| 2007-07-20 15:10:14 | REVISION DENIED BY BUILDING |
| | |
| | 1) THE VALUE OF THE PROJECT HAS INCREASED SIGNIFICANTLY |
| | DUE TO THE ADDITIONAL SCOPE OF WORK. PLEASE INDICATE |
| | THE COSTS OF THE ADDITIONAL WORK SO THAT THE VALUE OF |
| | THE JOB CAN BE ADJUSTED. ADDITIONAL PERMIT FEES WILL BE |
| | ASSESSED. |
| | |
| | 2)SPECIFY HOW THE GAS WATER HEATER IN THE GARAGE WILL |
| | BE PROTECTED FROM MECHANICAL DAMAGE AS REQUIRED BY FBC |
| | MECHANICAL 303.4. |
| | |
| | 3)SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION. |
| | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM |
| | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. |
| | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL |
| | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1-3 / 8 |
| | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE |
| | STEEL DOORS NOT LESS THAN 1 3 / 8 INCHES (35 MM) THICK, |
| | OR 20-MINUTE FIRE-RATED DOORS. - |
| | |
| | 4)SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. |
| | THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND |
| | ITS ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM) |
| | GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES |
| | BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL |
| | HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH |
| | (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE |
| | SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE |
| | SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY |
| | NOT LESS THAN 1/2-INCH (12.7 MM) GYPSUM BOARD OR |
| | EQUIVALENT. |
| | |
| | 5) REVISE THE ROOF SHEATHING FASTENING NOTES ON SHEET 2 |
| | TO COMPLY WITH FBC R803.2.3.1 OF 2006 REVISIONS TO 2004 |
| | FBC RESIDENTIAL CODE. WHICH REQUIRES 8D RING-SHANK |
| | NAILS AT 6 INCHES ON CENTER IN ROOF ZONES 1 AND 2 AND 4 |
| | INCHES ON CENTER IN ROOF ZONE 3 (CORNERS) IN ACCORDANCE |
| | WITH FIGURE R803.2.3.1. |
| | |
| | 6) THE SIMPSON CONNECTOR CATALOG REQUIRES A MINIMUM 12" |
| | EMBED FOR THE MGT 5/8" EPOXY SET THREADED ROD. PLEASE |
| | REVISE CONNECTOR NOTE ON SHEET 2. |
| | |
| | 7) SPECIFY THE GARAGE DOOR WINDLOAD PRESSURES ON THE |
| | PLANS. SEE SHEET 1. |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. THE SIGNED AND SEALED |
| | LETTER SUBMITTED IS NOT SPECIFIC AND NOT ACCEPTABLE. |
| | |
| | - ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |