Plan Review Notes
Plan Review Notes For Permit 06110756
Permit Number 06110756
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-19 16:51:56DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE PLEASE REFERENCE
 THE ATTACHED CORRECTED SANITARY RISER DIAGRAM IN RED
 INK FOR THE RESUBMITTAL:
  
 1. SHEET 1, PER FBC-2003 CHAPTER 1, SEC. 106.3.5.4
 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
 NOTE: NOT ALL TRAPS ARE SIZED AND THE DISH WASHER IS
 MISSING.
  
 2. SHEET 1, PER FBC-2004 PLUMBING, SEC. 917.4 THE AIR
 ADMITTANCE VALVE IS INDICATED WRONG. THE AIR ADMITTANCE
 VALVE SHALL BE LOCATED A MINIUM OF 4 INCHES ABOVE THE
 HORIZONTAL BRANCH DRAIN OR FIXTURE DRAIN BEING VENTED.
  
 3. SHEET 1, PER FBC-2004 PLUMBING, THE FOLLOWING IS
 REQUIRED FOR THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE ON DRAWING.
 (C)708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. CLEANOUT FOR THE WASHING MACHINE TO BE AT
 FOUR FEET ABOVE FINNISH FLOOR AND INDICATED AS SUCH ON
 THE RESUBMITTAL.
  
 4. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: ON SHEET 1, SANITARY RISER DIAGRAM ALL
 BATHROOM-GROUPS ARE NON CODE COMPLIANT. PLEASE
 REFERENCE THE ATTACHED CORRECTED SANITARY RISER DIAGRAM
 IN RED INK FOR THE RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved