Plan Review Notes
Plan Review Notes For Permit 06110868
Permit Number 06110868
Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-27 16:03:00THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS
 COMMENTS AND RESPONSES FOR THE PURPOSE OF CONTINUITY:
  
 1. OK
  
 2. OK EXCEPT: PLEASE SHOW MEANS OF CONDENSATE DISPOSAL
 THAT IS IN COMPLIANCE WITH FBC,M SEC. 307, INCLUDING
 307.2.3, WHICH REQUIRES AUXILIARY OR SECONDARY DRAIN
 PROTECTION. CONDENSATE DISPOSAL SHALL ALSO COMPLY WITH
 FBC 1503.6.
  
 *NEW COMMENTS*:
  
 1.PLEASE PROVIDE STRUCTURAL DETAIL FOR ROOF CURB TO
 STRUCTURE ATTACHMENT AND EQUIPMENT TO CURB ATTACHMENT
 PER FBC,M 301.13. PROVIDE WIND LOAD CALCULATIONS
 SHOWING ALL ELEMENTS TO BE DESIGNED TO THE 140MPH WIND
 ZONE PER FBC CH.16.
  
 2. PLEASE PROVIDE A PERMANENT MEANS OF ACCESS TO THE
 ROOFTOP A/C UNIT PER FBC,M 306.5. THIS MAY BE ACHIEVED
 BY A LADDER PERMANENTLY AFFIXED TO THE EXTERIOR OF THE
 BUILDING, THROUGH A SCUTTLE AT THE ROOF WITH A
 PERMANENTLY AFFIXED LADDER WITHIN THE ELEVATOR MACHINE
 ROOM OR BY ANY OTHER MEANS APPROVED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  
 IF YOU HAVE ANY QUESTION, PLEASE FEEL FREE TO CONTACT
 ME.
  