Plan Review Notes
Plan Review Notes For Permit 06111064
Permit Number 06111064
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-30 15:40:29DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 PERMIT APPLICATION.
  
 3) INDICATE THE SQFT AREA OF SLOPED ROOF AND FLAT ROOF
 SEPARATELY IN ORDER FOR THE CONSTRUCTION VALUE TO BE
 ACCURATELY CALCULATED.
  
 4) THE MAXIMUM DESIGN PRESSURE SPECIFIED IN THE NOA FOR
 THE POLYGLASS MODIFIED SYSTEM IS -60 PSF. THIS PRESSURE
 IS NOT ADEQUATE FOR THE CORNER AREAS, WHICH WILL
 REQUIRE ENHANCED FASTENING. LIMITATION #7 ALLOWS FOR
 THIS, BUT REQUIRES THE RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING TO BE PREPARED, SIGNED AND SEALED BY
 A FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED
 ROOFING CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  