| 2006-12-13 12:24:14 | BUILDING PLAN REVIEW |
| | PERMIT: 06110744 |
| | ADD: 444 W RAILROAD AVSUITE# 400 |
| | CONT:PBM DEVELOPMENT |
| | TEL: (561)715-1800 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) ADDITIONAL INFORMATION REQUIRED. 106.1.2* |
| | THIS COMMENT SHALL DEAL WITH THE EXIT ACCESS CORRIDOR. |
| | THE SHELL PERMIT REMOVED THE EXIT ACCESS CORRIDORS |
| | FROM |
| | |
| | THEIR SCOPE OF WORK. |
| | EITHER ONE OF TWO THINGS WILL NEED TO HAPPEN. UNDER THE |
| | SHELL PERMIT PUT A REVISION IN TFOR THE FOURTH FLOOR |
| | CORRIDORS OR MAKE THE FOURTH FLOOR CORRIDORS PART OF |
| | THIS PERMIT. |
| | SHEET A-02 INDICATES THAT THE EXIT ACCESS CORRIDORS ARE |
| | EXISTING. |
| | |
| | 3) SHEET A-02THE FOLLOWING DOORS ARE MISSING THE 18" |
| | ON |
| | THE LATCH/ PULL SIDEOF THE DOOR: 404, 408,409 & 416. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL.11-4.4.4 PROTRUDING OBJECTS. OBJECTS |
| | PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) WITH |
| | THEIR |
| | LEADING EDGES BETWEEN 27 INCHES AND 80 INCHES (685 MM |
| | AND 2030 MM) |
| | ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4 |
| | INCHES (102 MM) |
| | INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES |
| | [SEE FIGURE 11-8 (A)]. |
| | OBJECTS MOUNTED WITH THEIR LEADING EDGES AT OR BELOW 27 |
| | INCHES (685 MM) |
| | ABOVE THE FINISHED FLOOR MAY PROTRUDE ANY AMOUNT [SEE |
| | FIGURE 11-8 (A) AND |
| | FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON |
| | POSTS OR PYLONS MAY |
| | OVERHANG 12 INCHES (305 MM) MAXIMUM FROM 27 INCHES TO |
| | 80 INCHES |
| | (685 MM TO 2030 MM) ABOVE THE GROUND OR FINISHED FLOOR |
| | [SEE FIGURE 11-8 (C) |
| | AND FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT |
| | REDUCE THE CLEAR WIDTH OF AN |
| | ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE 11-8 |
| | (E)]. |
| | 1003.3.3 HORIZONTAL PROJECTIONS. |
| | ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE |
| | THAN 4 INCHES (102 MM) |
| | WHEN THEY ARE LOCATED BETWEEN 27 AND 80 INCHES (686 AND |
| | 2032 MM) ABOVE |
| | THE FLOOR. HANDRAILS CAN PROJECT UP TO 4? INCHES (114 |
| | MM) FROM THE WALL. |
| | |
| | 4) SHEET A-02 RESTROOM 407, PLEASE PROVIDE TURNING |
| | RADIUS WITHIN THE RESTROOM. |
| | 11-4.2.3 WHEELCHAIR TURNING SPACE. THE SPACE REQUIRED |
| | FOR A WHEELCHAIR TO M |
| | AKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES |
| | (1525 MM) DIAMETER [SEE |
| | FIGURE 11-3 (A)] OR A T-SHAPED SPACE [SEE FIGURE 11-3 |
| | (B)]. |
| | |
| | 5) SHEET A-02 RESTROOM PLEASE INDICATE THE CLEAR FLOOR |
| | SPACE REQUIRED FOR THE PLUMBING FIXTURES. 11-4.22.2 |
| | DOORS. ALL DOORS TO |
| | ACCESSIBLE TOLIET ROOMS SHALL COMPLY |
| | WITH 11-4.13. DOORS SHALL NOT SWING INTO |
| | CLEAR FLOOR SPACE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 6) SHEETA-06 BREAK ROOM THE PLANS DO NOT INDICATE A |
| | SINK BUT THE PLUMBING ISOMETRIC DOES. |
| | PLEASE PROVIDE CABINET DETAILSCOMPLYING WITH: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 7)SHEET A-05 INDICATES VARIOUS DETAILS WITH CROWN |
| | MOULDINGS, NO MENTION OF TYPE OF MATERIAL, |
| | 2604.1 GENERAL. |
| | PLASTIC MATERIALS INSTALLED AS INTERIOR FINISH OR TRIM |
| | SHALL COMPLY WITH CHAPTER 8 . FOAM PLASTICS SHALL ONLY |
| | BE INSTALLED AS INTERIOR FINISH WHERE APPROVED IN |
| | ACCORDANCE WITH THE SPECIAL PROVISIONS OF SECTION |
| | 2603.8 . FOAM PLASTICS THAT ARE USED AS INTERIOR FINISH |
| | SHALL ALSO MEET THE FLAME SPREAD INDEX REQUIREMENTS FOR |
| | INTERIOR FINISH IN ACCORDANCE WITH CHAPTER 8 . FOAM |
| | PLASTICS INSTALLED AS INTERIOR TRIM SHALL COMPLY WITH |
| | SECTION 2604.2 . |
| | TRIM |
| | 2604.2 INTERIOR TRIM . |
| | FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH |
| | SECTIONS 2604.2.1 THROUGH 2604.2.4 . |
| | |
| | 2604.2.1 DENSITY. |
| | THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20 |
| | PCF (320 KG/M 3 ). |
| | |
| | 2604.2.2 THICKNESS. |
| | THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5 |
| | INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES |
| | (204 MM). |
| | |
| | 2604.2.3 AREA LIMITATION. |
| | THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10 |
| | PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY |
| | ROOM OR SPACE. |
| | |