| 2007-04-26 14:04:07 | DENIED 3RD TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 1. THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM |
| | DOES NOT RELECT THE FLOOR PLAN. PER FBC-2004 SECTION |
| | 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED. PLEASE REFERENCE THE SANITARY |
| | ISOMETRIC RISER DIAGRAM ATTACHED TO THE PLUMBING |
| | COMMENTS THAT REFLECTS THE FLOOR PLAN AND IS CODE |
| | COMPLIANT. |
| | |
| | 2. IF IT IS THE INTENT TO SUBMIT AN ISOMETRIC WATER |
| | RISER DIAGRAM (NOT REQUIRED FOR RESIDENTIAL ONE AND |
| | TWO-FAMILY) PLEASE INDICATE THE WATER HAMMER ARRESTOR |
| | FOR THE WASHING MACHINE PER FBC-2004 PLUMBING 604.9 |
| | WATER HAMMER ARRESTORS REQUIRED ON QUICK CLOSING |
| | VALVES. |
| | |
| | 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |