| Plan Review Notes For Permit 06110830 |
| Permit Number |
06110830 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-22 18:18:46 | | | | PROVISO | | | | | | WHERE THE SERVICE FROM ONE BUILDING IS FEEDING THE PUMP | | | DISCONNECT FOR ANOTHER BUILDING, CONNECTED TO A | | | DIFFERENT SERVICE, DO NOT MOUNT THE DISCONNECT TO THAT | | | STRUCTURE. M9OUNT AT PUMP LOCATION. | | | LOCATE A PLAQUE PER 225.37 AT THE DISCONNECT. | | | | | | 225.37 IDENTIFICATION. | | | WHERE A BUILDING OR STRUCTURE HAS ANY COMBINATION OF | | | FEEDERS, BRANCH CIRCUITS, OR SERVICES PASSING THROUGH | | | IT OR SUPPLYING IT, A PERMANENT PLAQUE OR DIRECTORY | | | SHALL BE INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT | | | DISCONNECT LOCATION DENOTING ALL OTHER SERVICES, | | | FEEDERS, OR BRANCH CIRCUITS SUPPLYING THAT BUILDING OR | | | STRUCTURE OR PASSING THROUGH THAT BUILDING OR STRUCTURE | | | AND THE AREA SERVED BY EACH. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|