Plan Review Notes
Plan Review Notes For Permit 06110868
Permit Number 06110868
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-04-16 17:18:34*****UNSAT*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR
 THE VICINITY OF THE STRUCTURE (INCLUDING FIRE
 DAPARTMENT CONNECTIONS, FIRE HYDRANTS, AND FIRE LANES).
 ADD COMMENT TO AN APPROPIATEPLAN SHEET
  
 3.WHERE THE BUILDING IS PROTECTED BY FIRE PROTECTION
 SYSTEMS, SYSTEMS SHALL REMAIN OPERATIONAL AT ALL TIMES
 DURING THE SCOPE OF WORK.WPBFR SHALL BE NOTIFIED
 IF/WHEN FIRE PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT
 IS RETURNED TO SERVICE DUE TO THE SCOPE OF THE WORK.
 ADD COMMENT TO AN APPROPIATE PLAN SHEET
  
 6.DOES THE PROPOSED PEDESTRIAN BRIDGE PLANNED TO
 PROVIDE ANY EXITING FROM THE BUILDING?IF EXITING IS
 PLANNED, PROVIDE EXIT SIGN AND EMERGENCY LIGHTING. EXIT
 LIGHTS WERE NOTED AS PER YOUR RESPONSE LETTER, HOWEVER
 BETTER CLARITY IS NEEDED TO VERIFY THE LOCATION OF
 EMERGENCY LIGHTING ( AHA DRAWINGS?).
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED ON
 THE PLANS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW