Plan Review Notes
Plan Review Notes For Permit 06110868
Permit Number 06110868
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-09 13:13:14*****DENIED*****
  
  
 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE
 SCOPE OF THE WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLODK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR
 THE VICINITY OF THE STRUCTURE (INCLUDING FIRE
 DAPARTMENT CONNECTIONS, FIRE HYDRANTS, AND FIRE
 LANES).
  
 3.WHERE THE BUILDING IS PROTECTED BY FIRE PROTECTION
 SYSTEMS, SYSTEMS SHALL REMAIN OPERATIONAL AT ALL TIMES
 DURING THE SCOPE OF WORK.WPBFR SHALL BE NOTIFIED
 IF/WHEN FIRE PROTECTION SYSTEM IS SHUT DOWN AND WHEN IT
 IS RETURNED TO SERVICE DUE TO THE SCOPE OF THE WORK.
  
 4.ON SHEETS FA0.01 AND FP0.01NT CORRECT VERBAGE FOR
 FIRE PROTECTION NOTES AS FOLLOWS:NFPA 1 2003, THE
 UNIFORM FIRE CODE; NFPA 14 2003 EDITION; NFPA 20 1999
 EDITION; NFPA 101 2003 EDITION (INCLUDING CHAPTER 11-
 HIGH RISE BUILDINGS) THE LIFE SAFETY CODE; FLORIDA FIRE
 PREVENTION CODE 2004 EDITION.
  
 5.PLEASE EXPLAIN WHY THE DOORS AS SEEN ON SHEETS
 A5.81NT-#1,A5.91NT-#2, ANDE2.01NT-#2SWING
 OPPOSITE THE DIRECTION OF EGRESS TRAVEL.
  
 6.DOES THE PROPOSED PEDESTRIAN BRIDGE PLANNED TO
 PROVIDE ANY EXITING FROM THE BUILDING?IF EXITING IS
 PLANNED, PROVIDE EXIT SIGN AND EMERGENCY LIGHTING.
  
 7.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OF THE FIRE
 EXTINGUISHER(S) AT DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 8.DOES THE PROPOSED PEDESTRIAN BRIDGE RUN ACROSS A
 STREET OR ROAD?IF SO, THE PROPOSED HEIGHT OF THE
 LOWEST PORTION OF THE BRIDGE FROM THE FINISHED GRADE OF
 THE STREET OR ROAD.FIRE RESCUE ACCESS IS REQUIRED
 BELOW A STREET/ROAD BRIDGE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED ON
 THE PLANS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved