2006-12-21 10:22:12** UNSAT **
  
 NORTH ELEVATOR TOWER AND HALLWAY LIGHTING.
  
 ** PLEASE SEE NOTES BELOW. PLEASE SEE THAT AS SOME
 INFORMATION ON PLANS IS NOT COMPLETE AT THIS TIME,
 REVIEW SOME ITEMS FOR CODE COMPLIANCE CAN NOT BE DONE.
  
 1) NOTE: PLEASE SHOW THE TRANSFORMER, SIZE ETC TO
 VERIFY OVER CURRENT PROTECTION ETC.
 PLEASE SEE MISSING CONDUCTORS FROM DP TO TRANSFORMER.
 SEE OTHER COMMENTS.
 106.1.2 FBC ADMIN SECTION.
 310.16, 240.4, 450.3 ETC.
  
 2) NOTE: PLEASE SUBMIT THE COMPLETE PANEL SCHEDULE FOR
 THE MAIN DISTRIBUTION PANEL. PLEASE SEE AS SOME
 CIRCUITS ARE SHOWN ON PLANS, THE LOAD, OVER CURRENT
 PROTECTION AND CONDUCTOR SIZES CAN NOT BE VERIFIED AT
 THIS TIME.
 240.4, 310.16, 408.4 ETC.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE CORRELATE CIRCUITING ON PLANS WITH THAT
 OF THE SUBMITTED PANEL SCHEDULE AND THE PANEL SCHEDULE
 FOR DP TO BE SUBMITTED.
 PLEASE SEE CIRCUIT(S) SHOWN TO A PANEL "DP1N"?
 408.4,
 FBC 106.1.2,ETC
  
 4) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE ATTACHMENT
 POINTS FOR THE NEW SERVICE PER 250.50.
 NEW FOOTING STEEL, EXISTING BUILDINGS GROUNDING
 ELECTRODE SYSTEM(AS NOTED ) FIRE SPRINKLER ETC.
  
 5) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION FOR
 THE NEW TRANSFORMER PER 250.20, 250.30 AND 250.50
  
 6) NOTE: PLEASE PLACE NOTE ON SITE PLANS ALONG WITH
 NOTE WHICH STATES THAT THE OLD CONDUIT FROM FPL IS
 BEING ABANDONED WHICH ALSO STATES ALL OLD, SEC'S SHALL
 BE REMOVED.
 FBC 106.1.2
  
 7) NOTE: PLEASE INDICATE ALL CONDUCTORS AND CONDUIT
 SIZES FROM THE NEW DP TO THE EXISTING SERVICE WHICH IS
 BEING RE-FED.
 PLEASE INDICATE THE NEW EQUIPMENT GROUNDING CONDUCTOR
 SIZE ALSO AS THIS/THESE CONDUITS ARE NOW AFTER THE
 FIRST MEANS OF DISCONNECT.
 250.6, 250.24B, 250.122.
  
 8) NOTE: PLEASE SEE PLANS ARE NOTING ON THE
 ARCHITECTURAL AND ELECTRICAL PLANS THAT THE CANOPY IS
 PART OF THIS PERMIT AND BEING FED FROM THIS ELECTRICAL
 SERVICE. PLEASE SEE THIS CANOPY IS PART OF THE MAIN
 BUILDING FOR 525 OKEECHOBEE WHICH IS NOT PART OF THIS
 LEGAL PERMIT APPLICATION.
 PLEASE ADJUST PLANS ACCORDINGLY AND PLEASE SEE BUILDING
 REVIEW COMMENTS.
 TABLE 603 OF THE FBC AND NEC FOR ELECTRICAL SYSTEMS
 FROM SEPARATE SERVICES AND BUILDINGS WHICH MAY NOT
 CROSS. 230.2
  
 9) NOTE: PLEASE PROVIDE COLOR CODING FOR 277/480V
 SYSTEM CONDUCTORS WHICH ARE EXISTING IN BUILDING ALSO.
 BROWN/PURPLE/YELLOW
  
 10) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR NEW HALLWAY
 FOR LIGHTING UNDER NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 2003 7.8 AND 7.9
  
 11) NOTE: PLEASE SEE LIGHTING WHICH SEEMS TO BE SHOWN
 OUTSIDE OF THE NEW PROPOSED CLOSED IN HALLWAY. AN
 ELEVATION/DETAIL WAS ATTEMPTED TO BE LOCATED SHOWING
 THIS AS IT IS UNCLEAR IF THESE NEW FIXTURES ARE BEING
 INSTALLED ABOVE PARKING SPACES?
 PLEASE SEE BUILDING REVIEW FOR POSSIBLE COMMENTS WITH
 RESPECT TO ANY DOOR SWINGS INTO EGRESS PATHS. PLEASE
 SEE SOME DOORS CLEARLY DO NOT SHOW THE FULL SWING OF
 180 DEGREES AND MAY OR MAY NOT AFFECT EGRESS PATH.
 THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS
 TIME.
  
 12) NOTE: PLEASE SEE THE "S" /STRUCTURAL SHEETS CONTAIN
 A "RUBBERSTAMP" FOR THE REQUIRED ORIGINAL SIGNATURE FOR
 THE ENGINEER OF RECORD. PLEASE KNOW THIS COMMENT HAS
 BEEN MADE ON MORE THAN TWO REVIEWS BEFORE THESE PLANS
 WERE DATED AND SUBMITTED. THIS COMMENT IS THAT THE
 ENGINEER MAY NOT AND SHALL NOT USE A RUBBER-STAMP IN
 LIEU OF THE REQUIRED ORIGINAL SIGNATURE. THIS HAS BEEN
 CONFIRMED WITH THE STATE OF FLORIDA BOARD OF ENGINEERS
 AND AT REQUEST OF THE BOARD OF ENGINEERS PLANS ARE
 BEING RETAINED AND WILL BE PLACED WITH OTHER PLANS
 WHICHWERE RETAINED FROM PREVIOUS SUBMITTED PLANS
 WHICH ALSO CONTAINED THE RUBBER-STAMP FOR SAID
 SIGNATURE.
 PLEASE KNOW THIS OFFICE HAS GIVEN MORE THAN SUFFICIENT
 INFORMATION AND NOTICE BASED ON THE REQUIREMENTS OF THE
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE.
 FS471.025 AND FAC 61G15-23.002
  
 13) NOTE: PLEASE SEE FEEDERS FROM THE DP TO THE
 ELEVATORS. PLEASE SEE THE CONDUCTORS SHOWN ARE RATED AT
 85A'S PER 310.16 AND 110.14 AND THE MAIN OVER CURRENT
 PROTECTION IS 200A'S? PLEASE SEE THE TERMINATION INTO
 THE ELEVATOR DISCONNECT IS INTO 110A OCP WHICH IS OK
 FOR MOTOR LOADS HOWEVER NOT ENOUGH INFORMATION FOR
 MOTORS, AND TYPE OF OCP IS PROVIDED IN ORDER TO REVIEW
 FOR CORRECT SIZING OF SAID CONDUCTORS AND OCP DEVICES.
 240.4
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  