Plan Review Notes
Plan Review Notes For Permit 06110795
Permit Number 06110795
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-06 08:55:09 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE DESCRIPTION ON THE APPLICATION DOES NOT INDICATE TO
 WHAT EXTENT THE ELECTRICAL SYSTEM IS TO BE AFFECTED BY
 THIS PERMIT.
 THEREFORE THIS REVIEW IS BASED ON A COMPLETE REWIRE.
 SINCE THERE IS NO LOAD CALCULATIONS OR RISER DIAGRAM,
 THIS REVIEW ASSUMES THE EXISTING SERVICE TO BE ADEQUATE
 AND THEREFORE NOT PART OF THIS APPLICATION.
  
 1}PLEASE PROVIDE A PANEL SCHEDULE(S) INDICATING
 OVERCURRENTAND CONDUCTOR SIZES PER 310.16,ALSO
 COMPLIANCE OF THE DEDICATED CIRCUIT ARTICLES FOR SMALL
 APPLIANCES, BATHROOMS ETC, PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 3} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH
 R313.1 RESIDENTIAL FLORIDA BUILDING CODE.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  