2007-01-26 16:49:33SPRINGHILL SUITES HOTEL
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1 THROUGH 10, PLEASE
 CORRECT.
  
 2) SEE PAGE M-101 PLANS SHOW GUEST LAUNDRY ROOM, NEEDS
 TO SHOW FIRE PUMP ROOM, PLEASE CORRECT.
  
 3) SEE PAGE M-102 PLANS SHOW ENG. & MAINT. NEEDS TO
 SHOW JAN./GUEST LAUNDRY, PLEASE CORRECT.
  
 4) NEED DETAIL ON PLANS SHOWING HOW CONDENSER UNIT (CU)
 STANDS ARE TO BE SECURED TO THE ROOF AND HOW THE
 CONDENSER UNITS ARE TO BE SECURED TO THE STANDS TO
 WITHSTAND 140 MPH WINDS, PER 2004 FBC 1609.
  
 5) PLEASE PROVIDE PRODUCT APPROVALS FOR LOUVER VENTS ON
 POOL HOUSE AND CONDENSER UNIT STANDS.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.