Plan Review Notes
Plan Review Notes For Permit 06110795
Permit Number 06110795
Review Stop B
Sequence Number 2
Notes
Date Text
2007-02-22 18:24:11BUILDING PROVISO
  
 THE INSULATION IN THE CEILING IS REQUIRED TO HAVE A
 MINIMUM R VALUE OF R-19 PER FBC 13-604.1.ABC.1.
  
 INSULATION ON RENOVATED WALLS SHALL COMPLY WITH FBC
 13-602.1.C.1.1 AND 13-602.1.C.2.
 THE INSULATION AT MASONRY WALLS IS REQUIRED TO HAVE AN
 R VALUE OF R-5.
 THE INSULATION AT WOOD FRAME WALLS IS REQUIRED TO HAVE
 AN R VALUE OF R-11 FOR 2 X 4 WALLS AND R-19 FOR 2 X 6
 WALLS.