| 2007-02-06 12:15:54 | DENIED BY BUILDING |
| | |
| | 1) PLANS DO NOT REFLECT THE SCOPE OF WORK. SEE FBC * |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2) SPECIFY THELOCATIONS, TYPES AND SIZES OF THE |
| | EXTERIOR WINDOWS THAT ARE BEING REPLACED ON THE PLANS. |
| | |
| | 3) SPECIFY THE LOCATIONS, TYPES AND SIZES OF THE |
| | EXTERIOR DOORS THAT ARE BEING REPLACE ON THE PLANS. |
| | |
| | 4) SUBMIT PRODUCT APPROVALS FOR EACH TYPE OF WINDOW AND |
| | DOOR THAT WILL BE INSTALLED. |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 6)SPECIFY ON THE PLANS THE IF ALL OF THE DRY WALL IS |
| | BEING REPLACED. IF ONLY A PORTION IS BEING REPLACED, |
| | THEN SPECIFY THE AREAS ON THE PLANS. SPECIFY IF THE |
| | CEILINGS, WALLS ONLY OR BOTH ARE BEING REPLACED. |
| | |
| | 7) SPECIFY IF THE WALL AND CEILING INSULATION AS LISTED |
| | ON THE ENERGY CALCULATION FORM IS EXISTING OR IS BEING |
| | INSTALLED. |
| | |
| | 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. |
| | FORM. |
| | |
| | 9)IDENTIFY THE PROJECT IN THE TITLE BLOCK OF THE |
| | PLANS. (TYPICALLY THE JOB NAME AND ADDRESS.) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |