Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-20 16:28:36 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
  
 2.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE
 LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM
 THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE
 TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR
 WEBSITE. FAC 61G1-16.004(1) & FS 481.2055.
  
 3. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
  
 4. SHT AC103 INFORMATIONAL: A SEPARATE POOL PERMIT IS
 REQUIRED. PLANS SHALL BE REVIEWED, APPROVED, AND
 STAMPED BY THE PALM BEACH COUNTY HEALTH DEPT. PRIOR TO
 SUBMITTAL FOR APPLICATION AND REVIEW BY WEST PALM BEACH
 PLAN REVIEW. SECTION 102.2.1.
  
 5. SHT G-000 GUESTROOM MATRIX INDICATES 2 HEARING
 IMPAIRED UNITS, STANDARD DOUBLE/DOUBLE, BUT THE FLOOR
 PLANS SHTS A-101 THRU A-105 ONLY SHOW 1 ON THE 4TH
 FLOOR. PLEASE CLARIFY & CORRELATE INFORMATION BETWEEN
 THE FLOOR PLANS & MATRIX. SECTION 106.1.1 & SECTION
 11-9.1.3.-PLEASE INDICATE WHICH ROOMS COMPLY WITH
 SECTION 11-9.1.3.
  
 6. SHT G-000 PLEASE CLARIFY THE DIFFERENCE BETWEEN A
 KING STANDARD, A KING CONNECTOR, A KING SUITE, AND
 INDICATE HOW THE ACCESSIBLE UNITS ARE DISPERSED AMONG
 THE VARIOUS CLASSES. ALSO PLEASE CLARIFY DIFFERENCE
 BETWEEN THE KING TYPE A, KING ALTERNATE, THE KING & THE
 KING ALT B AND INDICATE HOW THE ACCESSIBLE UNITS ARE
 DIAPERSED AMONG THE VARIOUS CLASSES.--PLEASE
 CLARIFY THE DIFFERENCE BETWEEN THE DOUBLE/DOUBLE
 STANDARD, THE DOUBLE/DOUBLE CONNECTOR STANDARD, THE
 DOUBLE/DOUBLE TYPE "A", THE DOUBLE/DOUBLE TYPE "B", THE
 DOUBLE/DOUBLE TYPE "C", THE DOUBLE/DOUBLE SUITE TYPE
 "A", THE DOUBLE/DOUBLE SUITE TYPE "B", AND THE
 DOUBLE/DOUBLE ALTERNATE.--THE DIFFERENCES SHALL BE
 CALLED OUT ON THE PLANS.-- OF CONCERN ALSO IS THE
 MATRIX DOES NOT MENTION THE PRESIDENTIAL SUITE SHOWN ON
 SHT A-411, AND IS INDICATED AS A DOUBLE/DOUBLE ON SHTS
 A-103, A-104 & A-105. PLEASE INDICATE WHY AN ACCESSIBLE
 UNIT FOR THE PRESIDENTIAL SUIT IS NOT PROVIDED.--
 ALSO OF CONCERN IS THE GUESTROOM MATRIX SHOWS
 ACCESSIBLE KING UNITS UNDER THE SECTION OF THE MATRIX
 INDICATED AS "KING GUESTROOMS", BUT UNDER THE SECTION
 INDICATED AS "DOUBLE/DOUBLE GUESTROOMS" THE ACCESSIBLE
 UNITS ARE "KING ACCESSIBLE UNITS". PLEASE CLARIFY.
 PLEASE COMPLY WITH SECTION 11-9.1.2.
  
 7. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE
 FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX
 INDICATES A TOTAL OF 7 ACCESSIBLE UNITS, BUT THE FLOOR
 PLANS INDICATE A TOTAL OF 12 UNITS. PLEASE CORRELATE
 THE INFORMATION ON THE MATRIX AND THE FLOOR PLANS.
 SECTIONS 106.1.1 AND 11-9.1.2.
  
 8. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.
  
 9. SHT A-401 TOILET ROOM 134, NO FIXTURES ARE SHOWN.
 PLEASE CLARIFY. SECTION 1106.1.
  
 10. SHTS A-411, & A-412 SHOW THE CLEAR FLOOR SPACE FOR
 EACH FIXTURE AND SHOW EACH FIXTURE IN THE ACCESSIBLE
 UNITS. SECTIONS 11-4.16.
  
 11. SHT A-600 FINISH SCHEDULE FOR ROOMS 134, 150, & 151
 SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2
 CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT
 AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE COMPLY.
  
 12 SHT A-801 ELEVATION 15. THE SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD APPROACH
 CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED.
  
 13. SHTS A-802 APPLICABLE ELEVATIONS 1 THRU 13,A-803
 APPLICABLE ELEVATIONS 1- THRU 14, A-804 APPLICABLE
 ELEVATIONS 1 THRU 15, SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & 11-4.22
 AND ALL SUBSECTIONS. PLEASE INDICATE ON ELEVATIONS.
 ALSO SHOW ALL W/C'S TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, & SHOW ALL LAVS TO BE MIN.
 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE WHERE
 THE FIXTURES ARE ADJACENT TO THE WALLS. FIGURES 11-28
 AND 11-32.
  
 14. SHT A-806 DETAIL 5 INDICATE THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 15. SHT A-806 DETAILS 1,3,5 & 6 REFERENCE A BREAKFAST
 ROOM. THIS IS NOT SHOWN ON SHTS A-101 1ST FLOOR PLAN,
 NOR ON SHT A-401. PLEASE CLARIFY. IDENTIFY THIS ROOM ON
 THE FLOOR PLAN & INDICATE THE DETAIL NUMBERS AND THE
 SHT THAT THE DETAILS CAN BE FOUND ON THE FLOOR PLAN.
 SECTION 106.1.1.
  
 16. SHT A-812 DETAIL 1, INDICATES A WATER WALL FEATURE.
 MORE INFORMATION IS REQUIRED. WILL THERE BE A WATER
 SUPPLY LINE CONNECTED TO THE WATER FEATURE? WILL THE
 WATER FEATURE CONNECT TO THE SANITARY DRAINAGE SYSTEM.
 PLEASE CLARIFY.SECTION 106.1.1.
  
 17. SHT A-813 DETAIL 4, SHOW THE FOLLOWING:
 A. 11-4.19.2 CLEARANCE
 B. 11-4.19.5 FAUCETS
  
 18. ALL MPE SHEETS. A "WET SIGNATURE" IS REQUIRED AND
 SHALL BE AFFIXED TO THE PLANS WHEN THE DOCUMENT IS
 SEALED & DATED. "STAMP SIGNATURES" ARE NOT APPROVED.
 FAC 61G15-23.002(2) & FS 471.025.
  
 19. ALL MECH. AND PLMG. SHEETS. THE ENGINEER'S SEAL IS
 NOT APPROVED. THERE WAS A 2 YEAR GRACE PERIOD ENDING
 DEC. 31, 2006 ALLOWING THE USE OF THE OLDER SEALS THAT
 ARE OBSOLETE NOW AND HAD THE WORD "CERTIFICATE" ON THE
 SEAL. THE NEW SEAL SHALL HAVE THE WORD "LICENSE" ON THE
 SEAL. (SEE THE ATTACHED SHEET FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS). PLEASE RESEAL ALL SHEETS
 DESIGNED BY ENGINEERS. FAC 61G15-23.001 & FS 471.025.
  
 20. SHTS P101 THRU P105 MINIMUM 1/8" SCALE PLANS
 REQUIRED. SECTION 106.1.3. PLEASE SUBMIT FLOOR PLANS
 THAT MEET THIS REQUIREMENT.
  
 21. SHT P101 PLUMBING KEYNOTES #14 AND FLOOR PLAN
 SHOWING THE ELEVATOR SUMP PUMP CONNECTING TO THE
 SANITARY SYSTEM. THIS IS NOT APPROVED AND THE
 WATER/WASTE/OIL FROM THE ELEVATOR SUMP PIT SHALL BE
 COLLECTED AND TREATED AS HAZARDOUS MATERIAL AND
 DISPOSED OF AS SUCH.MUNICIPAL CODE 90-125(B)(1).
  
 22. SHT P101 SOME RISERS AND SOME FIRST FLOOR FIXTURES
 SHOW NO PIPING OR BRANCH LINES CONNECTING THE
 RISERS/FIXTURES TO THE BUILDING DRAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 23. SHTS P101 & CIVIL PLAN SHT 6 OF 9. SHT 6 OF 9 SHOWS
 A 3" METER, BACKFLOW, & WATER SERVICE. SHT P101 SHOWS
 4" DOMESTIC WATER ENTERING THE BUILDING. PLEASE SUBMIT
 CALCULATIONS FOR THE REQUIRED SIZE FOR THE WATER
 SERVICE PER SECTION 603.1 AND TABLE 603.1. SEE APPENDIX
 "E"
  
 24. SHT P101 TOILET ROOMS BY THE EXERCISE ROOM SHOW
 FLOOR DRAINS IN THE SHOWERS, BUT NO PIPING TO THE
 SHOWER DRAINS. PLEASE CLARIFY. SECTION 106.1.1.
  
 25. SHTS P101 THRU P105 GENERL NOTES #1. "ALL SANITARY
 AND WASTE PIPING SHALL SLOPE @ 1/8"/FT UNLESS OTHERWISE
 NOTED". PIPE SHALL BE SLOPED PER TABLE 704.1. PIPE
 2-1/2" OR LESS SHALL BE SLOPED MINIMUM 1/4" PER FT.
 PLEASE INDICATE ON PLANS.
  
 26. SHTP105 SHOW THE LOCATION OF ALL PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW ALL RELATED PIPING. SECTION
 106.1.1.
  
 27. SHT P401 WATER HEATER ROOM. PLEASE INDICATE WHY A
 DOUBLE CHECK BACKFLOW PREVENTOR IS BEING CALLED FOR IN
 THE DISTRIBUTION WATER PIPING UPSTREAM OF THE BOOSTER
 PUMPS. AN RPZV BACKFLOW WILL BE INSTALLED DOWNSTREAM OF
 THE METER ON THE WATER SERVICE, AND A DOUBLE CHECK
 BACKFLOW IS NOT THE CORRECT USAGE FOR THE DISTRIBUTION
 OF POTABLE WATER. TABLE 608.1. PLEASE DELETE FROM
 PLANS. SECTION 106.1.1.
  
 28. SHT P401 FIRE PUMP ROOM, THE FLOOR DRAINS ARE NOT
 VENTED. SECTION 901.2.1. THE FLOOR PLAN DOES NOT
 REFLECT THE PIPING LAYOUT ON SHT P101. PLEASE CORRELATE
 THE FLOOR PLANS. SECTION 106.1.1.
  
 29. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401).P-8 IS SHOWN FOR TUBS INDICATED AS P-9 ON
 SHT P401. PLEASE CORRELATE RISERAND FLOOR PLAN.
 SECTION 106.1.1. - THE BRANCH LINE FOR THE DETAIL IS
 SHOWN AS OFFSET, BUT THE FLOOR PLAN SHOWS THE PIPING TO
 THE CENTER OF THE BATHROOMS. PLEASE CORRELATE.
  
 30. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401) . P-8 IS SHOWN FOR TUBS INDICATED AS P-9 ON
 SHT P401. PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1. - THE BRANCH LINE FOR THE DETAIL IS
 SHOWN AS OFFSET, BUT THE FLOOR PLAN SHOWS THE PIPING TO
 THE CENTER OF THE BATHROOMS. PLEASE CORRELATE RISER AND
 FLOOR PLAN.
  
 31. SHT P501 DETAIL 7 DOES NOT REFLECT THE FLOOR PLAN
 FOR THE FIRST FLOOR. CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
  
 32. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
  
 33 SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
  
 36. SHT 602 DETAIL 1 SHOWS A GREASE TRAP INSIDE THE
 FOOD PREP AREA. THIS IS NOT APPROVED PER SECTION
 90-124(7)(B) OF THE MUNICIPAL CODE. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
  
 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND
 MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING
 ON THE REVISIONS OR COMMENT RESPONSES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  