| 2007-01-17 18:39:24 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT A5.81NT DETAIL 2 REFERS TO DETAIL 6, AND DETAIL |
| | 3 REFERS TO DETAIL 8. DETAILS 6 & 8 HAVE NOT BEEN |
| | SUBMITTED. PLEASE CLARIFY.SECTION 106.1.1. |
| | |
| | 2. SHT P1.01NT SUBMIT CALCULATIONS FOR THE STORM |
| | GUTTERS. SHOW THE SQUARE FOOTAGE AREA PLUS 1/2 THE AREA |
| | OF ALL VERTICAL WALLS INCLUDING PARAPETS. INDICATE |
| | TOTAL SQUARE FOOTAGE BEING DRAINED.SECTION 1106WITH |
| | ALL SUBSECTIONS. INDICATE THE SIZE OF THE GUTTERS PER |
| | TABLE 1106.6. SHOW THE HIGH POINTS OF THE GUTTERS AND |
| | INDICATE THE SLOPE OF THE GUTTERS. |
| | |
| | 3. SHOW THE SIZE OF THE RWL'S THAT THE CANOPY DRAIN |
| | WILL BE CONNECTING TO. SUBMIT INFORMATION ON THE AMOUNT |
| | OF EXISTING SQUARE FOOTAGE DRAINING THROUGH THE |
| | EXISTING RWL'S. INDICATE THE TOTAL AMOUNT DRAINING |
| | THROUGH OUT THE EXISTING BUILDING STORM DRAIN AND THE |
| | TOTAL WITH THE ADDED SF LOAD AS WELL AS THE PIPE SIZE |
| | OF THE BUILDING STORM DRAIN. SECTION 106.1.1 & TABLE |
| | 1106.3. |
| | |
| | 4. SUBMIT EXTERIOR ELEVATIONS OF THE WALLS FOR THE |
| | BUILDING AND THE PARKING GARAGE TO VERIFY VERTICAL |
| | CONTRIBUTION. INDICATE HEIGHT OF THE WALLS AND INDICATE |
| | THE HEIGHT OF THE CANOPY SECTIONS. SECTION 106.1.2. |
| | |
| | 5. SHT P1.01NT NEW ROOF DRAINAGE PIPING IS SHOWN AS |
| | S=.02 & S=.01. HORIZONTAL DRAINAGE PIPING SHALL BE |
| | INSTALLED IN UNIFORM ALIGNMENT AND UNIFORM SLOPE. |
| | PLEASE INDICATE ON PLANS. SECTION 704.1. |
| | |