Plan Review Notes
Plan Review Notes For Permit 06110756
Permit Number 06110756
Review Stop P
Sequence Number 4
Notes
Date Text
2007-07-25 13:24:29REVISION DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 FUEL GAS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1: PLEASE INDICATE HOW THE NEW GAS WATER
 HEATER IS TO BE PROTECTED IN THE PROPOSED 1 CAR GARAGE
 PER FBC-2004 FUEL GAS, SECTION 303.4 PROTECTION FROM
 PHYSICAL DAMAGE. APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO PHYSICAL DAMAGE UNLESS
 PROTECTED BY APPROVED BARRIERS MEETING THE REQUIREMENTS
 OF THE FLORIDA FIRE PREVENTION CODE. FOR EXAMPLE, AN
 APPLIANCE (WATER HEATER) INSTALLED IN A GARAGE MIGHT BE
 SUBJECT TO VEHICLE IMPACT. BARRIERS MUST BE APPROVED
 AND STRONG ENOUGH TO RESIST THE TYPE OF IMPACT
 ANTICIPATED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731