Plan Review Notes
Plan Review Notes For Permit 06110868
Permit Number 06110868
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-17 10:27:41DENIED:
 1.PLAN SHEET H1.01 - THE 10" X 8" TRANSFER DUCT FROM
 THE ELEC ROOM, PLEASE CLARIFY IF THIS IS A WALKWAY,
 BALCONY, ETC.PER 2004 FMC 401.5 OUTDOOR AIR EXHAUST &
 INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 10 FT
 FROM LOT LINES OR BUILDINGS ON THE SAME LOT.
  
 2.PLEASE INDICATE IF THE CONDENSATE FROM PTAC UNITS
 TO VESTIBULE 100 & 400 WILL CREATE A NUISANCE OR SLIP
 HAZARD WHERE IT IS LOCATED.
  