| Plan Review Notes For Permit 06110795 |
| Permit Number |
06110795 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-22 18:24:11 | BUILDING PROVISO | | | | | | THE INSULATION IN THE CEILING IS REQUIRED TO HAVE A | | | MINIMUM R VALUE OF R-19 PER FBC 13-604.1.ABC.1. | | | | | | INSULATION ON RENOVATED WALLS SHALL COMPLY WITH FBC | | | 13-602.1.C.1.1 AND 13-602.1.C.2. | | | THE INSULATION AT MASONRY WALLS IS REQUIRED TO HAVE AN | | | R VALUE OF R-5. | | | THE INSULATION AT WOOD FRAME WALLS IS REQUIRED TO HAVE | | | AN R VALUE OF R-11 FOR 2 X 4 WALLS AND R-19 FOR 2 X 6 | | | WALLS. |
|