| 2007-03-20 11:28:40 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK IN THE | | | EXTERIOR WALLS. | | | | | | 3) SUBMIT PRODUCT APPROVALS FOR THE STORM PANELS THAT | | | ARE REQUIRED TO PROTECT THE NON-IMPACT RATED EXTERIOR | | | GLAZING. SPECIFY WHICH OPENINGS WILL BE SHUTTERED. | | | SPECIFY THE TYPE OFFASTENERS,FASTENER SPACING, | | | PANEL SPANS, MOUNT TYPE, ETC. THAT WILL BE USED. CIRCLE | | | THE APPROPRIATE ITEMS ON THE PRODUCT APPROVAL OR SUBMIT | | | AN INSTALLATION SCHEDULE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|