| 2007-02-22 08:47:49 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT |
| | ON THE PLAN. 215.5,230.70(A)(1), 110.26. |
| | |
| | 2} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. THE INFORMATION FROM FPL WAS |
| | SUBMITTED BUT THE RATING OF THE EQUIPMENT WAS NOT |
| | INDICATED. |
| | |
| | 3} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 4} THE A/C LOAD IN THE CALCULATION IS INCORRECT. THE |
| | DESIGNER IS USING 220.83"THIS SECTION SHALL BE |
| | PERMITTED TO BE USED TO DETERMINE IF THE EXISTING |
| | SERVICE OR FEEDER IS OF SUFFICIENT CAPACITY TO SERVE |
| | ADDITIONAL LOADS." ARTICLE 220.82 SHOULD BE USED WHEN |
| | UNING AN OPTIONAL CALCULATION FOR A NEW SERVICE, |
| | THEREFORE THE A/C LOAD WOULD BE CALCULATED AT 65%. THE |
| | PROPOSED SERVICE IS SUFFICIENT, BUT CALCULATION NEEDS |
| | TO BE CORRECT FOR CLARITY AND COMPLIANCE. |
| | |
| | 5} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENSING |
| | UNIT) ON THE PLAN. ALSO SHOW COMPLIANCE WITH THE |
| | REQUIRED RECEPTACLE PER 210.63, DISCONNECT PER 440.14. |
| | |
| | 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. SEE REVIEWED |
| | PLAN FOR LOCATIONS. |
| | |
| | 7} BEDROOM #2 RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(B). |
| | |
| | 8} THE SMOKE ALARM CIRCUIT LISTED IN THE PANEL SCHEDULE |
| | MUST BE AFCI PER 210.12. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |