| Plan Review Notes For Permit 06111067 |
| Permit Number |
06111067 |
|
| Review Stop |
E |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2009-07-16 13:06:17 | ** DENIED REVISIONS ** | | | | | | 1) NOTE: THE SUBMITTED SHEET E-501 WAS NOT ACTUALLY | | | REVISED. THE SAME REVISION #7 ON THE TITLE BLOCKS WAS | | | SUBMITTED PREVIOUSLY. KEEP IN MIND THE PREVIOUS RISER | | | WAS REDLINED ON REV #7 AS ONE MDP SCHEDULE INDICATES | | | 3200 AND THE OTHER 3500AMP BREAKER. BASED ON THE | | | SERVICE ENTRANCE CONDUCTORS, IT SHOULD BE THE 3200 AS | | | GONE OVER ON THE PREVIOUS CONVERSATIONS AND E-MAILS | | | WITH THE ENGINEER. | | | ** THIS WAS REDLINED ON PREVIOUS REVISION HOWEVER IF | | | MAKING CHANGES PLEASE REVISE AND COORDINATE. | | | | | | 230.70, FBC 106.1.1 | | | | | | 2) NOTE: PLEASE SUBMIT REVISED PANEL SCHEDULES AND LOAD | | | CALCULATIONS FOR ALL PANELS AND EQUIPMENT AFFECT BY THE | | | NEW CIRCUITING AND EQUIPMENT ON THE REVISED E401. ONE | | | EXAMPLE WOULD BE M1- 20,22, 24. THIS EQUIPMENT AND | | | CIRCUIT IS SHOWN AS A *SPARE* ON THE LATEST M1 SCHEDULE | | | AND CALCULATIONS. THIS IS ONE EXAMPLE ONLY AS THERE ARE | | | OTHER ITEMS WHICH WERE ALSO NOT UPDATED. | | | 408.4, FBC 106.1.1,106.5 | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|