| Plan Review Notes For Permit 06111067 |
| Permit Number |
06111067 |
|
| Review Stop |
FIRE |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2009-04-24 11:08:24 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS | | | IN TERMS OF CLASS A, CLASS B, OR CLASS C AS PER | | | 28.3.3.2 OF NFPA 101. | | | | | | 4. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR | | | CLASS II AS PER 28.3.3.3 OF NFPA 101. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|