| Plan Review Notes For Permit 06111064 |
| Permit Number |
06111064 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-30 15:40:29 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE | | | PERMIT APPLICATION. | | | | | | 3) INDICATE THE SQFT AREA OF SLOPED ROOF AND FLAT ROOF | | | SEPARATELY IN ORDER FOR THE CONSTRUCTION VALUE TO BE | | | ACCURATELY CALCULATED. | | | | | | 4) THE MAXIMUM DESIGN PRESSURE SPECIFIED IN THE NOA FOR | | | THE POLYGLASS MODIFIED SYSTEM IS -60 PSF. THIS PRESSURE | | | IS NOT ADEQUATE FOR THE CORNER AREAS, WHICH WILL | | | REQUIRE ENHANCED FASTENING. LIMITATION #7 ALLOWS FOR | | | THIS, BUT REQUIRES THE RAS 117 CALCULATIONS FOR | | | ENHANCED FASTENING TO BE PREPARED, SIGNED AND SEALED BY | | | A FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED | | | ROOFING CONSULTANT. SUBMIT SIGNED AND SEALED RAS 117 | | | CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|