Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop B
Sequence Number 2
Notes
Date Text
2007-05-16 10:29:10 
  
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 2NDREVIEW
 ACTION: DENIED
  
 NOTE, THIS REVIEW IS FOR SPRINGHILL SUITES BUT THE
 RESPONCE COMENTS ARE
 HOMEWOOD SUITES!!!!!!!!!!!!!!!
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 802.2.1 QUESTIONABLE SOIL. WILL REQUIRE (3) SIGNED AND
 SEALED ORIGINALS.
  
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4)2ND REQUEST,ADMINISTRATIVE CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5)2ND REQUEST, THE THRESHOLD INSPECTION PLAN IS NOT
 TO BE A GUIDE
 BUT EXPLICIT INSTRUCTIONS DESIGN BY THE ENGINEER OF
 RECORD FOR THE THRESHOLD
 INSPECTOR TO FOLLOW. SINCE THIS IS A DOCUMENET
 CREATED
 BY THE ENGINEER IT IS TO BE SIGNED AND SEALED.FL S.
 S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6)2ND REQUEST,
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7)COMPLIED.
  
 8) 2ND REQUEST, I COULD NOT LOCATE A PLAN ANY PLAN
 AG002,
 THERE IS NO SUCH SHEET IN THE INDEX?109.3.10* IMPACT
 OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9)2ND REQUEST, I COULD NOT LOCATE A PLAN
 ANY PLAN AG002, THERE IS NO SUCH SHEET IN THE INDEX?
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) 2ND REQUEST, PRINTING THE ARCHITECTS NAME COMPLIES
 WITH COMMENT# 11.
 PFVS NEEDS TO BE REGISTERED WITH THE STAT AS A DBA
 "DOING BUSINESS AS" AND ALSO REGISTERED AS AN
 ARCHITECTURAL BUSINESS!!!!!!
 PFVS ARCHITECTURE PLANNING AND INTERIORS
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11)COMPLIED.
  
 12) 2ND REQUEST SHEET G.000 THIS SHEET INDICATES
 NIELSEN STRUCTURAL ENGINEERING
 AS ONE OF THE FIRMS WORKING ON THIS PROJECT BUT THEY
 ARE NOT NOTED ON THE STRUCTURAL SHEETS?106.1.2* IF
 NEILSEN STRUCTURAL ENGINEERING IS THE DESIGNER FOR THIS
 STRUCTURE THEY ARE THE ENGINEERING OF RECORD AND SINCE
 THEY ARE A ENGINEERING BUSINESS A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED.
 471.023 FS CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING SERVICES, SHALL
 INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO
 EACH SHEET.THIS MAY BE ADDED BY HAND.
  
 13) 2ND REQUEST, COMMENT NOT EVEN SHOWN ON THE COMMENT
 SHEET!!!
 SHEET G-000
 13A) 2ND RESPONCE, WHEN OVER 50 SPRINKLER HEADS ARE
 REQUIRED, THE SYSTEM IS TO BE DESIGNED BY A ENGINEER!!
 AGAIN FLORIDA STATUTES REQUIRE THE FIRE SPRINKLER PLANS
 TO BE PART OF THE
 PERMIT PACKAGE.
 THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE I-B
 SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE
 SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES
 BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS,
 SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
  
 14) SHEET A-401, COMPLIED.
 14B) NEW COMMENT THE ACCESS AISLE FOR THE DISSABLED
 PARKING DOES NOT SHOW A CURB CUT OR THE SIDEWALKS
 HAVING SLOPE DOWN TO THE ACCESS AISLE.
  
 15) 2ND REQUEST RESPONCE INDICATED SEE CHANGES ON
 A-401, NO CHANGE INDICATED,
 SHEET A-401, THE FRONT ENTRY DOORS (VESTIBULE) APPEAR
 TO BE HORIZONTAL SLIDING DOORS,
 PLEASE PROVIDE INFORMATION FOR MANUAL LY OPERATED
 (BREAK AWAY) IF LOSS OF POWER. SECTION 1008.1.3.3.
  
  
 16) SHEET A-101:
 16A-C) COMPLIED.
  
 16D) 2ND REQUEST, ROOM 136C LAUNDRY TERMINATION ROOM,
 THE ROOM REQUIRES A 1 HR FIRE RATING SHEET A-401
 ENLARGED PLAN IS MISSING RATED WALLS.707.13.4. 707.13.2
 MATERIALS. A SHAFT ENCLOSURE CONTAINING A REFUSE OR
 LAUNDRY CHUTE SHALL BE CONSTRUCTED OF MATERIALS AS
 PERMITTED BY THE BUILDING TYPE OF CONSTRUCTION. 16D)(1)
 PLEASE PROVIDE THE BLOCK WALL EQUIVALENT THICKNESS, SEE
 TABLE 721.3.2. PROVIDE DOCUMENTATION FROM THE BLOCK
 MANUFACTURER THE MODEL OF BLOCK TO BE USED AND THE
 EQUIVALENT THICKNESS.
 16D)(2)PLANS INDICATE THE USE OF U-438 TYPE WALL BUT
 THE DETAIL DOES NOT PROVIDE INFORMATION ON THE TYPE OF
 JOINT AT THE FLOOR AND CEILING. SEE 713.1.& 713.2.
  
 16E-G) COMPLIED.
  
 16H) 2ND REQUEST, THE PLANS (A-401 ENLARGED) ALSO
 INDICATE SUITES 104 & 106, THERE IS NO WALL TYPE
 IDENTIFICATION. PROVIDE THE STC RATING BETWEEN ROOM.
 RESPONSE SEE A-604 FOR REVISIONS.
 A-604 IS DOOR SCHEDULE. WALL TAG 3A WALL TYPEU-904 DOES
 NOT PROVIDE A STC RATING. WALL WALL TAG# 1A U465 ALSO
 DOES NOT INDICATE A STC RATING, A 3 5/8" METAL STUD
 WALL WITH 5/8" GYPSUM BOARD AND INSULATION ONLY HAS A
 STC RATING OF 46 WITH INSULATION,NOT 50STC.
  
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 16I) 2ND REQUEST, THIS SAME SITUATION SHALL OCCUR
 BETWEEN SUITES BETWEEN FLOORS, SHOW COMPLIANCE WITH:
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16J) COMPLIED.
  
 16K) 2ND REQUESTPLEASE PROVIDE LAUNDRY SHUTE DETAILS:
 707.13.2 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16L) COMPLIED.
  
 16M) 2ND REQUEST, SEE DETAIL# 2 SHEET A-701 UNDER THE
 STAIRS, PLEASE PROVIDE CODE COMPLIANCE FOR HEADROOM
 CLEARENCE UNDER STAIRWELLS,11-4.4.2 HEADROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 16N) 2ND REQUEST,SHEET A-101- A-105 ALL CORRIDORS WITH
 OCCUPANT LOAD GREATER THAN 10 (R-1)REQUIRES 1-HR
 RATED CORRIDORS WITH OPENING PROTECTIVES. PROVIDE DOOR
 IDENTIFICATION AND FIRE RATING. SEE SECTION 715.3. NEW
 STATEMENT IN 715.3 WE ARE LOOKING AT ALL FIRE RATED
 DOORS AND THE REQUIREMENTS OF NFPA 80 REQUIREMENTS
 INCLUDING DOOR CLOSERS & 715.3.3 DOOR ASSEMBLIES IN
 CORRIDORS WHICH REQUIRE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLIES TESTED IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH
 OF THE BOTTOM OF THE DOOR ASSEMBLY.
  
 16O)COMPLIED.
  
 16P) 2ND REQUEST, PLEASE PROVIDE INFORMATION FOR
 ELEVATOR CARS TO ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.RESPONSE SEE A-702 I DO NOT SEE A DETAIL WITH
 THE STRETCHER REQUIREMENT?
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
  
  
 16Q) COMPLIED.
  
  
 16R) 2ND REQUEST,PLEASE PROVIDE INFORMATION FOR THE
 FIRE PUMP, SIZE OF PUMP, TYPE OF PUMP FUEL LOADS IF NOT
 ELECTRIC. THE PLUMBING SHEET P-401 AND ESHEET E-401 ALL
 MATCH EXCEPT FOR
 RPM'S THE ELECTRIC INDICATES 1800 WHILE THE PLUMBING
 SHEET INDICATES 3550? PLEASE PROVIDE HE SPRINKLER PLANS
 AND CALCULATIONS. 903.6.1ANY BUILDING WHICH IS OF
 THREE STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.1 .
  
 17) SHEET A-402
 17A) COMPLIED.
  
 17B) 2ND REQUEST, SHEET A-402 DETAIL# 7 ALSO INDICATES
 A RECESSED FIRE EXTINGUISHER CABINET, HOW IS THE 2 HR
 RATING BEING MAINTAINED? 106.1.2* SECOND REVIEW THIS
 DETAIL HAS NOW BEEN DELETED, PLEASE INDICATE HOW
 COMPLIANCE WITH A 2 HR FIRE RATING WILL BE ACHIEVED?
  
 17C) COMPLIED.
  
 17D) 2ND REQUEST, DETAIL # 1 IS NOW DELETED, SHEET
 A-402 DETAIL# 1, ELEVATOR LOBBY DOORS ARE NOT
 IDENTIFIED, FLOORS 2-5 INDICATE AS DOOR *34, DOOR
 SCHEDULE INDICATES "C" LABEL REQUIRES
 RATING ACCORDING TO TABLE 715.3. THESE DOORS ALSO
 INDICATE HOLD OPEN DEVICES, "E" SHEETS DO NOT INDICATE
 IF TIED TO SMOKE ALARM, SPRINKLER, ETC.
  
 17E) COMPLIED.
  
 18) 2ND REQUEST,A-201- A-202ELEVATIONS INDICATE THE
 USE OF EFISOR EPS (COMBUSTIBLE)TRIM ABOVE 40' ABOVE
 GRADE. BUILDING TYPE I-B.SHEETS A-301, A-302 & A-303.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS
  
 19) 2ND REQUEST, A-303 PARAPET DETAIL (NO EPS ABOVE
 40') DOESN'T INDICATE ANY FASTENING SYSTEM NOR
 STRUCTURAL INFORMATION NOR REFRENCE ANY STRUCTURAL
 SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20A) 2ND REQUEST PLEASE PROVIDE ELEVATION MARKERS, NO
 COMBUSTIBLE TRIM ABOVE 40',A-501 & A-502,PARAPET
 DETAIL DOESN'T INDICATE ANY FASTENING SYSTEM NOR
 STRUCTURAL INFORMATION NOR REFRENCE ANY STRUCTURAL
 SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20B) SHEET A-501 DETAIL# 1 ALSO INDICATES THE USE OF
 5/8" P.T. PLYWOOD ON THE WALL AS WELL AS 3/4" P.T.
 PLYWOOD ROOF SHEATHING. ARCHITECTURAL TRIM TO BE
 NON-COMBUSTILE 1406.2.2.
 ROOF SHEATHING TABLE 601 FOOTNOTE (C)(2) PLEASE PROVIDE
 ELEVATIONS OF VARIOUS DETAILS.
  
 21)2ND REQUEST,ROOF ACCESS SEE A-702 DETAIL# 5 PLANAS
 INDICATE DOOR SWINGING IN AND OUT, PLEASE EXPLAIN?
 106.1.2* ADD INFO REQUIRED.
  
 22) COMPLIED.
  
 23) 2ND REQUEST SHEET A-106AROOF DRAINS AND OVERFLOW
 DRAINS, WHERE IS THE OUTLET FOR THE OVERFLOW ROOF
 DRAINS? 106.1.2*ADD INFO REQUIRED.
  
 24) COMPLIED.
  
 25) 2ND REQUEST,A-604 & A-605 BOTH INDICATE THE USE
 OF WOOD BUCKS FOR WINDOWS AND DOORS. PLANS DO NOT
 INDICATE HOW THE BUCKS ARE TO BE FASTENED, 1714.5.4.1
 ANCHORING REQUIREMENTS.PLANS DO NOT SPECIFY THE
 DIAMETER OF THE TAPCON?
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 25A) WINDOW TYPE W3 INDICATES VARIOUS DETAILS, DETAIL#
 2& 3 INDICATES A HORIZONTAL MULLION BETWEEN THE WINDOW
 AND PTAC UNIT, THE DETAIL DOES NOT INDICATE HOW THE
 MULLION WILL BE TIED BACK INTO THE STRUCTURAL FRAME OF
 THE BUILDING?1707.4.5.2 MULLIONS SHALL BE DESIGNED
 TO TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE
 WINDOW OR DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE.
  
 25B) DETAIL# 4 IS A HEAD DETAIL INDICATING A FIN TYPE
 WINDOW APPLICATION, NOTE THE CLOSENESS OF THE WINDOW
 FIN AND EDGE OF BLOCKWORK OR BEAM AND DERATING THAT
 WILL NEED TO TAKE PLACE FOR TAPCONS! PROVIDE THE
 MANUFACTURER OF TAPCON TO SEE IF DERATING OF TAPCON IS
 ALSO NEEDED IF INSPECTIONS ARE NOR PREFORMED!
  
 25C) DETAIL# 5 IT APPEARS THAT LESS THAN 3/4" OF THE
 WINDOW FIN IS OVER THE WINDOW BUCK NOTE ON THE PRODUCT
 APPROVAL EDGE DISTANCE WHEN SUBMITTED.
  
 25D) NOTE AGAIN EFIS OR EPS SYSTEMS OVER THE 40'
 ELEVATION NOT ALLOWED IF COMBUSTIBLE PROVIDE
 DOCUMENTATION!!!!!!
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28A) SHEET A-702 PLEASE PROVIDE ELEVATOR DETAIL FOER
 VENTING.EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1 ,
 THE AREA OF THE VENTS SHALL NOT BE LESS THAN 3? PERCENT
 OF THE AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET
 (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 3?
 PERCENT NOR LESS THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS
 GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY OPEN TYPE UNLESS
 ALL VENTS ACTIVATE UPON DETECTION OF SMOKE FROM ANY OF
 THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 28B) COMPLIED.
  
 29A) COMPLIED.
  
 29B) 2ND REQUESTPRODUCT APPROVALS SUBMITTED
 WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 29C) 2ND REQUEST,WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 29D)2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS-STOREFRONT,
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN,EPDM ROOFING
 SLOPED:UNDERLAYMENTS, METAL ROOFS
  
 30) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 31) S-101
 31A) PLANS INDICATE PLANS WERE CALCULATED TO ASCE 7-98
 SEE CHAPTER35REFERENCE STANDARDS FOR CORRECTION.
  
 32) 2ND REQUEST, PLEASE PROVIDE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR THE INTERIOR ZONE AND THE END ZONES
 FOR THE OPENING SIZES 10'-100'WITH THE HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENTS. S-101SHOWS THE MAIN
 WIND FORCE RESISTING SYSTEM PRESSURES,NOT THE DESIGN
 WIND PRESSURES LISTED UNDER COMPONENTS AND CLADDING
 INCLUDE HEIGTH AND EXPOSURE
 COEFFICIENTS TABLE1609.6.2.1(4). PLEASE SHOW ON THE
 ELEVATIONS.
  
 33) COMPLIED AS NOTED.
  
 34) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  