Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-07 13:45:53** UNSAT ***
  
 SPRINGHILL SUITES
 5-STORY 130 UNITS.
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE: PLEASE KNOW AS THIS WILL BE A THRESHOLD
 PROJECT AND THREE SETS OF ALL PLANS AND ALL DOCUMENTS
 SHALL BE SUBMITTED FOR REVIEW AND STAMPING.
 PLEASE SEE BUILDING REVIEW NOTES ALSO.
 FBC ADMIN SECTIONS 109.3.6, 106.1.2
  
 2) NOTE: PLEASE SEE FS 471.025 AND FAC 61G15-23.002 AS
 ALL PLANS SHALL BEAR THE ORIGINAL AND LEGAL SIGNATURE
 FOR THE ENGINEER OF RECORD ON ALL DOCUMENTS. PLEASE SEE
 BOTH SETS OF PLANS SUBMITTED IN FACT CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURES AND DATE ON MOST OF
 THE MP AND E SHEETS. PLEASE SEE ONLY SOME OF THE SHEETS
 ACTUALLY CONTAINED AN ORIGINAL WET INK SIGNATURE.
 PLEASE KNOW THE COMMENT IS FOR ALL MEP PLANS WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADE(S).
 PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS
 OFFICE.
  
 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS ON ALL
 ENGINEERING SHEETS WHICH ARE REQUIRED PER FAC
 61G15-23.002 AND FS 471.023
 THIS IS FOR M,E,P AND S SHEETS.
 PLEASE ALSO SEE MISSING THE FOLLOWING.
 THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER.
 THE CERTIFICATE OF AUTHORIZATION NUMBER/ALSO KNOWN AS
 THE ENGINEERING BUSINESS #.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE SEE THE MECHANICAL AND PLUMBING SHEETS
 WHICH ARE SEALED WITH A RAISED SEAL WHICH IS NO LONGER
 VALID FOR USE IN THE STATE OF FLORIDA. PLEASE SEE THE
 FAC 61G1-16.001 WHICH RULED IN FEBRUARY OF 2004 THAT
 ALL SEALS SHALL BEAR THE WORDING OF "LICENSE" AND THE
 PREVIOUS WORDING OF "CERTIFICATE" WOULD NO LONGER BE
 PERMITTED IN THE STATE OF FLORIDA. PLEASE KNOW AN
 EXTENSION WAS GRANTED TO THE DATE OF DECEMBER 31ST,
 2005 HOWEVER ALL PLANS AFTER THIS DATE SHALL CONTAIN
 THE NEW WORDING OF LICENSE. PLEASE OBTAIN NEW SEAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 7) NOTE: PLEASE SEE THAT ONCE THE ADDRESS FOR SAID
 PROJECT IS FINALIZED; PLEASE BE SURE THE TITLE BLOCKS
 FOR ALL SHEETS CONTAIN THE CORRECT ADDRESS.
 PLEASE SEE A PRELIMINARY ADDRESS OF 2437 METROCENTRE
 BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL
 CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS
 ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING
 REVIEWER AND THE FIRE MARSHAL'S OFFICE. AT THIS TIME
 THE ADDRESSING REVIEW HAS ASSIGNED THE ABOVE 2437. FAC
 61G1-16.004, FAC 61G15-23.002
 * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES.
  
 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY
 READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
  
 9) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A
 POOL, PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT
 WITH PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 10) NOTE: PLEASE SEE NO ENERGY CALCULATIONS PER FBC
 2004 CHAPTER 13 WERE SUBMITTED FOR REVIEW.
 13-415.1.AB.1
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE
 GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE
 SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES
 STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE.
 PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS
 MAXIMUM FOR TIMER TYPE DEVICES.
 PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR
 EXTERIOR BUILDING LIGHTING ALLOWANCES.
  
 ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS
 REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE
 SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO
 COMPLY.
  
 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
  
 12) NOTE: PLEASE SEE THE BASE PLANS FOR THIS BUILDING
 SHALL CONTAIN THE COMPLETE FIRE SPRINKLER LAYOUT AND
 BASE FIRE ALARM SYSTEM PLEASE KNOW THAT BOTH OF THESE
 WILL STILL BE SUBMITTED FOR SEPARATE PERMITS PLANS AND
 FEES AT A LATER DATE ONCE THE BUILDING PERMIT IS
 ISSUED. BASE SYSTEM FOR FIRE ALARM IS SHOWN, HOWEVER
 PLEASE SEE COMMENTS WITH RESPECT TO PLANS SUBMITTED FOR
 THIS AND DEVICES MISSING ETC.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS.
 PLEASE KNOW IS NOTED THAT THE LEVELS FOR ACCESSIBLE
 UNITS ARE NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR
 ALL OTHER AREAS AS STATED IN 11-4.28.1
 PLEASE SEE PLANS CURRENTLY STATE THE 1995 CANADA
 NATIONAL BUILDING CODE. PLEASE SEE THAT THESE PLANS ARE
 BEING SUBMITTED IN THE STATE OF FLORIDA IN THE US.
 PLEASE ADJUST PLANS AND ALL CODE REFERENCES. PLEASE BE
 SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN DEVICES
 FROM THE FBC AND PLEASE ALSO SEE NFPA-72. PLEASE KNOW
 THAT THE FBC CHAPTER 11 REQUIREMENTS ARE MORE STRINGENT
 AND THE MORE STRINGENT SHALL APPLY.
  
 14) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS THERE
 SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS ARE
 MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM, ELEVATOR MACHINE ROOM ) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 15) NOTE: PLEASE SEE SOME OF THE CODES REFLECTED ON
 PLANS ARE NO LONGER IN USE IN THE STATE OF FLORIDA.
 PLEASE SEE THE FOLLOWING CODES SHALL BE LISTED ON ALL
 PLANS AND ANY CODES RELEVANT TO THE SPECIFIC TRADES
 SHEETS SHALL BE STATED ON THOSE SHEETS. (ELECTRICAL)
 PLEASE LIST THE FOLLOWING AT A MINIMUM AS REQUIRED FOR
 ELECTRICAL REVIEW.
 2002 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD
 ALSO BE STATED ON E-TITLE SHEET.
 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20
 NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY
 CODE.
  
 16) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER
 EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY
 OUT AND AWAY FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 17) NOTE: PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR
 ALL THE REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS. PLEASE 620.23 AND .24 WHICH MORE
 SPECIFICALLY SHOWS THE LIGHTING AND RECEPTACLES ALSO
 BEING SHOWN CIRCUITED TO OTHER AREAS AND ROOMS WHICH
 ARE NOT PERMITTED.
 PLEASE ALSO SEE 620.51 FOR REQUIRED DISCONNECTING MEANS
 FOR ALL AS NOTED AND LOCATIONS REQUIRED.
  
 18) NOTE: PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE
 ELEVATOR EQUIPMENT A NOT COMPLETE ON PLANS AT THIS
 TIME. PLEASE SEE KNOW THAT REVIEW OF THIS CAN NOT BE
 DONE AT THIS TIME. PLEASE SEE THE FOLLOWING COMMENT.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 19) NOTE: PLEASE LIST THE CIRCUITING ON THE MDP WITH
 THE RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL
 SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS
 SUBMITTED.
 1,3,5,7,9 / 2,4,6,8, ETC.
 PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE
 ITEMS SHALL CORRELATE.
 FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC
  
 20) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING ROOMS
 WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK
 UP LIGHT OF SOME KIND.
 MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, BOTH ELEVATOR
 CONTROL/MACHINE ROOMS.
 90.4, LS 101 7.8, 7.9, 700.12E, 700.16.
  
 21) NOTE: PLEASE CLARIFY THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT AND PANELS. PLEASE SEE THE RISER AND
 SOME PANELS SHOW SOME PANELS AND THEIR RATINGS, HOWEVER
 NOT ALL.
 PLEASE COMPLETE.
 PLEASE SEE 110.9, 110.10, 240.12 ETC.
 PLEASE ALSO SEE THE NOTES WITH RESPECT TO THE FIRE PUMP
 CONTROLLER WHICH SHALL ALSO STATE THE MINIMUM RATINGS.
  
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
  
 ** PLEASE KNOW DETERMINATION FOR WHETHER OR NOT ON-SITE
 GENERATOR BACK UP FOR THE FIRE PUMP HAS NOT YET BEEN
 CONFIRMED WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE KNOW AS FLORIDA HAS BECOME PRONE TO HURRICANES
 AND TROPICAL STORMS ON MORE OF A SUBSTANTIAL TIME FRAME
 FROM YEARS PAST AND THE POWER NOT BEING AVAILABLE FOR
 THE FIRE PUMP IN AN EMERGENCY HAS BECOME A CONCERN OF
 THIS OFFICE AND THE FIRE MARSHAL'S OFFICE. PLEASE KNOW
 THIS MAY BE CONSIDERED AS REQUIRED PER 695.3, NFPA-20
 9.2.1.1 THAT A ON-SITE POWER MAY BE REQUIRED. PLEASE
 SEE THE NEXT COMMENT.
  
 23) NOTE: PLEASE BE SURE TO PLACE NOTE(S) ON PLANS FOR
 ALL SIGNAGE REQUIRED FOR SERVICE LOCATIONS AND FIRE
 PUMP LOCATION. 230.2E
 PLEASE ALSO SEE 9.3.2.2.3.2 WHICH STATES A PLACARD
 SHALL BE PLACED ADJACENT TO THE FIRE PUMP CONTROLLER
 STATING THE LOCATION OF THIS DISCONNECTING MEANS AND
 THE LOCATION OF THE KEY (IF THE DISCONNECTING MEANS IS
 LOCKED).
 FBC 106.1.2 ADMIN SECTION.
  
 24) NOTE: PLEASE SEE FIXTURE LEGEND SHALL STATE THE
 MINIMUM TIMES ON THE EMERGENCY AND EXIT LIGHTS AS
 REQUIRED PER LS 101 7.9.2.1
  
 25) NOTE: PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD
 NOT BE LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE
 COMPLETE FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY
 OF THE REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN
 KEYNOTES WILL MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
  
 27) NOTE: PLEASE CORRELATE ARCHITECTURAL PLANS WITH
 THAT OF THE ELECTRICAL PLANS FOR ALL ROOM LAYOUTS AND
 FOOT PRINTS OF ROOMS/BUILDING. PLEASE SEE THE MAIN
 ELECTRICAL ROOM FOR ONE EXAMPLE. PLEASE SEE THE FLOOR
 LAYOUTS DO NOT CORRELATE AND REVIEW FOR SOME ITEMS FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. PLEASE
 SEE THE ELECTRICAL PLANS DO NOT SHOW ANY ELECTRICAL
 ROOMS FOR THE TYPICAL LAYOUTS AND THE ELECTRICAL
 PANELS. PLEASE SEE NOT DOORS ARE BEING SHOWN TO ACCESS
 ANY PANELS? PLEASE SEE ARCHITECTURAL SHEETS AND
 CORRELATE.
 PLEASE SEE 240.24, 110.26 ETC
  
 28) NOTE: PLEASE SEE THE MAIN FLOOR AND TYPICAL FLOOR
 PLANS SHALL MEET A MINIMUM OF 1/8INCH SCALE. PLEASE
 SUBMIT FOR REVIEW AS MANY ITEMS ARE VERY SMALL FOR
 VERIFICATION.
 PLEASE SEE FBC ADMIN SECTION 106.1.2, 106..1.3.
  
 29) NOTE: PLEASE SEE PANEL MDP SHOWS THE MAIN OVER
 CURRENT DEVICE FOR PANEL R! AT 400AMPS, YET THIS PANEL
 R1 IS SHOWN AS 200AMP MLO?
 PLEASE SEE THERE ARE SEVERAL OTHER PANELS WHICH DO NOT
 CORRELATE WITH THE RISER OR ARE NOT SUBMITTED FOR PANEL
 SCHEDULES OR ARE LOCATED ON RISER DIAGRAM.
 PLEASE SEE SOME FOR EXAMPLE. PANEL RT, HT ETC. PLEASE
 CORRELATE ALL PANELS ON RISER, MDP AND PANEL SCHEDULES
 TO BE SUBMITTED.
 FBC ADMIN SECTION. 106.1.2, 106.3.5.1.2
 NEC 215.5, 408.4, 310.16, 240.4 ARE ONLY SOME SECTIONS
 WHICH CAN NOT BE VIEWED FOR CODE COMPLIANCE AS MANY OF
 THESE WERE NOT SUBMITTED ETC.
  
 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52
 FOR ITEMS REQUIRED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. PLEASE
 KNOW AT THIS TIME IT SEEMS THESE MICROWAVE UNITS ARE
 BEING PERMANENTLY INSTALLED AT AN UPPER LEVEL. PLEASE
 SEE SOME OF THE FOLLOWING COMMENTS WHICH MAY VERY WELL
 APPLY.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO THE HEIGHT OF
 THE MICROWAVE IN ACCESSIBLE UNITS.
  
 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16.
 PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE
 CIRCUITS.
 (IF APPLICABLE)
  
 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES
 LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE
 FED FROM THE LIGHTING CIRCUITS WHICH ARE NOT PERMITTED.
 PLEASE SEE 210.11C1, 220.16 AS NOTED IN NOTE #31 (WHERE
 APPLICABLE AS NOTE IN NOTE #30)
  
 33) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52 FOR 2FT
 OF WALL , KITCHEN AREA, KITCHEN WALL OVER 2FT, WITHIN
 6FT OF DOORS ETC.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED.
 PLEASE SEE MOST UNITS SEEM TO BE OK, HOWEVER THERE ARE
 SOME UNITS WHICH DO NOT HAVE ANY RECEPTS LOCATE DON
 WALLS. PLEASE KNOW IF THIS IS NOT A UNIT WITH PERMANENT
 COOKING WHICH IS NOT YET DETERMINED THEN, SPACING MAY
 FALL UNDER GUEST ROOMS/SUITES AND NOT DWELLING. 210.60
  
 34) NOTE: PLEASE SEE THE HEIGHTS FOR THE MICROWAVES IN
 ACCESSIBLE UNITS ARE AT 62INCHES, WHERE ARE THESE UNITS
 GOING TO BE MOUNTED? AND SHOW DETAIL.
 FBC CHAPTER 11, FHAR 24CFR100.205
  
 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
  
 36) NOTE: PLEASE CLARIFY THE ARC FAULT PROTECTION WHICH
 IS NOT CURRENTLY BEING SHOWN. PLEASE SEE NOTE #30 AND
 IF UNITS CONTAIN PERMANENT COOKING MOUNTED EQUIPMENT
 THEN THESE WILL BE REQUIRED FOR PROTECTION IN SLEEPING
 ROOMS. 210.12
  
 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE
 CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
 38) NOTE: PLEASE SEE THE LOAD ON R1 EXCEEDS THAT OF THE
 RATING OF THE PANELS(S). SHOWN AT 200 AMPS. 240, 408
 ETC.
  
 39) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT THE FIRE PUMP SERVICE.
 250.50
  
 40) NOTE: PLEASE SUBMIT A COMPLETED GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE PLANS DID NOT SHOW AS REQUIRED PER
 250.50. PLEASE SEE MISSING FOOTER STEEL.
 PLEASE ALSO SEE 250.104 FOR ANY WATER AND OTHER TYPES
 OF METAL PIPING. (SPRINKLER ETC)
  
 41) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT DETACHED BUILDINGS/STRUCTURES PER 250.32
  
 42) NOTE: PLEASE SEE MISSING PANEL SCHEDULE FOR PANEL
 "P".
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE
 VERIFIED FOR PANEL SCHEDULE.
 CONTINUOUS LOADS ETC.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 43) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS AND
 SUMMARY FOR ALL LOADS AND SHOW ALL CONTINUOUS/LARGEST
 MOTOR LOADS AT 125%.
 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC.
  
 44) NOTE: PLEASE SEE THAT ALL CIRCUITING AT THE POOL
 HOUSE STRUCTURE SHALL EITHER COME FROM PANEL P OR SHALL
 CONTAIN DISCONNECTING MEANS AND ALL SHALL BE GROUPED
 AND GROUNDED PER 225.31-225.39, 250.32.
  
 45) NOTE: PLEASE SEE SOME CIRCUITS ARE SHOWN FROM R
 PANEL(S).
 PLEASE ALSO CORRELATE ALL PLANS AND SHEETS AS THE PANEL
 P IS BEING SHOWN IN MULTIPLE LOCATIONS. ONE SHEET PANEL
 IS SHOWN IN ONE ROOM AND ANOTHER SHEET SHOWS THIS SAME
 PANEL LOCATED AT ANOTHER ROOM. PLEASE CORRELATE. FBC
 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION/CLARIFICATION.
  
 46) NOTE: PLEASE SEE ROOF TOP PLANS WHICH INDICATE A
 RTU HOWEVER NOT CIRCUITING IS BEING SHOWN ETC. PLEASE
 SEE 440.11 AND 210.63 FOR OTHER REQUIRED DISCONNECTS
 AND WP GFI REQUIRED.
  
 47) NOTE: PLEASE SEE NFPA-72 FOR REQUIREMENTS OF THE
 FACP CIRCUIT(S).
 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 4.4.1.4.2.2 CIRCUIT DISCONNECTING MEANS SHALL HAVE A
 RED MARKING SHALL BE ACCESSIBLE ONLY TO AUTHORIZED
 PERSONNEL, AND SHALL BE IDENTIFIED AS "FIRE ALARM
 CIRCUIT."
 4.4.1.4.2.3 THE LOCATION OF THE CIRCUIT DISCONNECTING
 MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM
 CONTROL UNIT
 PLEASE KNOW ANY NOTATION FOR THE REQUIRED LOCK OFF TYPE
 BREAKER SHALL STATE "ANY LOCK-OFF DEVICE SHALL HAVE THE
 HANDLE/LOCK AN INTEGRAL PART OF THE BREAKER" OR WORDS
 TO THAT AFFECT. PLEASE KNOW DEVICES SUCH AS THE
 SNAP/CLIP ON TYPE ARE NOT PERMITTED AS THEY ARE EASILY
 REMOVED OR FALL OFF WHEN A PANEL COVER IS REMOVED WHICH
 THEN NO LONGER PROVIDES THE NEEDED PROTECTION OF THE
 CIRCUITS(S).
  
  
 48) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS
 REQUIRED.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
 49) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD
 ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1,
 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL
 OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY
 FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE
 ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS.
  
 50) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES
 LOCATIONS OF SMOKE DETECTORS TO BE INSTALLED WITH
 MINIMUM CRITERIA. PLEASE SEE AREAS WHERE THERE ARE
 SLOPED CEILINGS AS SHOWN ON THE ARCHITECTURAL SHEETS,
 THE SD SHALL BE INSTALLED WITHIN 3FT OF THE PEAK OF
 THAT SLOPE. (LOUNGE) ETC OR WITHIN 12 INCHES OF THE
 HIGHEST POINT ON A FLAT CEILING. PLEASE NOTE THE
 REQUIREMENTS AS LISTED. (3FT FROM BATH ROOM AND KITCHEN
 DOORS/OPENINGS ETC. PLANS DO ALREADY CONTAIN A NOTE FOR
 THE SMOKE DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS.
 THIS COMMENT MAYBE EXPANDED UPON.
 PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION
 MISSING WHICH WILL REQUIRE ADDITIONAL.
  
