Plan Review Notes
Plan Review Notes For Permit 06110785
Permit Number 06110785
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-28 09:35:37DENIED BY BUILDING
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SUBMIT COVERSHEETS WITH STATE FL NUMBERS.
  
 2) PRODUCT APPROVAL FOR CERTAINTEED MODIFIED SYSTEM HAS
 BEEN REVISED BY NOA 03-0827.02. PLEASE SUBMIT THIS NOA
 AND STATE COVERSHEET WITH FL 479-R1.
  
 3) THE SBS MODIFIED SYSTEM THAT IS SPECIFIED HAS A
 MAXIMUM DESIGN PRESSURE OF -45 PSF WHICH IS TOO LOW FOR
 THE PERIMETER AND CORNER AREAS. LIMITATION #9 IS ALSO
 SPECIFIED, WHICH DOES NOT ALLOW THE PRESSURE TO BE
 INCREASE BY ENHANCED FASTENING. THEREFORE THIS SYSTEM
 IS NOT ACCEPTABLE.
 NOTE: LIMITATION NUMBER 7 DOES ALLOW ENHANCED
 FASTENING. HOWEVER, THE RAS 117 CALCULATIONS ARE
 REQUIRED TO BE PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT. SEE PAGE 30 OF THE NOA.
  
 4) THE MINIMUM SLOPE FOR ASPHALT SHINGLES IS TWO UNITS
 VERTICAL IN 12 UNITS HORIZONTAL AND TWO LAYERS OF
 UNDERLAYMENT IS REQUIRED FOR SLOPES LESS THAN 4/12 PER
 FBC 1507.2.8.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved