| Plan Review Notes For Permit 06110795 |
| Permit Number |
06110795 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-12 08:37:00 | *** DENIED *** | | | 1) MECHANICAL PLANS NEED TO BE SIGNED AND SEALED BY THE | | | ENGINEER OF GLOBAL ENGINEERING CONSULTANAS, INC. AS | | | THERE INFOMATION IS IN THE TITAL BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 2) THE ENGINEERING FIRM GLOBAL ENGINEERING NEEDS THEIR | | | CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITAL BLOCK, | | | PER FAC 61G15-23.002. | | | | | | 3) ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL. | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|