Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 16
Notes
Date Text
2009-09-20 12:25:46 
  
 ** DENIED **
  
 ** NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 REVISING.
  
 1) NOTE: SEE COMMENT #2 FROM PREVIOUS REVIEW. NO ACCESS
 CONTROL SYSTEM PERMIT AND PLANS HAVE BEEN SUBMITTED TO
 DATE. IF A SYSTEM HAS BEEN INSTALLED IT WAS DONE
 WITHOUT REVIEW FOR CODE COMPLIANCE AND PERMIT.
 PLANS DO NOT SHOW COMPLIANCE FOR ANY SUCH SYSTEM ONLY
 NOTES FOR FUTURE.
 **ON PREVIOUS REVIEW IT WAS NOTED THAT REVIEW FOR
 NFPA-101 CHAPTER 7 AND OTHER APPLICABLE CODES HAVE NOT
 BEEN DONE.
 ONE EXAMPLE OF NON-CODE COMPLIANCE IS THE FACT THAT A
 JUNCTION BOX FOR FUTURE SYSTEM IS SHOWN IN STAIRS WHICH
 IS NOT PERMITTED PER FBC 1019.1.2
 ACCESS CONTROLS INSIDE STAIRS IS NOT PART OF THE
 STAIRS. PLEASE ADDRESS WITH BUILDING REVIEWER AND FIRE
 MARSHAL CHIEF CARSILLO.
  
 2) NOTE: IT WAS REQUESTED ON PREVIOUS REVIEW TO SUBMIT
 A COMPLETE REVISED PLAN WITH ALL CIRCUITING ON PLANS TO
 BE REVISED AND COORDINATED WITH REVISED SUBMITTED PANEL
 SCHEDULES. SOME REVISED PLANS WERE SUBMITTED ALONG WITH
 RESPONSE SHEETS FROM DESIGN TEAM. THE RESPONSE SHEETS
 DO NOT ACTUALLY RESPOND TO PREVIOUS COMMENTS THEY ONLY
 STATE CHANGES WHICH WERE MADE ON SPECIFIC SHEETS. THE
 RESPONSE ONLY INDICATES CHANGES TO THE FOLLOWING
 SHEETS:
 E001,
 E102,
 E105,
 E401,
 E402,
 E501,
 E504, AND 504A
  
 ** IT SHOULD BE NOTED THAT SOME OF THE PREVIOUS
 COMMENTS WERE NOT ACTUALLY RESPONDED TO BY DESIGN TEAM
 AND PLANS WERE NOT REVISED/CORRECTED EITHER. PLEASE SEE
 PREVIOUS NOTES #16 AND #18 FOR EXAMPLE; SEE NOTES
 BELOW.
  
  
 WHAT ABOUT SHEETS E103, E 411, 412 ??
 PREVIOUS NOTES MENTIONED TO REVISE PLANS FOR ALL
 CIRCUITING. REVIEW FOR LOAD CALCULATIONS FOR EXAMPLE
 CAN NOT BE DONE UNTIL ALL CIRCUITING IS REVISED AND
 COORDINATED WITH PLANS SUBMITTED.
  
 A) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE.
 PLANS INDICATE CIRCUIT R-151 SHOWN FOR CORRIDOR
 LIGHTING HOWEVER REVISED PANEL SCHEDULE FOR PANEL R1
 INDICATES CIRCUIT 151 AS THE BREAK ROOM RECEPTACLE.
 REVISED SHEET 401 DOES INDICATE THIS HOWEVER BASED ON
 E103, THIS CIRCUIT IS SHOWN FOR BOTH LOCATIONS. THIS IS
 NOT POSSIBLE.
  
 B) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE.
 PLEASE SEE CIRCUIT R1-149 WHICH PER E103 INDICATES THIS
 AS LIGHTING FOR STAIRS. HOWEVER BASED ON REVISED R1
 PANEL SCHEDULE R149 IS SHOWN FOR DISPOSAL.
  
 C) SEE LATEST REVISED SHEET E-103 WHICH WAS NOT
 SUBMITTED OR IN NOTED IN LETTER FROM DESIGN TEAM. THIS
 SHEET HOWEVER IS ON FILE. PLEASE SEE CIRCUIT M1-48
 SHOWN ON PLANS AS EXTERIOR LIGHTS. AS NOTED ON PREVIOUS
 REVIEW PANEL M1 IS A 42 CIRCUIT PANEL AND THERE ARE NO
 CIRCUITS ABOVE 42 LISTED.
  
 D) PLEASE REVISE THE LATEST ROOM PLANS FOR ALL
 RECEPTACLES AND LOCATIONS. REVISED CIRCUITING FOR
 ELECTRICAL NEEDS BE REVIEWED FOR CODE COMPLIANCE. IT
 SHOULD BE NOTED THAT CIRCUITS SUCH AS R*147 ON LATEST
 REVISED FILE SET OF PLANS ON SHEET E104 IS FOR CORRIDOR
 LIGHTS ON MULTIPLE FLOORS HOWEVER PER LATEST REVISED R*
 SCHEDULES, THIS IS ACTUALLY NOTED FOR ROOM MICROWAVES.
  
 E) PLEASE SEE LATEST REVISED PANELS R* R1-R5 INDICATE
 CIRCUIT R*164 AS MULTIPLE DIFFERENT CIRCUITS YET THE
 LATEST REVISED PLANS ON FILE FOR SHEET E104 INDICATES
 ALL R* 164 BEING TYPICAL TO ELEVATOR LOBBY LIGHTS.
 OTHERS LISTED ARE * VENDING MACHINE*, EXERCISE ROOM
 RECEPTACLES*, * HALL RECEPTACLE, * ENG/MAIN RECEPTACLE.
 ETC.
  
 *** BASED ON NO REVISED SHEETS SUBMITTED FOR THE ABOVE
 LISTED, REVIEW FOR MINIMUM CODE COMPLIANCE FOR MANY
 OTHER CIRCUITS, LOAD CALCULATIONS, PANELS BEING ETC CAN
 NOT BE DONE AT THIS TIME. PLEASE SUBMIT A COMPLETE SET
 OF REVISED PLANS SO THAT REVISED PLANS CAN BE REVIEWED.
 THE ABOVE ARE SOME EXAMPLES AND ARE NOT ALL AS PLANS ON
 FILE ARE SUBSTANTIALLY DIFFERENT FROM REVISED PANELS
 AND LOAD CALCULATIONS SUBMITTED.
  
 ** 408.4, 220 UNDER 2002 NEC 220.3, 220.11, 220.12,
 220.14 ETC
  
 3) NOTE: NEW COMMENT EVEN THOUGH FBC CHAPTER 11 WAS
 NOTED ON ORIGINAL REVIEWS. ALL AREAS WHICH ARE ADA
 ACCESSIBLE NEED TO MEET FBC 11-4.27.4 FOR CONTROL
 DEVICES. THE ORIGINAL PLANS MENTION TWIST TIMERS IN
 GUEST LAUNDRY ROOMS. ARE ALL OF THESE ROOMS ADA?
 GUEST LAUNDRY AREAS WHICH ARE ADA NEED TO MEET SECTION
 ABOVE. IT SHOULD BE VERIFIED AS IT IS UNDERSTOOD BY
 THIS REVIEWER, WHAT IS SHOWN ON PLANS AND INSTALLED MAY
 NOT MEET SECTION. TYPE OF DEVICE AND ACCESSIBILITY IS
 KEY TO MEETING MINIMUM COMPLIANCE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT #16. NO
 RESPONSE FROM DESIGN TEAM AND RISER SHEET WAS NOT
 REVISED.
 PLEASE REVISE VOLTAGE DROP CALCULATIONS TO COORDINATE
 WITH THE REVISED FEEDERS FOR ALL PANELS. SEVERAL WERE
 REVISED TO ALUMINUM YET THE CALCULATIONS STILL INDICATE
 12.9 FOR CONSTANT IN CALCULATIONS.
 ANOTHER WOULD BE FEEDER SIZES. EXAMPLE WOULD BE M-5.
 PER MDP THE CONDUCTORS ARE 4/0 ALUMINUM YET THE VOLTAGE
 DROP CALCULATIONS INDICATE 1/0 COPPER.
 ANOTHER WOULD BE PANEL H-5 AS SPECIFICALLY NOTED ON
 PREVIOUS REVIEW. MDP STILL INDICATES 300MCM ALUMINUM
 YET CALCULATIONS CLEARLY STILL INDICATE 500MCM COPPER.
 13-413.1ABC.1,13-413.1.ABC.1.1,13-413.1.ABC.1.2, NEC
 310.16, TABLES IN CHAPTER 9
  
 5) NOTE: PLEASE SEE THAT NO RESPONSE TO PREVIOUS REVIEW
 COMMENT #18 WAS SUBMITTED AND NO REVISED SHEET E503 WAS
 SUBMITTED.
  
 6) NOTE: PLEASE SEE THAT NO RESPONSE WAS MADE TO
 PREVIOUS COMMENT #17. SOME SHEETS WERE SUBMITTED AND
 REVISED HOWEVER BASED ON COMMENTS ABOVE THIS WAS NOT
 ADDRESSED. HOUSE LOADS ON PANEL SCHEDULES CAN NOT BE
 CONFIRMED AS MEETING MINIMUM CODE IF THE PLANS DO NOT
 COORDINATE.
 PLEASE RESPOND, REVISE AND SUBMIT COMPLETED PLANS.
 220,310,240, 408.4ETC
  
 7) NOTE: AS STATED IN PREVIOUS REVIEW, SHEET E501
 STATES HOUSE PANEL M1 HAS *0* AS THE LOAD FOR LIGHTING.
 THIS IS NOT POSSIBLE WHEN THE LIGHTING PLANS SUCH AS
 E103 STILL INDICATE HOUSE LIGHTING CIRCUITS TO M1
 PANEL.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  