OR BETTER. THE STATE OF
 FLORIDA ADOPTED THE FBC ENERGY CODE ON OCT 1ST, 2005.
 THIS IS REQUIRED STATEWIDE.
 PLEASE KNOW THAT SOME OF THE LOCATIONS WHICH WOULD BE
 CONSIDERED FOR 24HR OPERATION MAY BE THE LOBBY, FRONT
 DESK, RECEPTION OFFICE LOCATIONS ALONG WITH HALLWAYS.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE SEE TRACK LIGHTING REQUIREMENTS PER
 13-415.2.ABC.1.2
 ** PLEASE SEE NOTE #16 WITH RESPECT TO STAIRWELLS AND
 FAILURE OF DEVICES AS PER NFPA-101.
 ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE
 GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE
 SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES
 STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE.
 PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS
 MAXIMUM FOR TIMER TYPE DEVICES.
 PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR
 EXTERIOR BUILDING LIGHTING ALLOWANCES.
  
 ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS
 REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE
 SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO
 COMPLY.
  
 13) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
 NO RESPONSE WAS SUBMITTED FOR THIS. PLEASE SEE THE
 INFORMATION ON PLANS MENTIONS THE MINIMUM RATING AND
 MENTIONS INFORMATION TO THE ELECTRICAL INSPECTOR.
 PLEASE KNOW THAT THIS INFORMATION IS AND WILL BE
 REQUIRED BE DONE ON PLANS AND SUBMITTED FOR REVIEW
 BEFORE ANY INSTALLATION. PLEASE KNOW THAT IF THE WIND
 LOAD CALCULATIONS AND INFORMATION IS NOT SUBMITTED AT
 THIS TIME, THIS WILL BE PART OF THE CONDITIONS OF
 ISSUANCE WHICH MAY BE DONE..
  
 14) NOTE: PLEASE SEE THE ONLY SOME INFORMATION WAS
 SHOWN FOR THE FIRE ALARM INFORMATION AND NO FIRE
 SPRINKLER INFORMATION WAS SUBMITTED.PLEASE SEE THE
 BASE PLANS FOR THIS BUILDING SHALL CONTAIN THE COMPLETE
 FIRE SPRINKLER LAYOUT AND BASE FIRE ALARM SYSTEM PLEASE
 KNOW THAT BOTH OF THESE WILL STILL BE SUBMITTED FOR
 SEPARATE PERMITS PLANS AND FEES AT A LATER DATE ONCE
 THE BUILDING PERMIT IS ISSUED. BASE SYSTEM FOR FIRE
 ALARM IS SHOWN; HOWEVER PLEASE SEE COMMENTS WITH
 RESPECT TO PLANS SUBMITTED FOR THIS AND DEVICES MISSING
 ETC.
 PLEASE KNOW THAT EVEN THOUGH THESE WILL BE UNDER
 SEPARATE PERMIT, THE MINIMUM REQUIREMENTS FOR THE CODE
 SHALL BE SHOWN ON PLANS.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
 15) NOTE: PLANS DID NOT CHANGE. COMPLIANCE FOR ADA
 DEVICES, LOCATIONS, LEVELS ETC HAVE NOT BEEN MET.
 PLEASE SEE PLANS STILL INDICATE BEING DONE UNDER THE
 CANADIAN NATIONAL BUILDING CODE.
 PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL
 MINIMUM LEVELS AS REQUIRED FOR ALL AREAS. PLEASE KNOW
 IS NOTED THAT THE LEVELS FOR ACCESSIBLE UNITS ARE NOTED
 ON PLANS, HOWEVER THIS IS REQUIRED FOR ALL OTHER AREAS
 AS STATED IN 11-4.28.1
 PLEASE SEE PLANS CURRENTLY STATE THE 1995 CANADA
 NATIONAL BUILDING CODE. PLEASE SEE THAT THESE PLANS ARE
 BEING SUBMITTED IN THE STATE OF FLORIDA IN THE US.
 PLEASE ADJUST PLANS AND ALL CODE REFERENCES. PLEASE BE
 SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN DEVICES
 FROM THE FBC AND PLEASE ALSO SEE NFPA-72. PLEASE KNOW
 THAT THE FBC CHAPTER 11 REQUIREMENTS ARE MORE STRINGENT
 AND THE MORE STRINGENT SHALL APPLY.
 THIS IS THE SAME COMMENT AS NO CHANGES HAVE BEEN MADE.
  
  
 16) NOTE: THIS COMMENT WILL REMAIN AS THE LOCATIONS OF
 ALL DEVICES WHICH MAY BE STATED BY THE FIRE REVIEW MAY
 ALSO AFFECT THE ELECTRICAL PLANS.
 *PREVIOUS REVIEW NOTE * PLEASE SEE FIRE REVIEW COMMENTS
 AS THERE SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS
 ARE MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM, ELEVATOR MACHINE ROOM ) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 17) NOTE:PLEASE BE SURE THESE CODES AS PREVIOUSLY
 NOTED ARE ON THE ARCHITECTURAL PLANS TITLE SHEETS FOR
 CODES AND THE ELECTRICAL PLANS AT A MINIMUM. PLEASE SEE
 SOME OF THE CODES REFLECTED ON PLANS ARE NO LONGER IN
 USE IN THE STATE OF FLORIDA. PLEASE SEE THE FOLLOWING
 CODES SHALL BE LISTED ON ALL PLANS AND ANY CODES
 RELEVANT TO THE SPECIFIC TRADES SHEETS SHALL BE STATED
 ON THOSE SHEETS. (ELECTRICAL) PLEASE LIST THE FOLLOWING
 AT A MINIMUM AS REQUIRED FOR ELECTRICAL REVIEW. 2002
 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD ALSO
 BE STATED ON E-TITLE SHEET.
 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20
 NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY
 CODE.
  
 18) NOTE:PLEASE SEE THAT SOME OF THE PHOTO-METRICS
 SUBMITTED DO NOT COMPLY WITH THE MINIMUM LEVELS
 REQUIRED FOR LIFE SAFETY. PLEASE SEE THE LEVELS AS
 STATED IN PREVIOUS REVIEW. (SEE STAIRS WHICH SHOW ONLY
 2.9FC WHEN A MINIMUM OF 10FC IS REQUIRED.).
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL EGRESS
 PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER EMERGENCY
 LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY OUT AND AWAY
 FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 19) NOTE: PLEASE SEE THIS COMMENT WILL REMAIN AS THE
 DISCONNECTING MEANS FOR EQUIPMENT AND LOCATIONS IN THE
 ELEVATOR EQUIPMENT ROOM NEEDS TO BE MORE DETAILED.
 PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR ALL THE
 REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS. PLEASE 620.23 AND .24 WHICH MORE
 SPECIFICALLY SHOWS THE LIGHTING AND RECEPTACLES ALSO
 BEING SHOWN CIRCUITED TO OTHER AREAS AND ROOMS WHICH
 ARE NOT PERMITTED.
 PLEASE ALSO SEE 620.51 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL AS NOTED AND LOCATIONS REQUIRED.
  
 20) NOTE:SEE NOTE ABOVE, LABEL EQUIPMENT,
 DISCONNECTS, CIRCUITING.
 PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE ELEVATOR
 EQUIPMENT A NOT COMPLETE ON PLANS AT THIS TIME. PLEASE
 SEE KNOW THAT REVIEW OF THIS CAN NOT BE DONE AT THIS
 TIME. PLEASE SEE THE FOLLOWING COMMENT.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 21) NOTE:SAME AS PREVIOUSLY NOTED.
 PLEASE LIST THE CIRCUITING ON THE MDP WITH THE
 RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL
 SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS
 SUBMITTED.
 1,3,5,7,9 / 2,4,6,8, ETC.
 PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE
 ITEMS SHALL CORRELATE.
 FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC
  
  
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME. NO INFORMATION
 WAS SUBMITTED FOR REVIEW.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
 NEC 110.3, 90.7
 FBC 106.1.2
  
  
 23) NOTE:SAME NOTE TO REMAIN AS THE SYMBOLS ON PLANS
 WILL CHANGE AND SOME ARE NOT CLEAR AT THIS TIME. SEE
 PLANS.
 PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD NOT BE
 LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE COMPLETE
 FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 24) NOTE:SAME NOTE TO REMAIN AS SYMBOL AND LEGEND
 WILL CHANGE.
 PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY OF THE
 REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN KEYNOTES
 WILL MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
  
 25) NOTE: PLEASE CORRELATE ARCHITECTURAL PLANS WITH
 THAT OF THE ELECTRICAL PLANS FOR ALL ROOM LAYOUTS AND
 FOOT PRINTS OF ROOMS/BUILDING. PLEASE SEE THE MAIN
 ELECTRICAL ROOM FOR ONE EXAMPLE. PLEASE SEE THE FLOOR
 LAYOUTS DO NOT CORRELATE AND REVIEW FOR SOME ITEMS FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE
 SEE THE ELECTRICAL PLANS DO NOT SHOW ANY ELECTRICAL
 ROOMS FOR THE TYPICAL LAYOUTS AND THE ELECTRICAL
 PANELS. PLEASE SEE NO DOORS ARE BEING SHOWN TO ACCESS
 ANY PANELS? PLEASE SEE ARCHITECTURAL SHEETS AND
 CORRELATE.
 PLEASE SEE 240.24, 110.26 ETC
 ** PLEASE SEE THE ELECTRICAL ROOM WHICH ALSO CONTAINS
 BATHROOM FIXTURES ON PLANS.
 ** PLEASE SEE THE DOOR SWING IN THE MAIN ELECTRICAL
 ROOM SHALL FACE OUTWARD, ALONG WITH PANIC HARDWARE
 ETC.
 PLEASE ADJUST PLANS AND BEAR IN MIND THE REQUIREMENTS
 FOR THE DOOR SWINGS IN THE EGRESS CORRIDOR FOR BUILDING
 CODE.
 PLEASE SEE THE PLANS SHALL ALSO CONTAIN A NOTE FOR DOOR
 HARDWARE.
  
  
  
 26) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE 210.60 WHICH REFERENCES TO 210.52 FOR ITEMS
 REQUIRED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. PLEASE
 KNOW AT THIS TIME IT SEEMS THESE MICROWAVE UNITS ARE
 BEING PERMANENTLY INSTALLED AT AN UPPER LEVEL. PLEASE
 SEE SOME OF THE FOLLOWING COMMENTS WHICH MAY VERY WELL
 APPLY.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO THE HEIGHT OF
 THE MICROWAVE IN ACCESSIBLE UNITS.
  
 27) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE MISSING THE SMALL APPLIANCE CIRCUITS AS
 REQUIRED PER 210.52B1, 210.11C1 AND 220.16. PLEASE KNOW
 THAT NO OTHER OUTLETS MAY BE FED FROM THESE CIRCUITS.
 (IF APPLICABLE)
  
 28) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES LOCATED IN
 THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE FED FROM
 THE LIGHTING CIRCUITS WHICH ARE NOT PERMITTED. PLEASE
 SEE 210.11C1, 220.16 AS NOTED IN NOTE #31
 (WHERE APPLICABLE AS NOTE IN NOTE #30)
  
 29) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR. PLEASE ALSO
 SEE THERE ARE SOME WALL AREAS WHICH ARE MISSING
 RECEPTACLES AS NOTED.
  
 PLEASE SEE MISSING RECEPTSPER 210.52 FOR 2FT OF WALL
 , KITCHEN AREA, KITCHEN WALL OVER 2FT, WITHIN 6FT OF
 DOORS ETC.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED.
 PLEASE SEE MOST UNITS SEEM TO BE OK, HOWEVER THERE ARE
 SOME UNITS WHICH DO NOT HAVE ANY RECEPTS LOCATE DON
 WALLS. PLEASE KNOW IF THIS IS NOT A UNIT WITH PERMANENT
 COOKING WHICH IS NOT YET DETERMINED THEN, SPACING MAY
 FALL UNDER GUEST ROOMS/SUITES AND NOT DWELLING. 210.60
  
 30) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 HEIGHTS, AND USE IS NOT CLEAR AT THIS TIME.
 PLEASE SEE THE HEIGHTS FOR THE MICROWAVES IN ACCESSIBLE
 UNITS ARE AT 62INCHES, WHERE ARE THESE UNITS GOING TO
 BE MOUNTED? AND SHOW DETAIL.
 FBC CHAPTER 11, FHAR 24CFR100.205
  
 31) NOTE: **THIS NOTE WILL REMAIN AS USE AS SUITES AND
 PERMANENT MEANS OF COOKING IS NOT CLEAR.
 PLEASE KNOW THAT IN EITHER CASE WHETHER OR NOT THE
 FACILITY CONTAINS PERMANENT MEANS FOR COOKING THE
 RECEPTACLES SERVING KITCHEN COUNTER SPACE SHALL BE
 GFI/GFI PROTECTED.
 PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING KITCHEN
 COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
  
  
 32) NOTE:PLEASE SEE THE 2002 NEC AS ARC FAULT
 PROTECTION IS NO LONGER ONLY FOR RECEPTACLES IN
 SLEEPING ROOMS. PLEASE SEE THE NOTES ON PLANS WHICH
 MENTION AFCI PROTECTION ONLY FOR RECEPTACLES.
 * PREVIOUS NOTE.
 PLEASE CLARIFY THE ARC FAULT PROTECTION WHICH IS NOT
 CURRENTLY BEING SHOWN. PLEASE SEE NOTE #30 AND IF UNITS
 CONTAIN PERMANENT COOKING MOUNTED EQUIPMENT THEN THESE
 WILL BE REQUIRED FOR PROTECTION IN SLEEPING ROOMS.
 210.12
  
 33) NOTE:SAME NOTE.
 PLEASE EITHER PROVIDE SCHEDULE FOR OCP AND AWG RATINGS,
 OR COMPLETE PANEL SCHEDULES AS PREVIOUSLY NOTED. PLEASE
 COMPLETE ALL PANEL BOARDS WITH THE CONDUCTOR SIZES FOR
 ALL BRANCH CIRCUITS.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
 34) NOTE: PLEASE SEE MISSING SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR TO THE FIRE PUMP SERVICE. 250.50
  
 35) NOTE: PLEASE SEE LOADS FOR CONTINUOUS LOADS IN
 PANEL "P" NEED TO BE SHOWN..
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 PLEASE ADJUST LOAD CALCULATIONS AND MDP. PREVIOUSLY
 NOTED FOR CONTINUOUS LOADS.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 36) NOTE: THIS NOTE WILL REMAIN AND THERE WILL BE
 CHANGES ON PLANS.
 * PREVIOUS NOTE * PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS AND SUMMARY FOR ALL LOADS AND SHOW ALL
 CONTINUOUS/LARGEST MOTOR LOADS AT 125%.
 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC.
  
 37) NOTE: PLEASE ALSO CORRELATE ALL PLANS AND SHEETS AS
 THE PANEL P IS BEING SHOWN IN MULTIPLE LOCATIONS. ONE
 SHEET PANEL IS SHOWN IN ONE ROOM AND ANOTHER SHEET
 SHOWS THIS SAME PANEL LOCATED AT ANOTHER ROOM. PLEASE
 CORRELATE.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION/CLARIFICATION.
  
 38) NOTE:PLEASE SEE ROOF TOP PLANS WHICH INDICATE A
 RTU HOWEVER NO CIRCUITING IS BEING SHOWN ETC. PLEASE
 SEE 440.11 AND 210.63 FOR OTHER REQUIRED DISCONNECTS
 AND WP GFI REQUIRED.
 THIS WAS NOTED ON PREVIOUS PLANS AND SOME INFORMATION
 ON THE MDP WAS PROVIDED HOWEVER DISCONNECTING MEANS AND
 GFI CAN NOT BE DETERMINED AT THIS TIME. PLEASE SEE THE
 NOTES ON PLANS MENTION THE EQUIPMENT CONTAINS INTERNAL
 DISCONNECTING MEANS YET THIS CAN NOT BE VERIFIED.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS WHICH SHOWS
 THIS AS REQUIRED PER 440.11.
 PLEASE SEE THE NOTE ALSO MENTIONS THE GFI REQUIRED WILL
 BE FED FROM THE RTU. HOW IS THIS POSSIBLE WHEN THE
 CIRCUITING DOES NOT INDICATE ANY NEUTRAL CONDUCTOR
 BEING FED FROM THE MDP TO UNIT. THE LOAD FOR THE GFI
 CAN NOT BE FED FROM THE UNIT.
 THE FOLLOWING SCENARIO IS AN EXAMPLE, THE UNIT NEEDS TO
 BE SERVICED AND THE POWER TO THE UNIT IS SHUT DOWN, HOW
 WILL A RECEPTACLE WHICH IS FED FROM THIS UNIT STILL
 CONTAIN POWER FOR SERVICING OR ANY OTHER NEEDS WHEN
 THERE IS NO POWER?
 PLEASE ALSO EXPLAIN WHO THE NEUTRAL IS BEING DERIVED?
 THERE ARE SEVERAL UNANSWERED QUESTIONS AT THIS TIME.
 PLEAS COORDINATE AND ADJUST PLANS.
  
 39) NOTE: PLEASE EXPLAIN WHERE NOTES AND INFORMATION
 FOR THE BELOW AS PREVIOUSLY NOTED IS MET.
 PLEASE SEE NFPA-72 FOR REQUIREMENTS OF THE FACP
 CIRCUIT(S).
 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2 CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS ?FIRE ALARM
 CIRCUIT.?
 4.4.1.4.2.3 THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT
 PLEASE KNOW ANY NOTATION FOR THE REQUIRED LOCK OFF TYPE
 BREAKER SHALL STATE "ANY LOCK-OFF DEVICE SHALL HAVE THE
 HANDLE/LOCK AN INTEGRAL PART OF THE BREAKER" OR WORDS
 TO THAT AFFECT. PLEASE KNOW DEVICES SUCH AS THE
 SNAP/CLIP ON TYPE ARE NOT PERMITTED AS THEY ARE EASILY
 REMOVED OR FALL OFF WHEN A PANEL COVER IS REMOVED WHICH
 THEN NO LONGER PROVIDES THE NEEDED PROTECTION OF THE
 CIRCUITS(S).
  
  
 40) NOTE:PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS
 REQUIRED.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
 THIS IS THE SAME COMMENT AS THE RISER SHOWS TWO
 DIFFERENT SETS OF SERVICE ENTRANCE CONDUCTORS??
  
 41) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD
 ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1,
 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL
 OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY
 FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE
 ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS.
  
 42) NOTE: THIS NOTE REMAINS AS ALL LOCATIONS HAVE NOT
 YET BEEN CONFIRMED AND LOCATIONS ON CEILINGS NEED TO BE
 VERIFIED.
 * PREVIOUS REVIEW NOTE*
 PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES LOCATIONS OF
 SMOKE DETECTORS TO BE INSTALLED WITH MINIMUM CRITERIA.
 PLEASE SEE AREAS WHERE THERE ARE SLOPED CEILINGS AS
 SHOWN ON THE ARCHITECTURAL SHEETS, THE SD SHALL BE
 INSTALLED WITHIN 3FT OF THE PEAK OF THAT SLOPE.
 (LOUNGE) ETC OR WITHIN 12 INCHES OF THE HIGHEST POINT
 ON A FLAT CEILING. PLEASE NOTE THE REQUIREMENTS AS
 LISTED. (3FT FROM BATH ROOM AND KITCHEN DOORS/OPENINGS
 ETC. PLANS DO ALREADY CONTAIN A NOTE FOR THE SMOKE
 DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS. THIS COMMENT
 MAYBE EXPANDED UPON.
 PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION
 MISSING WHICH WILL REQUIRE ADDITIONAL.
  
 43) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. THIS IS REQUIRED FOR ALL ENLARGED LAYOUT
 SHEETS AS WELL.
 FBC 106.1.2, 106.3.5.1.2
  
 44) NOTE: PLEASE SHOW AND COMPLETE LOAD CALCULATIONS
 FOR TRACK LIGHTING PER 220.12B
  
 45) NOTE: NOTE FROM PREVIOUS REVIEW TO REMAIN AS NOTES
 ABOVE MENTION THIS. PLEASE KNOW DOORS SHALL BE SHOWN
 FOR ALL ROOMS, MORE SPECIFICALLY THE MAIN ELECTRICAL
 ROOM(S), ELEVATOR ROOMS ETC. PLEASE KNOW THE LAYOUTS
 FROM THE ARCHITECTURAL SHEETS AND THE ELECTRICAL SHEETS
 DO NOT CORRELATE, THE DOOR SWINGS MAY BE AN ISSUE IF
 THE DOORS ARE ACTUALLY ON THE INSIDE AND LOCATED IN AN
 EGRESS CORRIDOR. PLEASE SEE FBC AND LS101 FOR DOOR
 SWINGS IN EGRESS PATHS.7.2.1.4 ETC
  
 46) NOTE:SAME NOTE, SEE KITCHEN AREAS AND THE LIKE.
 PLEASE SEE 210.8B3 FOR BRANCH CIRCUITS IN KITCHEN AREAS
 AND THE LIKE WHICH REQUIRES PROTECTION FOR ALL 15/20
 AMP 120 CIRCUITS.
  
 47) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 ** ONE COMPLETE SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
  
 48) NOTE: PLEASE SEE THE LOADS ON THE MDP'S AS NOTED ON
 PLANS DO NOT CORRELATE. PLEASE SEE ONE MDP SHOWS ONE
 LOAD AND THE LOAD SHOWN FOR TEH SAME MDP IN OTHER
 LOCATIONS IS YET ANOTHER LOAD?
 PLEASE CORRDINATE ONCE ALL LOADS ARE DONE.
 FBC 106.1.3.5.1.2, 106.1.2
 NEC 220
  
 49) NOTE:PLEASE PROVIDE THE UL DETAILS FOR ANY AND
 ALL FIRE RATED PENETRATIONS.
 NEC 300.21, NFPA-221, 4.2 ETC.
 PLEASE PROVIDE DETAIL SHEET.
  
  
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC,
 THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-06 11:23:501-ROLL IN ELEC FOR REVIEW.
 NOTES TO FOLLOW