Plan Review Notes
Plan Review Notes For Permit 06111013
Permit Number 06111013
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-06 12:15:54DENIED BY BUILDING
  
 1) PLANS DO NOT REFLECT THE SCOPE OF WORK. SEE FBC *
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) SPECIFY THELOCATIONS, TYPES AND SIZES OF THE
 EXTERIOR WINDOWS THAT ARE BEING REPLACED ON THE PLANS.
  
 3) SPECIFY THE LOCATIONS, TYPES AND SIZES OF THE
 EXTERIOR DOORS THAT ARE BEING REPLACE ON THE PLANS.
  
 4) SUBMIT PRODUCT APPROVALS FOR EACH TYPE OF WINDOW AND
 DOOR THAT WILL BE INSTALLED.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 6)SPECIFY ON THE PLANS THE IF ALL OF THE DRY WALL IS
 BEING REPLACED. IF ONLY A PORTION IS BEING REPLACED,
 THEN SPECIFY THE AREAS ON THE PLANS. SPECIFY IF THE
 CEILINGS, WALLS ONLY OR BOTH ARE BEING REPLACED.
  
 7) SPECIFY IF THE WALL AND CEILING INSULATION AS LISTED
 ON THE ENERGY CALCULATION FORM IS EXISTING OR IS BEING
 INSTALLED.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC.
 FORM.
  
 9)IDENTIFY THE PROJECT IN THE TITLE BLOCK OF THE
 PLANS. (TYPICALLY THE JOB NAME AND ADDRESS.)
  