| Date |
Text |
| 2006-12-21 10:22:12 | ** UNSAT ** |
| | |
| | NORTH ELEVATOR TOWER AND HALLWAY LIGHTING. |
| | |
| | ** PLEASE SEE NOTES BELOW. PLEASE SEE THAT AS SOME |
| | INFORMATION ON PLANS IS NOT COMPLETE AT THIS TIME, |
| | REVIEW SOME ITEMS FOR CODE COMPLIANCE CAN NOT BE DONE. |
| | |
| | 1) NOTE: PLEASE SHOW THE TRANSFORMER, SIZE ETC TO |
| | VERIFY OVER CURRENT PROTECTION ETC. |
| | PLEASE SEE MISSING CONDUCTORS FROM DP TO TRANSFORMER. |
| | SEE OTHER COMMENTS. |
| | 106.1.2 FBC ADMIN SECTION. |
| | 310.16, 240.4, 450.3 ETC. |
| | |
| | 2) NOTE: PLEASE SUBMIT THE COMPLETE PANEL SCHEDULE FOR |
| | THE MAIN DISTRIBUTION PANEL. PLEASE SEE AS SOME |
| | CIRCUITS ARE SHOWN ON PLANS, THE LOAD, OVER CURRENT |
| | PROTECTION AND CONDUCTOR SIZES CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | 240.4, 310.16, 408.4 ETC. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE CORRELATE CIRCUITING ON PLANS WITH THAT |
| | OF THE SUBMITTED PANEL SCHEDULE AND THE PANEL SCHEDULE |
| | FOR DP TO BE SUBMITTED. |
| | PLEASE SEE CIRCUIT(S) SHOWN TO A PANEL "DP1N"? |
| | 408.4, |
| | FBC 106.1.2,ETC |
| | |
| | 4) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE ATTACHMENT |
| | POINTS FOR THE NEW SERVICE PER 250.50. |
| | NEW FOOTING STEEL, EXISTING BUILDINGS GROUNDING |
| | ELECTRODE SYSTEM(AS NOTED ) FIRE SPRINKLER ETC. |
| | |
| | 5) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION FOR |
| | THE NEW TRANSFORMER PER 250.20, 250.30 AND 250.50 |
| | |
| | 6) NOTE: PLEASE PLACE NOTE ON SITE PLANS ALONG WITH |
| | NOTE WHICH STATES THAT THE OLD CONDUIT FROM FPL IS |
| | BEING ABANDONED WHICH ALSO STATES ALL OLD, SEC'S SHALL |
| | BE REMOVED. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE INDICATE ALL CONDUCTORS AND CONDUIT |
| | SIZES FROM THE NEW DP TO THE EXISTING SERVICE WHICH IS |
| | BEING RE-FED. |
| | PLEASE INDICATE THE NEW EQUIPMENT GROUNDING CONDUCTOR |
| | SIZE ALSO AS THIS/THESE CONDUITS ARE NOW AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | 250.6, 250.24B, 250.122. |
| | |
| | 8) NOTE: PLEASE SEE PLANS ARE NOTING ON THE |
| | ARCHITECTURAL AND ELECTRICAL PLANS THAT THE CANOPY IS |
| | PART OF THIS PERMIT AND BEING FED FROM THIS ELECTRICAL |
| | SERVICE. PLEASE SEE THIS CANOPY IS PART OF THE MAIN |
| | BUILDING FOR 525 OKEECHOBEE WHICH IS NOT PART OF THIS |
| | LEGAL PERMIT APPLICATION. |
| | PLEASE ADJUST PLANS ACCORDINGLY AND PLEASE SEE BUILDING |
| | REVIEW COMMENTS. |
| | TABLE 603 OF THE FBC AND NEC FOR ELECTRICAL SYSTEMS |
| | FROM SEPARATE SERVICES AND BUILDINGS WHICH MAY NOT |
| | CROSS. 230.2 |
| | |
| | 9) NOTE: PLEASE PROVIDE COLOR CODING FOR 277/480V |
| | SYSTEM CONDUCTORS WHICH ARE EXISTING IN BUILDING ALSO. |
| | BROWN/PURPLE/YELLOW |
| | |
| | 10) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR NEW HALLWAY |
| | FOR LIGHTING UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | PLEASE SEE NFPA-101 2003 7.8 AND 7.9 |
| | |
| | 11) NOTE: PLEASE SEE LIGHTING WHICH SEEMS TO BE SHOWN |
| | OUTSIDE OF THE NEW PROPOSED CLOSED IN HALLWAY. AN |
| | ELEVATION/DETAIL WAS ATTEMPTED TO BE LOCATED SHOWING |
| | THIS AS IT IS UNCLEAR IF THESE NEW FIXTURES ARE BEING |
| | INSTALLED ABOVE PARKING SPACES? |
| | PLEASE SEE BUILDING REVIEW FOR POSSIBLE COMMENTS WITH |
| | RESPECT TO ANY DOOR SWINGS INTO EGRESS PATHS. PLEASE |
| | SEE SOME DOORS CLEARLY DO NOT SHOW THE FULL SWING OF |
| | 180 DEGREES AND MAY OR MAY NOT AFFECT EGRESS PATH. |
| | THIS IS ONLY BEING NOTED BY THIS REVIEWER AT THIS |
| | TIME. |
| | |
| | 12) NOTE: PLEASE SEE THE "S" /STRUCTURAL SHEETS CONTAIN |
| | A "RUBBERSTAMP" FOR THE REQUIRED ORIGINAL SIGNATURE FOR |
| | THE ENGINEER OF RECORD. PLEASE KNOW THIS COMMENT HAS |
| | BEEN MADE ON MORE THAN TWO REVIEWS BEFORE THESE PLANS |
| | WERE DATED AND SUBMITTED. THIS COMMENT IS THAT THE |
| | ENGINEER MAY NOT AND SHALL NOT USE A RUBBER-STAMP IN |
| | LIEU OF THE REQUIRED ORIGINAL SIGNATURE. THIS HAS BEEN |
| | CONFIRMED WITH THE STATE OF FLORIDA BOARD OF ENGINEERS |
| | AND AT REQUEST OF THE BOARD OF ENGINEERS PLANS ARE |
| | BEING RETAINED AND WILL BE PLACED WITH OTHER PLANS |
| | WHICHWERE RETAINED FROM PREVIOUS SUBMITTED PLANS |
| | WHICH ALSO CONTAINED THE RUBBER-STAMP FOR SAID |
| | SIGNATURE. |
| | PLEASE KNOW THIS OFFICE HAS GIVEN MORE THAN SUFFICIENT |
| | INFORMATION AND NOTICE BASED ON THE REQUIREMENTS OF THE |
| | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE. |
| | FS471.025 AND FAC 61G15-23.002 |
| | |
| | 13) NOTE: PLEASE SEE FEEDERS FROM THE DP TO THE |
| | ELEVATORS. PLEASE SEE THE CONDUCTORS SHOWN ARE RATED AT |
| | 85A'S PER 310.16 AND 110.14 AND THE MAIN OVER CURRENT |
| | PROTECTION IS 200A'S? PLEASE SEE THE TERMINATION INTO |
| | THE ELEVATOR DISCONNECT IS INTO 110A OCP WHICH IS OK |
| | FOR MOTOR LOADS HOWEVER NOT ENOUGH INFORMATION FOR |
| | MOTORS, AND TYPE OF OCP IS PROVIDED IN ORDER TO REVIEW |
| | FOR CORRECT SIZING OF SAID CONDUCTORS AND OCP DEVICES. |
| | 240.4 |
| | FBC 106.1.2 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |