Plan Review Notes
Plan Review Notes For Permit 06110868
Permit Number 06110868
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-17 18:39:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A5.81NT DETAIL 2 REFERS TO DETAIL 6, AND DETAIL
 3 REFERS TO DETAIL 8. DETAILS 6 & 8 HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY.SECTION 106.1.1.
  
 2. SHT P1.01NT SUBMIT CALCULATIONS FOR THE STORM
 GUTTERS. SHOW THE SQUARE FOOTAGE AREA PLUS 1/2 THE AREA
 OF ALL VERTICAL WALLS INCLUDING PARAPETS. INDICATE
 TOTAL SQUARE FOOTAGE BEING DRAINED.SECTION 1106WITH
 ALL SUBSECTIONS. INDICATE THE SIZE OF THE GUTTERS PER
 TABLE 1106.6. SHOW THE HIGH POINTS OF THE GUTTERS AND
 INDICATE THE SLOPE OF THE GUTTERS.
  
 3. SHOW THE SIZE OF THE RWL'S THAT THE CANOPY DRAIN
 WILL BE CONNECTING TO. SUBMIT INFORMATION ON THE AMOUNT
 OF EXISTING SQUARE FOOTAGE DRAINING THROUGH THE
 EXISTING RWL'S. INDICATE THE TOTAL AMOUNT DRAINING
 THROUGH OUT THE EXISTING BUILDING STORM DRAIN AND THE
 TOTAL WITH THE ADDED SF LOAD AS WELL AS THE PIPE SIZE
 OF THE BUILDING STORM DRAIN. SECTION 106.1.1 & TABLE
 1106.3.
  
 4. SUBMIT EXTERIOR ELEVATIONS OF THE WALLS FOR THE
 BUILDING AND THE PARKING GARAGE TO VERIFY VERTICAL
 CONTRIBUTION. INDICATE HEIGHT OF THE WALLS AND INDICATE
 THE HEIGHT OF THE CANOPY SECTIONS. SECTION 106.1.2.
  
 5. SHT P1.01NT NEW ROOF DRAINAGE PIPING IS SHOWN AS
 S=.02 & S=.01. HORIZONTAL DRAINAGE PIPING SHALL BE
 INSTALLED IN UNIFORM ALIGNMENT AND UNIFORM SLOPE.
 PLEASE INDICATE ON PLANS. SECTION 704.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]