Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-01 06:58:03 
  
 BUILDING PLAN REVIEW
 PERMIT: 06111067
 ADD: 2437 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SPRINGHILL SUITES BY MARIOTT
 FIVE STORY/ 130 UNITS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4) WEST PALM BCH ADMINISTRATIVE CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7) W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8) PLEASE NOTE:
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) PFVS ARCHITECTURE PLANNING AND INTERIORS
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11) MISSING INFORMATION ON THE ARCHITECTS (PFVS)
 TITLEBLOCK,
 61G1-16.004 FL. ADMIN. CODE. PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 12) SHEET G.000 THIS SHEET INDICATES NIELSEN STRUCTURAL
 ENGINEERING
 AS ONE OF THE FIRMS WORKING ON THIS PROJECT BUT THEY
 ARE NOT NOTED ON
 THE STRUCTURAL SHEETS? 106.1.2*
  
 13) SHEET G-000
 13A) THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE
 I-B SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE
 SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES
 BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS,
 SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
 14) SHEET A-401, PLEASE PROVIDE THE ELEVATIONS, CHANGE
 IN GRADE FROM UNDER THE PORTICO TO THE LOBBY, (DROP OFF
 AREA) PLANS ARE NOT CLEAR AS TO IF THERE IS A CURB OR
 ALL AT GRADE LEVEL. 11-4.5.2 CHANGES IN LEVEL.
  
 15) SHEET A-401, THE FRONT ENTRY DOORS (VESTIBULE)
 APPEAR TO BE HORIZONTAL SLIDING DOORS, PLEASE PROVIDE
 INFORMATION FOR MANUAL LY OPERATED (BREAK AWAY) IF LOSS
 OF POWER. SECTION 1008.1.3.3.
  
 16) SHEET A-101:
 16A) PLANS INDICATE 2 - 5 STORY STAIRWELLS THE DOOR
 SCHEDULE DOESN'T INDICATE 1 1/2 HR PROTECTIVES. PLEASE
 INDICATE IN HRS AND IN MINUTES THE OPENING PROTECTIVE
 RATING.707.4/ TABLE 715.3.
  
 16B) FIRE PUMP ROOM 132 ALSO REQUIRES 2 HR RATED WALLS
 SEE NFPA 20:5.1.12.1.1. OPENING PROTECTIVE FOR DOOR 1
 1/2 HR .TABLE 715.3.
  
 16C) ROOM # 160 DOMESTIC WATER HEATER ROOM INDICATES A
 SHAFT BUT NO WALL RATINGS ARE PROVIDED. 707.4
  
 16D) ROOM 136C LAUNDRY TERMINATION ROOM, THE ROOM
 REQUIRES A 1 HR FIRE RATING SHEET A-401 ENLARGED PLAN
 IS MISSING RATED WALLS.707.13.4.
 707.13.2 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16E) ROOM 136C LAUNDRY ROOM TERMINATION ROOM DOOR
 REQUIRES 3/4HR RATING SEE DOOR SCHEDULETABLE
 715.3/.707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN
 ENCLOSED ROOM COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE TERMINATION ROOM SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. REFUSE
 CHUTES SHALL NOT TERMINATE IN AN INCINERATOR ROOM.
 REFUSE AND LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE 302.1.1 .
  
 16F) PLANS INDICATE THE USE OF BLOCK WALLS SEPERATING
 THE CORRIDORS FROM THE INDIVIDUAL SUITES SECTION 3A OR
 3B PLEASE PROVIDE THE STC RATING FOR WALLS.
 SEE A-401 ENLARGED PLAN. 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL.
  
 16G) LAUNDRY CHUTE:707.13.6 AUTOMATIC FIRE SPRINKLER
 SYSTEM.
 AN APPROVED AUTOMATIC FIRE SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.10.2 .
 903.2.10.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
  
 16H) THE PLANS (A-401 ENLARGED) ALSO INDICATE SUITES
 104 & 106, THERE IS NO WALL TYPE IDENTIFICATION.
 PROVIDE THE STC RATING BETWEEN ROOM.
 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 16I) THIS SAME SITUATION SHALL OCCUR BETWEEN SUITES
 BETWEEN FLOORS, SHOW COMPLIANCE WITH:
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 16J) ENLARGED PLAN A-401 ELECTRIC ROOM 147 INDICATES
 THE USE OF SPANDRIAL GLASS THIS LOCATION? 106.1.2.
 ADDITIONAL INFORMATION.
  
 16K) PLEASE PROVIDE LAUNDRY SHUTE DETAILS: 707.13.2
 MATERIALS.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL BE CONSTRUCTED OF MATERIALS AS PERMITTED BY THE
 BUILDING TYPE OF CONSTRUCTION.
  
 16L) BOTH A-101 & A-401 SHOW A VENDING ROOM # 157 AND
 NO ACCESS. 106.1.2* ADDITIONAL INFO REQUIRED.
  
 16M) PLEASE PROVIDE CODE COMPLIANCE FOR HEADROOM
 CLEARENCE UNDER STAIRWELLS, 11-4.4.2 HEADROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AISLES, OR OTHER
 CIRCULATION SPACES SHALL HAVE 80 INCHES (2030 MM)
 MINIMUM CLEAR HEAD ROOM [SEE FIGURE 11-8 (A)]. IF
 VERTICAL CLEARANCE OF AN AREA ADJOINING AN ACCESSIBLE
 ROUTE IS REDUCED TO LESS THAN 80 INCHES (2032 MM)
 (NOMINAL DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY-IMPAIRED PERSONS SHALL BE PROVIDED [SEE FIGURE
 11-8 (C-1)].
  
 16N) SHEET A-101- A-105 ALL CORRIDORS WITH OCCUPANT
 LOAD GREATER THAN 10 (R-1) REQUIRES 1-HR RATED
 CORRIDORS WITH OPENING PROTECTIVES. PROVIDE
 DOOR IDENTIFICATION AND FIRE RATING. SEE SECTION
 715.3.
  
  
 16O) STAIRWELLS ARE MISSING STANDPIPES,905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1. THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 MM)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2. THE HIGHEST FLOOR IS MORE THAN THREE STORIES ABOVE
 GRADE.
  
 16P) PLEASE PROVIDE INFORMATION FOR ELEVATOR CARS TO
 ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
  
 16R) PLEASE PROVIDE INFORMATION FOR THE FIRE PUMP, SIZE
 OF PUMP, TYPE OF PUMP FUEL LOADS IF NOT ELECTRIC.
  
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 176Q) STAIRWELL# 2 IS MISSING THE STANDPIPE:
 905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1. THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 MM)
 ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2. THE HIGHEST FLOOR IS MORE THAN THREE STORIES ABOVE
 GRADE
  
 17) SHEET A-402:
 17A) DETAIL# 7 LAUNDRY ACCESS ROOM INDICATES THE USE OF
 A 2 HR RATED WALL BUT NO SOUND TRANSMITION RATING IS
 PROVIDED? 1207.2.
  
 17B) SHEET A-402 DETAIL# 7 ALSO INDICATES A RECESSED
 FIRE EXTINGUISHER CABINET, HOW IS THE 2 HR RATING BEING
 MAINTAINED? 106.1.2*
  
 17C) SHEET A-402 DETAIL# 7 LAUNDRY ROOM ACCESS DOOR,
 THE SCHEDULE NEEDS TO BE IN MINUTES AND HRS. TABLE
 715.3.
  
 17D) SHEET A-402 DETAIL# 1, ELEVATOR LOBBY DOORS ARE
 NOT IDENTIFIED, FLOORS 2-5 INDICATE AS DOOR *34, DOOR
 SCHEDULE INDICATES "C" LABEL REQUIRES
 RATING ACCORDING TO TABLE 715.3. THESE DOORS ALSO
 INDICATE HOLD OPEN DEVICES, PLANS DO NOT INDICATE IF
 TIED TO SMOKE ALARM, SPRINKLER, ETC
  
 17E) SHEET A-402 DETAILS 3,4& 5 ALL INDICATE SHAFTS
 WITH WALLS NOT RATED (AO). 707.4.
  
 18) A-201- A-202 ELEVATIONS INDICATE THE USE OF EFIS
 TRIM ABOVE 40' ABOVE GRADE. BUILDING TYPE I-B.SHEETS
 A-301, A-302 & A-303.
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE STORIES OR 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE, EXTERIOR WALL COVERINGS
 SHALL BE PERMITTED TO BE CONSTRUCTED OF WOOD WHERE
 PERMITTED BY SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE EXTERIOR WALL
 COVERINGS, OTHER THAN FIRE-RETARDANT-TREATED WOOD
 COMPLYING WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10 PERCENT OF AN
 EXTERIOR WALL SURFACE AREA WHERE THE FIRE SEPARATION
 DISTANCE IS 5 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS
  
 19) A-303 PARAPET DETAIL DOESN'T INDICATE ANY FASTENING
 SYSTEM NOR STRUCTURAL INFORMATION NOR REFRENCE ANY
 STRUCTURAL SHEETS? 106.1.2 ADD INFO REQUIRED.
  
 20) A-501 & A-502, PARAPET DETAIL DOESN'T INDICATE ANY
 FASTENING SYSTEM NOR STRUCTURAL INFORMATION NOR
 REFRENCE ANY STRUCTURAL SHEETS? 106.1.2 ADD INFO
 REQUIRED.
  
 21) SHEET A-106 ROOF PLAN LEFT SIDE OF THE SHEET
 INDICATES A DOORWAY ONTO THE FLAT ROOF, SHEET A-105
 STORAGE ROOM BELOW DOESN'T INDICATE STAIRS TO THE ROOF
 LEVEL.SHEET A-105,NOTE 6 INDICATES A STEEL LADDER.
 1009.12 ACCESS TO ROOF.
 BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE
 WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED
 WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE
 MARKED AT STREET AND FLOOR LEVELS WITH A SIGN
 INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS
 ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES,
 STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR
 OCCUPANCY.
 CODE COMMENTARY: IN BUILDINGS FOUR OR MORE STORIES
 HIGH, ROOF THAT ARE NOT USED FOR HABITABLE PURPOSES
 MUST BE MADE ACCESSIBLE BY CONVENTIONALSTAIRWAYS. TWO
 REASONS FOR THIS ARE ACCESS FOR ROOF OR EQUIPMENT
 REPAIR AND FIRE DEPARTMENT ACCESS DURING A FIRE EVENT.
  
 22) A-105 THIS SAME NOTE INDICATES 2'X2' ACCESS PANELS
 2ND, 3RD & 4TH FLOORS, FOR WHAT PURPOSE? 106.1.2
 ADDITIONAL INFO REQUIRED.
  
 23) SHEET A-106 ROOF DRAINS AND OVERFLOW DRAINS: WHERE
 IS THE OUTLET FOR THE OVERFLOW ROOF DRAINS? 106.1.2.ADD
 INFO.
  
 24) A-402 WATER HEATER ROOMS VS THE END ELEVATIONS
 A-201 & A-202 THE END VIEWS INDICATE (2) LOUVERS ONE
 WILL END UP IN THE 2 HR FIRE RATED STAIRWAY,
 ARE THESE FOR THE GAS FIRED WATERHEATERS? IF SO HOW
 WILL THE LOUVER LOCATED IN THE STAIRWELL BE SEPERATED
 FROM THE STAIRWELL?
  
 25) A-604 & A-605 BOTH INDICATE THE USE OF WOOD BUCKS
 FOR WINDOWS AND DOORS. PLANS DO NOT INDICATE HOW THE
 BUCKS ARE TO BE FASTENED,
 1714.5.4.1 ANCHORING REQUIREMENTS.
 WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN
 ACCORDANCE WITH THE PUBLISHED MANUFACTURER?S
 RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE
 SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED FOR
 SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1 1
 / 2 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 INCHES (38 MM)
 OR GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK.
  
 26) SHEET A-606 PUBLIC RESTROOMS INDICATE THE USE OF
 V.W.C. ? 1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 27) A-701 THE STAIRWELL PLAN DOESN'T INDICATE THE
 HANDRAIL EXTENDING PAST THE FIRST RISER ON THE FIRST
 FLOOR.
 11-4.9.4(2) AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE
 TO SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM
 THE BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL
 BE HORIZONTAL [SEE FIGURE 11-19 (C) AND FIGURE 11-19
 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION
 11-4.4 .
  
 28A) SHEET A-702 DETAIL# 1,PLEASE PROVIDE VENTING FOR
 ELEVATORS:
 3004.1 VENTS REQUIRED.
 HOISTWAYS OF ELEVATORS AND DUMBWAITERS PENETRATING MORE
 THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE
 TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO
 THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE
 OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO
 PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR
 MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION HAVING NOT
 LESS THAN THE FIRE PROTECTION RATING REQUIRED FOR THE
 HOISTWAY. HOLES IN THE MACHINE ROOM FLOORS FOR THE
 PASSAGE OF ROPES, CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO PROVIDE GREATER
 THAN 2 INCHES (51 MM) OF CLEARANCE ON ALL SIDES.
  
 28B) A-702 PLANS DO NOT INDICATE REQUIREMENTS FOR
 BRAILLE CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5
 RAISED AND BRAILLE CHARACTERS ON HOISTWAY ENTRANCES.
 ALL ELEVATOR HOIST WAY ENTRANCES SHALL HAVE RAISED AND
 BRAILLE FLOOR DESIGNATIONS PROVIDED ON BOTH JAMBS. THE
 CENTERLINE OF THE CHARACTERS SHALL BE 60 INCHES (1525
 MM) ABOVE FINISH FLOOR. SUCH CHARACTERS SHALL BE 2
 INCHES (50 MM) HIGH AND SHALL COMPLY WITH SECTION
 11-4.30.4 . PERMANENTLY APPLIED PLATES ARE ACCEPTABLE
 IF THEY ARE PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE
 11-20 ).
  
 29A) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
  
 29B) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 29C) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.]
  
 29D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS-STOREFRONT,
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN, EPDM ROOFING
 SLOPED:UNDERLAYMENTS, METAL ROOFS
 G) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___ THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 31) S-101
 31A) PLANS INDICATE PLANS WERE CALCULATED TO ASCE 7-98
 SEE CHAPTER35 REFERENCE STANDARDS FOR CORRECTION.
  
 32) PLEASE PROVIDE POSITIVE AND NEGATIVE PRESSURES FOR
 THE INTERIOR ZONES AND END ZONES FOR OPENING SIZES 10'
 -100'
 WITH HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS.
 1606.2D.
  
 33) ASEPERATE PERMIT IS REQUIRED FOR THE POOL, POOL
 EQUIPMENT BUILDING , POOL FENCING AND SIGNAGE.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  