 50) NOTE: PLEASE CLARIFY THE CIRCUIT ON M1 WHICH SHOWS
 A CIRCUIT TO THE FIRE PUMP CONTROLLER? PLEASE SEE THIS
 FPC IS BEING FED FROM A SEPARATE SERVICE AND SERVICE
 ENTRANCE WHICH MAY NOT CONTAIN CIRCUITS FROM OTHER
 SERVICE EQUIPMENT TO THE SAME EQUIPMENT.
 230
  
 51) NOTE: PLEASE SEE NOTE ON RISER WHICH STATES THE
 FIRE PUMP SHALL MEET THE LATEST EDITION OF THE NEC.
 PLEASE KNOW THE CODE IN GENERAL OR SECTIONS OF THE CODE
 SHALL NOT BE QUOTED ON PLANS IN LIEU OF THE REQUIRED
 INFORMATION, DETAILS OR DESIGN CRITERIA.
 PLEASE KNOW AS NOTED ABOVE WHERE REQUIRED CODES
 RELEVANT TO THIS PROJECT SHALL BE ON PLANS, THE STATE
 OF FLORIDA ADOPTED THE 2005 NEC /NFPA-70 ON DECEMBER
 8TH, 2006 WHICH WOULD BE "LATEST EDITION", HOWEVER THIS
 PROJECT AS IT WAS SUBMITTED FOR PERMITTING BEFORE SUCH
 DATE WILL BE UNDER THE PREVIOUS CODE AND NOT THE LATEST
 EDITION.
  
 52) NOTE: PLEASE PLACE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. THIS IS REQUIRED FOR ALL ENLARGED LAYOUT
 SHEETS AS WELL.
 FBC 106.1.2, 106.3.5.1.2
  
 53) NOTE: PLEASE SHOW AND COMPLETE LOAD CALCULATIONS
 FOR TRACK LIGHTING PER 220.12B
  
 54) NOTE: PLEASE SEE 240.4C WHICH REQUIRES ALL SERVICE
 ENTRANCE CONDUCTOR AMPERAGE FOR DEVICES RATED 800AMPS
 OR MORE TO MEET OR EXCEED THE RATED DEVICE. PLEASE SEE
 310.16, 110.14
  
 55) NOTE: PLEASE SEE SOME ROOMS ON PLANS ARE MISSING
 LIGHTING. PLEASE SEE EXAMPLE OF THE ELEVATOR MACHINE
 ROOM.
 PLEASE COMPLETE PLANS. LS 101 7.8, 7.9
 FBC ADMIN SECTION 106.3.5.1.2
  
 56) NOTE: PLEASE KNOW DOORS SHALL BE SHOWN FOR ALL
 ROOMS, MORE SPECIFICALLY THE MAIN ELECTRICAL ROOM(S),
 ELEVATOR ROOMS ETC. PLEASE KNOW THE LAYOUTS FROM THE
 ARCHITECTURAL SHEETS AND THE ELECTRICAL SHEETS DO NOT
 CORRELATE, THE DOOR SWINGS MAY BE AN ISSUE IF THE DOORS
 ARE ACTUALLY ON THE INSIDE AND LOCATED IN AN EGRESS
 CORRIDOR. PLEASE SEE FBC AND LS101 FOR DOOR SWINGS IN
 EGRESS PATHS.7.2.1.4 ETC
  
 57) NOTE: PLEASE SEE 210.8B3 FOR BRANCH CIRCUITS IN
 KITCHEN AREAS AND THE LIKE WHICH REQUIRES PROTECTION
 FOR ALL 15/20 AMP 120 CIRCUITS.
  
 58) NOTE: PLEASE SEE SITE PLAN SHEET SHOWS THE NOTES
 FOR THE MAIN ELECTRICAL ROOM SERVICE AND OTHER SITE
 ELECTRICAL, HOWEVER PLEASE SEE THE SERVICE FOR THE FIRE
 PUMP IS NOT SHOWN? PLEASE SEE RISER SHOWS THIS COMING
 FROM THE SAME TRANSFORMER.
 PLEASE SHOW. FBC 106.1.2 FOR ADDITIONAL INFORMATION
 REQUIRED.
  
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC,
 THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-07 11:11:522007-01-07 11:11:52
 REVIEW COMMENCED
2007-01-03 07:33:362007-01-03 07:33:36
 IN ELECTRIC FOR REVIEW