| Plan Review Notes For Permit 06110718 |
| Permit Number |
06110718 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 06:59:05 | DENIED BY BUILDING | | | | | | 1) SPECIFY THE TYPE OF FASTENER AND THE AMOUNT REQUIRED | | | TO ATTACH THE LARGE ENTRANCE AWNING TO THE CONCRETE | | | FOOTERS. SPECIFY WHAT THE MINIMUM REQUIREMENT FOR THE | | | FOOTER OR SLAB TO WHICH IT WILL BE ANCHORED. | | | | | | 2) SPECIFY THE NUMBER AND LENGTH/EMBED DEPTH OF THE LAG | | | BOLTS USED TO ATTACH THE WINDOW AWNINGS TO THE | | | BUILDING. SPECIFY THE TYPE OF STRUCTURAL SUBSTRATE TO | | | WHICH THEY WILL BE ANCHORED. | | | | | | 3)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|