Plan Review Notes
Plan Review Notes For Permit 06110795
Permit Number 06110795
Review Stop M
Sequence Number 1
Notes
Date Text
2006-12-12 08:37:00*** DENIED ***
 1) MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER OF GLOBAL ENGINEERING CONSULTANAS, INC. AS
 THERE INFOMATION IS IN THE TITAL BLOCK, PER FAC
 61G15-23.002.
  
 2) THE ENGINEERING FIRM GLOBAL ENGINEERING NEEDS THEIR
 CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITAL BLOCK,
 PER FAC 61G15-23.002.
  
 3) ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.