Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 12
Notes
Date Text
2009-07-16 13:06:17** DENIED REVISIONS **
  
 1) NOTE: THE SUBMITTED SHEET E-501 WAS NOT ACTUALLY
 REVISED. THE SAME REVISION #7 ON THE TITLE BLOCKS WAS
 SUBMITTED PREVIOUSLY. KEEP IN MIND THE PREVIOUS RISER
 WAS REDLINED ON REV #7 AS ONE MDP SCHEDULE INDICATES
 3200 AND THE OTHER 3500AMP BREAKER. BASED ON THE
 SERVICE ENTRANCE CONDUCTORS, IT SHOULD BE THE 3200 AS
 GONE OVER ON THE PREVIOUS CONVERSATIONS AND E-MAILS
 WITH THE ENGINEER.
 ** THIS WAS REDLINED ON PREVIOUS REVISION HOWEVER IF
 MAKING CHANGES PLEASE REVISE AND COORDINATE.
  
 230.70, FBC 106.1.1
  
 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULES AND LOAD
 CALCULATIONS FOR ALL PANELS AND EQUIPMENT AFFECT BY THE
 NEW CIRCUITING AND EQUIPMENT ON THE REVISED E401. ONE
 EXAMPLE WOULD BE M1- 20,22, 24. THIS EQUIPMENT AND
 CIRCUIT IS SHOWN AS A *SPARE* ON THE LATEST M1 SCHEDULE
 AND CALCULATIONS. THIS IS ONE EXAMPLE ONLY AS THERE ARE
 OTHER ITEMS WHICH WERE ALSO NOT UPDATED.
 408.4, FBC 106.1.1,106.5
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  