| Date |
Text |
| 2007-02-09 13:13:14 | *****DENIED***** |
| | |
| | |
| | 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE |
| | SCOPE OF THE WORK WILL BE CONDUCTED SHALL BE IN THE |
| | TITLE BLODK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR |
| | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE |
| | DAPARTMENT CONNECTIONS, FIRE HYDRANTS, AND FIRE |
| | LANES). |
| | |
| | 3.WHERE THE BUILDING IS PROTECTED BY FIRE PROTECTION |
| | SYSTEMS, SYSTEMS SHALL REMAIN OPERATIONAL AT ALL TIMES |
| | DURING THE SCOPE OF WORK.WPBFR SHALL BE NOTIFIED |
| | IF/WHEN FIRE PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT |
| | IS RETURNED TO SERVICE DUE TO THE SCOPE OF THE WORK. |
| | |
| | 4.ON SHEETS FA0.01 AND FP0.01NT CORRECT VERBAGE FOR |
| | FIRE PROTECTION NOTES AS FOLLOWS:NFPA 1 2003, THE |
| | UNIFORM FIRE CODE; NFPA 14 2003 EDITION; NFPA 20 1999 |
| | EDITION; NFPA 101 2003 EDITION (INCLUDING CHAPTER 11- |
| | HIGH RISE BUILDINGS) THE LIFE SAFETY CODE; FLORIDA FIRE |
| | PREVENTION CODE 2004 EDITION. |
| | |
| | 5.PLEASE EXPLAIN WHY THE DOORS AS SEEN ON SHEETS |
| | A5.81NT-#1,A5.91NT-#2, ANDE2.01NT-#2SWING |
| | OPPOSITE THE DIRECTION OF EGRESS TRAVEL. |
| | |
| | 6.DOES THE PROPOSED PEDESTRIAN BRIDGE PLANNED TO |
| | PROVIDE ANY EXITING FROM THE BUILDING?IF EXITING IS |
| | PLANNED, PROVIDE EXIT SIGN AND EMERGENCY LIGHTING. |
| | |
| | 7.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS |
| | SHEET, INDICATE THE LOCATION OF THE FIRE |
| | EXTINGUISHER(S) AT DISTANCES TO SATISFY THE 75' TRAVEL |
| | DISTANCE REQUIREMENT. |
| | |
| | 8.DOES THE PROPOSED PEDESTRIAN BRIDGE RUN ACROSS A |
| | STREET OR ROAD?IF SO, THE PROPOSED HEIGHT OF THE |
| | LOWEST PORTION OF THE BRIDGE FROM THE FINISHED GRADE OF |
| | THE STREET OR ROAD.FIRE RESCUE ACCESS IS REQUIRED |
| | BELOW A STREET/ROAD BRIDGE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED ON |
| | THE PLANS |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | |
| | |