| 2007-04-10 14:54:40 | PERMIT: 06110868 |
| | ADD: 530 HIBISCUS ST |
| | CONT: CENTEX CONSTRUCTION |
| | TEL: (561)478-0381 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)SHEET A020NT CODE TOWER COMPLIANCE, |
| | (2)2ND REQUEST, THE PLANS INDICATE MINIMUM CONSTRUCTION |
| | TYPE: TYPE !-B FOR B-BLOCK PARKING GARAGE. |
| | PLEASE TAKE NOTE THAT THE RETAIL STORES OF "B" BLOCK |
| | AND THE "B" BLOCK |
| | PARKING GARAGE ARE CONSIDERED "ONE" SINGLE BUILDING. |
| | WHEN BUILT THE RETAIL |
| | SHOPS CAME IN UNDER ONE PERMIT AND THE PARKING GARAGE |
| | BEING AN ADDITION TO |
| | THE BASE BUILDING UNDER A SECOND PERMIT. THE KEY ISSUE |
| | ONE BUILDING VERSES |
| | TWO BUILDINGS IS WHERE THE ADDITION ADJOINS TO THE BASE |
| | BUILDING. |
| | THE CONNECTION BEING WIDER THAN 30 FEETMAKES THIS |
| | ONE BUILDING, SEE THE DEFINITION |
| | OF WALKWAY COVERED. |
| | PLEASE PROVIDE THE SQ. FOOTAGE FOR BOTH THE |
| | PARKING GARAGE AND THE RETAIL STORES |
| | (FOOTPRINT) THEN THE MINIMUM CONSTRUCTION TYPE WILL |
| | TRUELY BE ABLE TO BE DETERMINED. |
| | TABLE 503. |
| | PLEASE REVISE THE DEESCRIPTION OF WORK ON THE |
| | PERMIT |
| | APPLICATION O REFLECT THIS IS MORE THAN AN ADDITION TO |
| | JUST "B" PARKING FACILITY. |
| | THE ELIMINATION OF THE CANOPY DOES NOT ELIMINATE THIS |
| | ISSUE!!!!!! |
| | |
| | 4 &5) COMPLIED. |
| | |
| | 6) 2ND REQUEST, WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7 & 8) COMPLIED. |
| | |
| | 9A)SHEET A0.20NT INDICATES THE PROPERTY LINE TO BE |
| | 9'-11" FROM THE BUILDING NOT OVER THE 10'-0" FOR |
| | UNLIMITED OPENINGS AS THE REPLY COMMENT INDICATES. |
| | TABLE 704.3 FOOTNOTE "C". |
| | THE PLACEMENT OF THE NEW PROPERTY LINE HAS CREATED A |
| | CODE VIOLATION . |
| | |
| | 9B) COMPLIED. |
| | |
| | 9C)(1) 2ND REQUEST, SHEET A-5.91NT ADDED THE ACCESSIBLE |
| | PARKING FOR THE FIRST FLOOR, BUT THERE IS NOW A NEW |
| | ISSUE WITH THE ONE DISSABLED PARKING SPACE IS FORCED TO |
| | WHEEL BEHIND THE FIRST NEWLY CREATED ACCESSIBLE SPACE. |
| | 11-4.6.2(1) ACCESSIBLE ROUTE NO LESS THAN 44" SO THAT |
| | USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND |
| | PARKED CARS. |
| | 11-4.1.2(5) (B) VAN ACCESIBLE |
| | 11-4.6.5 VERTICAL CLEARENCE |
| | 11-4.6.2 LOCATION, SHORTEST ROUTE. |
| | |
| | 9C)(2)SHEET A-5.93 NOW INDICATES AN ACCESSIBLE AISLE |
| | BUT THERE IS AN EXTERIOR STAIR IN THE ACCESSIBLE AISLE. |
| | PLANS DO NOT INDICATE ANY BARRIER COMPLYING WITH |
| | 11-4.4.2 ALSO SEE FIGURE 8-C1. |
| | |
| | 10) SHEET S0.02 DOES NOW HAVE THE POSITIVE AND NEGATIVE |
| | PRESSURES FOR LESS THAN 10SQ. FT. AND FOR GREATER THAN |
| | 500 SQ. FT. PLEASE PROVIDE A BREAK DOWN ON OPENING |
| | SIZES 20 SQ FT,50 SQ FT AND 100 SQ FT. |
| | |
| | 11)2ND REQUEST,A5.92NT ALSO INDICATES THE USE OF |
| | PRECAST CONCRETE CROWN MOLDS PLEASE PROVIDE THE |
| | ATTACHMENT METHOD. SEE 1406.2.2. WHAT I'M LOOKING FOR |
| | IS TYPE OF FASTENER, SPACING AND LOADS TO BE RESISTED |
| | AND THE SAFETY FACTOR. |
| | |
| | 12)2ND REQUEST, PLEASE PROVIDE ADDITIONAL INFORMATION |
| | FOR THE NEW EXTERIOR STAIRS THAT LEAD TO THE ELEVATOR |
| | MACHINE ROOM AT THE TOP OF THE PARKING GARAGE. THE |
| | PLANS GIVE A PICTORIAL VIEW OF HOW THEY ARE TO APPEAR |
| | BUT THERE IS NO INFORMATION AS TO BUILD THEM. THEY ALSO |
| | ARE LACKING INFORMATION ON THE STRUCTURAL SHEETS, NO |
| | DIMENSIONS ON RISER HEIGHT, TREADS, LANDINGS NOR |
| | HANDRAIL OR GAURDRAILS, PLAN DO NOT PROVIDE ATTACHMENT |
| | CONNECTIONS WHAT CARRIES THE LANDINGS NOR COLUMN SIZES |
| | OR BASE PLATE AND ANCHORAGE.106.1.2 ADDITIONAL |
| | INFORMATION REQUIRED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14A) COMPLIED. |
| | |
| | 14B-14D) THE VARIOUS COMMENTS HAVE NOT BEEN ADDRESSED |
| | AND BY PULLING THE SHEET A5.81NT THE COMMENTS DO NOT GO |
| | AWAY. THE SUBMITTAL SHEET DATED MARCH 07/ 07 STILL |
| | INDICATES THE CANOPY WORK AS PART OF THIS PERMIT |
| | PACKAGE. |
| | |
| | 14B) DETAIL# 2 INDICATES A SECTION OR DETAIL#(4) IS |
| | THIS AREA A ENCLOSED PART OF THE BUILDING OR IS THIS |
| | AREA A OPEN COURTYARD? |
| | |
| | 14C) THE DETAIL# 5 INDICATES THE FRAMING MEMBERS |
| | REQUIRED FOR THE TRANSLUCENT POLYCARBONATE ROOF PANELS |
| | (NOA 05-11207.01), THIS DETAIL |
| | DOES NOT MATCH THE FRAMING MEMBERS OF HOW THIS SYSTEM |
| | WAS TESTED NOR SPANS WHICH THE SYSTEM WAS TESTED. THE |
| | SECOND ISSUE WITH THIS DETAIL IS NOTE# 3 INSTEAD OF |
| | USING ALUMINIUM FRAMING, HOW THE SYSTEM WAS TESTED |
| | THERE IS AN ALTERNATE FOR STEEL FRAMING IN THE PLANS |
| | THAT DOESN'T SHOW IN THE PRODUCT APPROVAL. PROVIDE |
| | FURTHER INFORMATION FOR RATIONAL ANYLSIS OR |
| | CALCULATIONS? |
| | |
| | 14D) THENOA SUPPLIED IS BASICALLY THE FRAMEWORK FOR A |
| | SKYLIGHT, THE DESIGNER OF RECORD HASN'T PROVIDED HOW |
| | THIS UNIT IS TO BE ATTACHED TO EITHER |
| | THE THE EXISTING WALLS OR HOW THE HORIZONTAL AND |
| | VERTICAL FRAMING MEMBERS ARE TO BE ATTACHEDOR THE |
| | BOTTOM PLATE TO THE ALUMINIUM COLUMNS NOR |
| | THE BASE PLATE TO CONCRETE DECK? CONTINIOUS LOAD PATH, |
| | MOMENT OF OVERTURNING, MAIN WIND FORCE RESISTING |
| | SYSTEM. |
| | |
| | 15) COMPLIED |
| | |
| | 16) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |