| Date |
Text |
| 2006-12-19 16:51:56 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE PLEASE REFERENCE |
| | THE ATTACHED CORRECTED SANITARY RISER DIAGRAM IN RED |
| | INK FOR THE RESUBMITTAL: |
| | |
| | 1. SHEET 1, PER FBC-2003 CHAPTER 1, SEC. 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS. |
| | NOTE: NOT ALL TRAPS ARE SIZED AND THE DISH WASHER IS |
| | MISSING. |
| | |
| | 2. SHEET 1, PER FBC-2004 PLUMBING, SEC. 917.4 THE AIR |
| | ADMITTANCE VALVE IS INDICATED WRONG. THE AIR ADMITTANCE |
| | VALVE SHALL BE LOCATED A MINIUM OF 4 INCHES ABOVE THE |
| | HORIZONTAL BRANCH DRAIN OR FIXTURE DRAIN BEING VENTED. |
| | |
| | 3. SHEET 1, PER FBC-2004 PLUMBING, THE FOLLOWING IS |
| | REQUIRED FOR THE WASHING MACHINE. |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE STANDPIPE ON DRAWING. |
| | (C)708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| | CLEANOUTS. CLEANOUT FOR THE WASHING MACHINE TO BE AT |
| | FOUR FEET ABOVE FINNISH FLOOR AND INDICATED AS SUCH ON |
| | THE RESUBMITTAL. |
| | |
| | 4. PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | NOTE: ON SHEET 1, SANITARY RISER DIAGRAM ALL |
| | BATHROOM-GROUPS ARE NON CODE COMPLIANT. PLEASE |
| | REFERENCE THE ATTACHED CORRECTED SANITARY RISER DIAGRAM |
| | IN RED INK FOR THE RESUBMITTAL. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |