| 2008-11-21 10:48:53 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06111067 |
| | ADD: 2437 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | SPRINGHILL SUITES BY MARIOTT |
| | FIVE STORY/ 130 UNITS |
| | |
| | REVISION# 4 : |
| | DENIED |
| | |
| | 1) SHEET A-106 REVISION INDICATES THE DELETION OF THE |
| | OVERFLOW SCUPPERS AND ADDITIONAL OVERFLOW ROOF DRAINS, |
| | THERE ARE TWO ISSUES: |
| | |
| | 1A) FOR OVERFLOW ROOF DRAINS ARE TO ACT AS AN OVERFLOW |
| | SCUPPER WOULD, BY BEING PLACED 2" TO 4" ABOVE THE ROOF. |
| | IF THIS IS A EMERGENCY OVERFLOW IT WOULD ONLY BE USED |
| | IF THE MAINDRAIN IS CLOGGED OR PLUGGED. 1503.4.3 |
| | |
| | 1B) THE SECOND ISSUE HAS TO DO WITH THE PLUMBING ASPECT |
| | OF THE NEW SECONDARY DRAIN BEING THE EMERGENCY |
| | OVERFLOW. I SPOKE WITH KEN THE PLUMBING REVIEWER ON |
| | THIS MATTER. THE PLANS O NOT INDICATE WHERE THE |
| | SECONDARY DRAIN TERMINATES, DOES IT TIE BACK INTO THE |
| | MAIN SYSTEM, A SEPERATE SYSTEM THAT CONTINUES TO GRADE |
| | OR DOES IT TRAVEL BENEATH THE ROOF DECK AND TERMINATE |
| | OVER A WINDOW OR IN THE WALL WHERE IF WATETR IS FLOWING |
| | OUT OF THE PIPE IT WOULD BE NOTICED BY THE PERSONNEL |
| | AND KNOW THERE IS A PROBLEM ? ON THE NEXT SUBMITTAL |
| | PLEASE PROVIDE BOTH THE ARCHITECTURAL SHEETS AS WELL AS |
| | THE PLUMBING SHEETS TO CORRELATE THE REVISION BETWEEN |
| | THE TRADES, THANKS FOR YOUR COOPERATION ON THIS MATTER. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |